Power

RP FUEGAR ®
Single or multiconductor - 0.6/1kV - 90ºC - IEC 60502-1 - IRAM 62266
Fire-resistant
Download PDF datasheet

Attributes

  • Low Smoke
  • Indoor Public Places
  • Industrial Applications
  • Halogen free
  • Fire-retardant
  • Fire-resistant

Certifications

Applications

Emergency lighting circuits, ventilation circuits, and water pumps.
Suitable for preserving electrical integrity in fire conditions in places like distilleries, petrochemical plants, shipyards, etcetera.

features

Temperature rating: 90ºC (operating),130°C (overload), 250°C (short circuit).
Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC
Construction requirements: As per IEC 60502-1 / IRAM 62266
Fire requirements: As per IEC 60332-3-24 / IRAM NM IEC 60332-3-24 - Fire-retardancy.
Fire-resistance requirements: As per IEC 60331-21 (at 750ºC for 90 minutes).Optional: IEC 60331-1/2 (830ºC) / BS6387 CWZ (950ºC). See alternatives: Extended circuit integrity.
Halogen content requirements: As per IEC 60754-1/2 - Non-halogen.
Smoke opacity requirements: As per IEC 61034 -Smoke density.
Toxicity requirements: As per NES 713 / CEI 20-37 - Non-toxic.
Conductor requirements: As per IEC 60228 / IRAM NM 280.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: Mica tape helical wrap plus extruded XLPE (crosslinked polyethylene)
Identification:

- 1 Conductors:        
- 2 Conductors:        
- 3 Conductors:        
- 4 Conductors:        

Sheath: LSZH-HFFR (Low Smoke, Zero Halogen - Halogen-Free, Flame-Retardant); orange.

optionals

Armour: Double aluminium tape spiral wrap (in single-conductor cables) and helical wire wrap or double zinc-plated steel tape spiral wrap (in multiconductor cables).

installation

Assembly: Minimum bend radius is 7xOD (in unarmoured versions) or 12xOD (in armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.
Identification: O
ne of the conductors in each insulated cable is marked green/yellow. Other colours such as black, grey, blue, etc. may be used for identification.
Extended circuit integrity: This is a special design engineered to comply with highly demanding fire tests. Special construction is compliant with the following standards and tests:
BS 6387 standard:
Category C: Direct exposure to fire for 3 hours at 950ºC.
Category W: Direct exposure to fire for 15 minutes at 650ºC + Exposure to water spray for a further 15 minutes.
Category Z: Direct exposure to fire for 15 minutes at 950ºC + Mechanical shock simulated by striking the cable specimen against the backing panel every 30 seconds.
IEC 60331-1/2 standard: Direct exposure to fire for 2 hours at 830ºC +Mechanical shock simulated by striking the cable specimen against the backing panel every 5 minutes.

Tables

Dimensions & Weight



Conductors x section
N° x sq mm
Code Outside diameter
mm
Weight kg/km Conductors x section N° x sq mm Code Outside diameter
mm
Weight kg/km
1x1 RP 0110 6.2 47 2x300 RP 23000 64.4 8341
1x1.5 RP 0115 6.5 54 3x1 RP 0310 10.4 132
1x2.5 RP 0125 7.0 66 3x1.5 RP 0315 11.1 158
1x4 RP 0140 7.4 82 3x2.5 RP 0325 12.0 195
1x6 RP 0160 8.1 106 3x4 RP 0340 13.0 252
1x10 RP 1100 9.1 151 3x6 RP 0360 14.4 329
1x16 RP 1160 10.1 208 3x10 RP 3100 16.7 486
1x25 RP 1250 11.7 301 3x16 RP 3160 21.3 800
1x35 RP 1350 12.7 393 3x25 RP 3250 24.8 1147
1x50 RP 1500 14.3 532 3x35 RP 3350 26.9 1469
1x70 RP 1700 16.5 732 3x50 RP 3500 30.4 1968
1x95 RP 1950 18.7 943 3x70 RP 3700 35.7 2744
1x120 RP 11200 20.3 1259 3x95 RP 3950 40.3 3518
1x150 RP 11500 23.1 1464 3x120 RP 31200 43.9 4606
1x185 RP 11850 24.9 1762 3x150 RP 31500 50.3 5502
1x240 RP 12400 28.3 2311 3x185 RP 31850 54.4 6596
1x300 RP 13000 31.5 2862 3x240 RP 32400 62.1 8667
1x400 RP 14000 35.2 3685 3x300 RP 33000 69.0 10711
1x500 RP 15000 39.0 4619 4x1 RP 0410 11.3 155
1x630 RP 16300 44.5 6110 4x1.5 RP 0415 12.0 184
2x1 RP 0210 9.9 117 4x2.5 RP 0425 13.1 233
2x1.5 RP 0215 10.5 137 4x4 RP 0440 14.2 304
2x2.5 RP 0225 11.4 168 4x6 RP 0460 15.8 402
2x4 RP 0240 12.3 212 4x10 RP 4100 18.3 598
2x6 RP 0260 13.6 272 4x16 RP 4160 23.2 977
2x10 RP 2100 15.7 394 3x25+1x16 RP 2516 26.1 1301
2x16 RP 2160 20.2 660 3x35+1x16 RP 3516 27.9 1609
2x25 RP 2250 23.4 931 3x50+1x25 RP 5025 31.8 2190
2x35 RP 2350 25.4 1177 3x70+1x35 RP 7035 37.0 3034
2x50 RP 2500 28.6 1558 3x95+1x50 RP 9550 42.0 3939
2x70 RP 2700 33.0 2123 3x120+1x70 RP 12070 46.4 5232
2x95 RP 2950 37.8 2770 3x150+1x70 RP 15070 51.8 6044
2x120 RP 21200 41.2 3576 3x185+1x95 RP 18595 56.6 7351
2x150 RP 21500 46.6 4266 3x240+1x120 RP 240120 64.2 9675
2x185 RP 21850 50.8 5146 3x300+1x150 RP 300150 71.6 11871
2x240 RP 22400 57.6 6699 --- --- --- ---

