Power

XF CONPREX ®
Single or multiconductor - XLPE/PVC - 0.6/1kV - 90ºC - IRAM 2178-1
Download PDF datasheet

Attributes

  • Flexible Stranded Conductors
  • Industrial Applications
  • Sequentially Marked
  • Fire-retardant

Certifications

Applications

Suitable for overhead trays, direct earth burial or duct-buried installations.
Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations, etc.

features

Temperature rating: 90ºC (operating), 130°C (overload) and 250°C (short circuit).
Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC
Construction requirements: As per IEC 60502-1 / IRAM 2178-1.
Fire requirements: IEC 60332-3-24 / IRAM NM IEC 60332-3-24 - Fire-retardancy.
Conductor requirements: As per IEC 60228 / IRAM NM 280.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: XLPE (crosslinked polyethylene).
Identification:

- 1 Conductors:        
- 2 Conductors:        
- 3 Conductors:        
- 4 Conductors:        

Sheath: Black PVC; fire-retardant.

As from July 1st 2018 this cable family will be commercialized with standard BLACK sheath.

optionals

Armour: Double aluminium tape spiral wrap (in single-conductor cables) and helical wire wrap or double zinc-plated steel tape spiral wrap (in multiconductor cables).

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) or 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: C or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.

Tables

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Armoured
Code Outside diameter mm Weight kg/km Code Under armour diameter mm Outside diameter mm Weight kg/km
1x1 XF 0110 Ne 5.4 37 -- -- -- --
1x1.5 XF 0115 Ne 5.8 44 -- -- -- --
1x2.5 XF 0125 Ne 6.2 54 -- -- -- --
1x4 XF 0140 Ne 6.7 71 -- -- -- --
1x6 XF 0160 Ne 7.3 92 -- -- -- --
1x10 XF 1100 Ne 8.4 137 -- -- -- --
1x16 XF 1160 Ne 9.3 190 XF 1160 DNe 13 18.6 517
1x25 XF 1250 Ne 10.9 281 XF 1250 DNe 13 18.6 569
1x35 XF 1350 Ne 11.9 372 XF 1350 DNe 13 18.6 634
1x50 XF 1500 Ne 13.5 509 XF 1500 DNe 13 18.6 721
1x70 XF 1700 Ne 15.7 707 XF 1700 DNe 13 18.6 843
1x95 XF 1950 Ne 17.9 917 XF 1950 DNe 16.9 22.5 1163
1x120 XF 11200 Ne 19.5 1232 XF 11200 DNe 18.5 24.1 1498
1x150 XF 11500 Ne 22.3 1437 XF 11500 DNe 21.1 26.7 1725
1x185 XF 11850 Ne 24.1 1734 XF 11850 DNe 22.9 28.5 2044
1x240 XF 12400 Ne 27.5 2285 XF 12400 DNe 26.1 31.7 2621
1x300 XF 13000 Ne 30.7 2838 XF 13000 DNe 29.1 34.9 3212
1x400 XF 14000 Ne 34.4 3665 XF 14000 DNe 33 39 4119
1x500 XF 15000 Ne 38.2 4605 XF 15000 DNe 36.6 42.8 5107
1x630 XF 16300 Ne 43.7 6108 XF 16300 DNe 41.7 48.3 6678
2x1 XF 0210 Ne 8.3 86 XF 0210 HNe 7.3 12.5 269
2x1.5 XF 0215 Ne 8.9 103 XF 0215 HNe 7.9 13.1 299
2x2.5 XF 0225 Ne 9.8 131 XF 0225 HNe 8.8 14 347
2x4 XF 0240 Ne 10.7 171 XF 0240 HNe 9.7 14.9 405
2x6 XF 0260 Ne 12 226 XF 0260 HNe 11 16.2 487
2x10 XF 2100 Ne 14.1 340 XF 2100 FNe 13.1 17.9 600
2x16 XF 2160 Ne 18.6 589 XF 2160 FNe 15 19.8 770
2x25 XF 2250 Ne 21.8 849 XF 2250 FNe 18.2 23 1065
2x35 XF 2350 Ne 23.8 1087 XF 2350 FNe 20.2 25 1326
2x50 XF 2500 Ne 27 1458 XF 2500 FNe 23.4 28.2 1733
2x70 XF 2700 Ne 31.4 2012 XF 2700 FNe 27.8 32.8 2350
2x95 XF 2950 Ne 36.2 2646 XF 2950 FNe 32.2 37.4 3019
2x120 XF 21200 Ne 39.6 3444 XF 21200 FNe 35.4 41.6 4131
2x150 XF 21500 Ne 45 4122 XF 21500 FNe 40.6 47.2 4928
2x185 XF 21850 Ne 49.2 4994 XF 21850 FNe 44.6 51.4 5876
2x240 XF 22400 Ne 56 6537 XF 22400 FNe 51 58.2 7543
2x300 XF 23000 Ne 62.8 8172 XF 23000 FNe 57.4 64.8 9271

