Control

MY COPERCOM®
Multiconductor - PVC-Nylon/PVC - 600 V - 90ºC - ICEA S-73-532
Download PDF datasheet

Attributes

  • Flexible Stranded Conductors
  • Sequentially Marked
  • Fire-retardant
  • Sunlight resistant
  • Mineral oil resistant

Certifications

Applications

Control, signalling, measuring and protective equipment; electric controls of industrial installations.
Suitable for overhead trays, direct earth burial or duct-buried installations.

features

Temperature rating: 90ºC (operating), 160°C (short circuit)
Voltage rating: 600V AC.
Construction requirements: As per ICEA S-73-532.
Fire requirements: As per ICEA T 30-520 -Fire-retardancy.
NEC Code:
  Compliant with Art. 310 - Art. 501 classified areas Cl1 Div.2 and Cl2 Div.2.
Conductor requirements: As per ASTM B 174.

description

Conductor: Annealed electrolytic copperflexible stranding.
Insulation:
PVC/Nylon.
Identification: According to Method 3 Table E-2; black  and printed in white or yellow.
Sheath: Black PVC; sunlight- and mineral-oil resistant.

optionals

Armour: Zinc-plated steel wire serve or double zinc-plated steel tape spiral wrap.

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) or 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: Class B semi-rigid stranded cable per ASTM B 8 can be supplied upon request.
Identification: According to Method 3 Table E-1 with other colour bases, Method 1 Table E-1, Method 1 Table E-2.

Tables

Dimensions & Weight



Conductors
X section
N° x AWG
Code Outside diameter
mm
Weight kg/km Conductors X section
Nª x AWG
Code Outside diameter mm Weight kg/km
2x16 MY 0216 7.3 79 2x12 MY 0212 8.9 141
3x16 MY 0316 7.7 95 3x12 MY 0312 9.4 176
4x16 MY 0416 8.4 115 4x12 MY 0412 10.3 219
5x16 MY 0516 9.1 139 5x12 MY 0512 11.2 267
7x16 MY 0716 9.8 176 7x12 MY 0712 12.2 350
10x16 MY 1016 12.2 227 10x12 MY 1012 16.1 487
12x16 MY 1216 12.6 263 12x12 MY 1212 16.6 568
14x16 MY 1416 14.3 326 14x12 MY 1412 17.8 654
16x16 MY 1616 15.0 367 16x12 MY 1612 18.8 745
19x16 MY 1916 15.8 424 19x12 MY 1912 19.8 866
21x16 MY 2116 16.5 461 21x12 MY 2112 20.8 952
24x16 MY 2416 18.0 523 24x12 MY 2412 23.8 1135
27x16 MY 2716 18.4 577 27x12 MY 2712 24.3 1256
30x16 MY 3016 19.3 634 30x12 MY 3012 25.5 1384
32x16 MY 3216 20.0 675 32x12 MY 3212 26.4 1472
37x16 MY 3716 20.8 768 37x12 MY 3712 27.4 1678
48x16 MY 4816 24.5 1032 48x12 MY 4812 30.9 2141
2x14 MY 0214 8.1 104 2x10 MY 0210 10.7 213
3x14 MY 0314 8.6 128 3x10 MY 0310 11.4 271
4x14 MY 0414 9.3 156 4x10 MY 0410 12.5 339
5x14 MY 0514 10.2 191 5x10 MY 0510 14.4 439
7x14 MY 0714 11.0 245 7x10 MY 0710 15.7 575
10x14 MY 1014 14.6 344 10x10 MY 1010 19.7 756
12x14 MY 1214 15.0 396 12x10 MY 1210 20.3 885
14x14 MY 1414 16.0 452 14x10 MY 1410 22.8 1070
16x14 MY 1614 16.9 515 16x10 MY 1610 24.1 1220
19x14 MY 1914 17.8 596 19x10 MY 1910 25.3 1413
21x14 MY 2114 18.6 650 21x10 MY 2110 26.6 1553
24x14 MY 2414 20.4 740 24x10 MY 2410 29.1 1764
27x14 MY 2714 21.8 865 27x10 MY 2710 29.8 1963
30x14 MY 3014 22.9 953 30x10 MY 3010 31.3 2166
32x14 MY 3214 23.7 1013 32x10 MY 3210 32.5 2311
37x14 MY 3714 24.6 1150 37x10 MY 3710 33.8 2643
48x14 MY 4814 25.5 1185 48x10 MY 4810 38.2 3380

Electrical Characteristics



Gauge AWG Electrical resistance at 90ºC in AC Ohm/km Current-carrying capacity in free air at 40ºC (*)
2x  Ampere 4x  Ampere 7x  Ampere 10x Ampere 19x Ampere 30x Ampere 37x Ampere 48x Ampere
16 17.5 22 17.5 15 11 11 10 9 7.5
14 11.0 32 25.5 22 16 16 14 13 11
12 6.9 36 29 25.5 18 18 16 15 13
10 4.3 50 40 35 25 25 22.5 20 17.5

(*) According to NEC 2008, tables 310.15 and 310.17.