Electrical Characteristics



Nominal cross-section
sq mm
Electrical resistance at 90ºC in AC Ohm/km Inductive reactance at 50hz Current-carrying capacity  in free air (2) Current-carrying capacity in earth (3)
Single- conductor (1) Ohm/km Multiconductor Ohm/km 1x (1) Ampere 2x  Ampere 3x (4) Ampere 1x (1) Ampere 2x  Ampere 3x (4) Ampere
1 24.86 0.166 0.107 N/A N/A N/A N/A N/A N/A
1.5 16.96 0.157 0.100 19.0 22.8 20.0 32.3 32.3 27.6
2.5 10.18 0.145 0.093 25.7 31.4 27.6 42.8 43.7 37.1
4 6.31 0.137 0.088 34.2 42.8 36.1 55.1 57.0 48.5
6 4.21 0.128 0.083 44.7 54.2 46.6 69.4 72.2 60.8
10 2.44 0.118 0.078 61.8 74.1 64.6 93.1 96.9 82.7
16 1.54 0.112 0.075 82.7 99.8 86.5 120.7 128.3 107.4
25 0.995 0.109 0.075 121.6 128.3 109.3 156.8 166.3 140.6
35 0.707 0.105 0.073 152.0 159.6 136.8 188.1 199.5 168.2
50 0.493 0.102 0.073 187.2 194.8 166.3 220.4 238.5 198.6
70 0.348 0.098 0.071 241.3 249.9 212.8 270.8 291.7 243.2
95 0.264 0.096 0.070 295.5 304.0 257.5 325.9 350.6 292.6
120 0.207 0.095 0.070 345.8 354.4 299.3 370.5 399.0 333.5
150 0.166 0.094 0.070 400.9 408.5 344.9 415.2 448.4 373.4
185 0.137 0.094 0.070 460.8 468.4 394.3 470.3 508.3 424.7
240 0.105 0.092 0.069 548.2 553.9 464.6 547.2 591.9 493.1
300 0.0853 0.091 0.069 636.5 640.3 536.8 621.3 668.8 558.6
400 0.0666 0.090 -- 750.5 -- -- 709.7 -- --
500 0.0547 0.090 -- 862.6 -- -- 824.6 -- --
630 0.0438 0.089 -- 994.7 -- -- 941.5 -- --

(1) Three single-conductor cables in one plane in contact with each other.
(2) Cables installed in free air at 40ºC according to IEC 364-5-523.
(3) Cables directly buried in earth at a ground temperature of 25ºC with ground specific thermal resistivity of 1K.m/W.
(4) The values also apply to 4-conductor and 5-conductor cables.
For further information about current-carrying capacity values and types of installations refer to IEC 364-5-523 and the regulations for electrical installations in buildings defined by Argentina's Electrotechnical Association (in Spanish, "Reglamentación para la ejecución de Instalaciones eléctricas en inmuebles", part 7 section 771).