Cables are letter coded to the type of protection they include.
Here,D = double aluminium tape spiral wrap.
F = double zinc-plated steel tape spiral wrap.
H = zinc-plated steel wire serve.

Electrical Characteristics



Nominal cross-section
sq mm
Electrical resistance at 90ºC in AC Ohm/km Inductive reactance at 50hz Current-carrying capacity in free air (2) Current-carrying capacity in earth (3)
Single-conductor (1) Ohm/km Multiconductor cables
Ohm/km
1x (1) Ampere 2x   Ampere 3x (4) Ampere 1x (1) Ampere 2x  Ampere 3x (4) Ampere
1 24.86 0.166 0.107 N/A N/A N/A N/A N/A N/A
1.5 16.96 0.157 0.100 19.0 22.8 20.0 32.3 32.3 27.6
2.5 10.18 0.145 0.093 25.7 31.4 27.6 42.8 43.7 37.1
4 6.31 0.137 0.088 34.2 42.8 36.1 55.1 57.0 48.5
6 4.21 0.128 0.083 44.7 54.2 46.6 69.4 72.2 60.8
10 2.44 0.118 0.078 61.8 74.1 64.6 93.1 96.9 82.7
16 1.54 0.112 0.075 82.7 99.8 86.5 120.7 128.3 107.4
25 0.995 0.109 0.075 121.6 128.3 109.3 156.8 166.3 140.6
35 0.707 0.105 0.073 152.0 159.6 136.8 188.1 199.5 168.2
50 0.493 0.102 0.073 187.2 194.8 166.3 220.4 238.5 198.6
70 0.348 0.098 0.071 241.3 249.9 212.8 270.8 291.7 243.2
95 0.264 0.096 0.070 295.5 304.0 257.5 325.9 350.6 292.6
120 0.207 0.095 0.070 345.8 354.4 299.3 370.5 399.0 333.5
150 0.166 0.094 0.070 400.9 408.5 344.9 415.2 448.4 373.4
185 0.137 0.094 0.070 460.8 468.4 394.3 470.3 508.3 424.7
240 0.105 0.092 0.069 548.2 553.9 464.6 547.2 591.9 493.1
300 0.0853 0.091 0.069 636.5 640.3 536.8 621.3 668.8 558.6
400 0.0666 0.090 -- 750.5 -- -- 709.7 -- --
500 0.0547 0.090 -- 862.6 -- -- 824.6 -- --
630 0.0438 0.089 -- 994.7 -- -- 941.5 -- --

(1) Three single-conductor cables in one plane in contact with each other.
(2) Cables installed in free air at 40ºC according to IEC 364-5-523.
(3) Cables directly buried in earth at a ground temperature of 25ºC with ground specific thermal resistivity of 1K.m/W.
(4) The values also apply to 4-conductor and 5-conductor cables.
For further information about current-carrying capacity values and types of installations refer to IEC 364-5-523 and the regulations for electrical installations in buildings defined by Argentina's Electrotechnical Association (in Spanish, "Reglamentación para la ejecución de Instalaciones eléctricas en inmuebles", part 7 section 771).

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Armoured
Code Outside diameter mm Weight kg/km Code Under armour diameter mm Outside diameter mm Weight kg/km
3x1 XF 0310 Ne 8.7 97 XF 0310 HNe 7.7 12.9 290
3x1.5 XF 0315 Ne 9.4 120 XF 0315 HNe 8.4 13.6 326
3x2.5 XF 0325 Ne 10.3 154 XF 0325 HNe 9.3 14.5 379
3x4 XF 0340 Ne 11.3 206 XF 0340 HNe 10.3 15.5 452
3x6 XF 0360 Ne 12.7 277 XF 0360 HNe 11.7 16.9 552
3x10 XF 3100 Ne 15 427 XF 3100 FNe 14 18.8 700
3x16 XF 3160 Ne 19.6 722 XF 3160 FNe 16 20.8 915
3x25 XF 3250 Ne 23.1 1056 XF 3250 FNe 19.5 24.3 1287
3x35 XF 3350 Ne 25.3 1377 XF 3350 FNe 21.7 26.5 1632
3x50 XF 3500 Ne 28.7 1860 XF 3500 FNe 25.1 29.9 2154
3x70 XF 3700 Ne 34.1 2630 XF 3700 FNe 30.3 35.3 2981
3x95 XF 3950 Ne 38.6 3387 XF 3950 FNe 34.6 40 3805
3x120 XF 31200 Ne 42.2 4467 XF 31200 FNe 38 44.4 5223
3x150 XF 31500 Ne 48.7 5363 XF 31500 FNe 44.1 50.9 6235
3x185 XF 31850 Ne 52.7 6440 XF 31850 FNe 47.9 54.9 7387
3x240 XF 32400 Ne 60.5 8517 XF 32400 FNe 55.3 62.7 9604
3x300 XF 33000 Ne 67.3 10546 XF 33000 FNe 61.7 69.5 11758
4x1 XF 0410 Ne 9.4 114 XF 0410 HNe 8.4 13.6 320
4x1.5 XF 0415 Ne 10.1 140 XF 0415 HNe 9.1 14.3 361
4x2.5 XF 0425 Ne 11.2 184 XF 0425 HNe 10.2 15.4 428
4x4 XF 0440 Ne 12.3 251 XF 0440 HNe 11.3 16.5 516
4x6 XF 0460 Ne 13.9 341 XF 0460 HNe 12.9 18.1 639
4x10 XF 4100 Ne 16.4 527 XF 4100 FNe 15.4 20.2 826
4x16 XF 4160 Ne 21.3 884 XF 4160 FNe 17.7 22.5 1096
3x25+1x16 XF 2516 Ne 24.2 1198 XF 2516 FNe 20.6 25.4 1441
3x35+1x16 XF 3516 Ne 26 1501 XF 3516 FNe 22.4 27.2 1764
3x50+1x25 XF 5025 Ne 29.9 2069 XF 5025 FNe 26.3 31.3 2389
3x70+1x35 XF 7035 Ne 35.1 2898 XF 7035 FNe 31.3 36.5 3277
3x95+1x50 XF 9550 Ne 40.1 3791 XF 9550 FNe 35.9 42.1 4488
3x120+1x70 XF 12070 Ne 44.6 5079 XF 12070 FNe 40.2 46.8 5877
3x150+1x70 XF 15070 Ne 49.9 5878 XF 15070 FNe 45.3 52.1 6774
3x185+1x95 XF 18595 Ne 54.7 7177 XF 18595 FNe 49.7 56.9 8158
3x240+1x120 XF 240120 Ne 62.3 9495 XF 240120 FNe 56.9 64.5 10614
3x300+1x150 XF 300150 Ne 69.7 11691 XF 300150 FNe 63.9 71.7 12912

Cables are letter coded to the type of protection they include.
F = double zinc-plated steel tape spiral wrap.
H = zinc-plated steel wire serve. 