Control

FX CONPREX ®
Multiconductor - XLPE/PVC - 0.6/1KV - 90ºC - IEC 60502-1
IRAM 2178-1
Download PDF datasheet

Attributes

  • Flexible Stranded Conductors
  • Industrial Applications
  • Sequentially Marked
  • Fire-retardant

Certifications

Applications

Control, signalling, measuring and protective equipment; electric controls of industrial installations.
Suitable for overhead trays, direct earth burial or duct-buried installations.

features

Temperature rating: 90ºC (operating), 130°C (overload), 250°C (short circuit).
Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC
Construction requirements: As per IEC 60502-1 / IRAM 2178-1
Fire requirements: As per IEC 60332-3-24 / IRAM NM IEC 60332-3-24 - Fire-retardancy.
Conductor requirements: As per IEC 60228 / IRAM NM 280.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: XLPE (crosslinked polyethylene).
Identification: White and alpha-numerically printed in black.
Sheath: Black PVC; fire-retardant.

As from July 1st 2018 this cable family will be commercialized with standard BLACK sheath.

optionals

Shield: Annealed copper tape helical wrap with 100% coverage and 20% overlap (W).
Armour: Zinc-plated steel wire serve or double zinc-plated steel tape spiral wrap.

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) or 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.
Identification: One of the conductors of each cable isolated on green / yellow. Use other colors to identify such as black, gray, blue, etc.

Tables

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Shielded Armoured
Code Outside diameter mm Weight kg/km Code Under shield diameter mm Outside diameter mm Weight kg/km Código Under armour diameter mm Outside diameter mm Weight kg/km
2x1 FX 0210 Ne 8.3 86 FX 0210 WNe 11.0 14.9 291 FX 0210 HNe 7.3 12.5 269
3x1 FX 0310 Ne 8.7 97 FX 0310 WNe 11.0 14.9 294 FX 0310 HNe 7.7 12.9 290
4x1 FX 0410 Ne 9.4 114 FX 0410 WNe 11.0 14.9 296 FX 0410 HNe 8.4 13.6 320
5x1 FX 0510 Ne 10.2 137 FX 0510 WNe 11.0 14.9 299 FX 0510 HNe 9.1 14.3 352
7x1 FX 0710 Ne 10.9 164 FX 0710 WNe 11.0 14.9 293 FX 0710 HNe 10.1 15.3 409
10x1 FX 1010 Ne 14.1 226 FX 1010 WNe 12.5 16.4 336 FX 1010 HNe 12.7 17.9 529
12x1 FX 1210 Ne 14.5 254 FX 1210 WNe 12.9 16.8 367 FX 1210 FNe 13.2 18.0 526
14x1 FX 1410 Ne 15.4 285 FX 1410 WNe 13.8 17.7 405 FX 1410 FNe 13.8 18.6 568
16x1 FX 1610 Ne 16.2 321 FX 1610 WNe 14.6 18.5 446 FX 1610 FNe 14.6 19.4 618
19x1 FX 1910 Ne 17.0 363 FX 1910 WNe 15.4 19.3 495 FX 1910 FNe 15.4 20.2 681
21x1 FX 2110 Ne 17.8 395 FX 2110 WNe 16.2 20.1 533 FX 2110 FNe 16.3 21.1 736
24x1 FX 2410 Ne 19.4 446 FX 2410 WNe 17.8 21.7 597 FX 2410 FNe 18.0 22.8 827
27x1 FX 2710 Ne 19.8 487 FX 2710 WNe 18.2 22.1 641 FX 2710 FNe 18.4 23.2 877
30x1 FX 3010 Ne 20.7 530 FX 3010 WNe 19.1 23.0 691 FX 3010 FNe 19.1 23.9 939
32x1 FX 3210 Ne 21.5 566 FX 3210 WNe 19.9 23.8 732 FX 3210 FNe 19.9 24.7 990
37x1 FX 3710 Ne 22.3 635 FX 3710 WNe 20.7 24.6 808 FX 3710 FNe 20.7 25.5 1083
48x1 FX 4810 Ne 25.1 797 FX 4810 WNe 23.5 27.5 1011 FX 4810 FNe 23.7 28.5 1325
2x1.5 FX 0215 Ne 8.9 103 FX 0215 WNe 11.0 14.9 296 FX 0215 HNe 7.9 13.1 298
3x1.5 FX 0315 Ne 9.4 120 FX 0315 WNe 11.0 14.9 301 FX 0315 HNe 8.4 13.6 326
4x1.5 FX 0415 Ne 10.1 140 FX 0415 WNe 11.0 14.9 305 FX 0415 HNe 9.1 14.3 361
5x1.5 FX 0515 Ne 11.0 170 FX 0515 WNe 11.0 14.9 310 FX 0515 HNe 10.0 15.2 403
7x1.5 FX 0715 Ne 11.9 210 FX 0715 WNe 11.0 14.9 304 FX 0715 HNe 11.0 16.2 449
10x1.5 FX 1015 Ne 15.3 284 FX 1015 WNe 13.7 17.6 399 FX 1015 FNe 13.9 18.7 531
12x1.5 FX 1215 Ne 15.7 321 FX 1215 WNe 14.1 18.0 438 FX 1215 FNe 14.4 19.2 578
14x1.5 FX 1415 Ne 16.8 365 FX 1415 WNe 15.2 19.1 490 FX 1415 FNe 15.2 20.0 633
16x1.5 FX 1615 Ne 17.6 409 FX 1615 WNe 16.0 19.9 537 FX 1615 FNe 16.0 20.8 686
19x1.5 FX 1915 Ne 18.5 466 FX 1915 WNe 16.9 20.8 601 FX 1915 FNe 16.9 21.7 761
21x1.5 FX 2115 Ne 19.4 509 FX 2115 WNe 17.8 21.7 650 FX 2115 FNe 17.9 22.7 821

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Shielded Armoured
Code Outside diameter mm Weight kg/km Code Under shield diameter mm Outside diameter mm Weight kg/km Código Under armour diameter mm Outside diameter mm Weight kg/km
24x1.5 FX 2415 Ne 21.2 577 FX 2415 WNe 19.6 23.5 730 FX 2415 FNe 19.8 24.6 916
27x1.5 FX 2715 Ne 21.6 630 FX 2715 WNe 20.0 23.9 785 FX 2715 FNe 20.3 25.1 982
30x1.5 FX 3015 Ne 22.7 693 FX 3015 WNe 21.1 25.0 855 FX 3015 FNe 21.1 25.9 1055
32x1.5 FX 3215 Ne 23.5 736 FX 3215 WNe 21.9 25.9 920 FX 3215 FNe 21.9 26.7 1107
37x1.5 FX 3715 Ne 24.4 830 FX 3715 WNe 22.8 26.8 1020 FX 3715 FNe 22.8 27.6 1219
48x1.5 FX 4815 Ne 27.5 1047 FX 4815 WNe 25.9 29.9 1258 FX 4815 FNe 26.2 31.2 1507
2x2.5 FX 0225 Ne 9.8 131 FX 0225 WNe 11.0 14.9 305 FX 0225 HNe 8.8 14.0 347
3x2.5 FX 0325 Ne 10.3 154 FX 0325 WNe 11.0 14.9 315 FX 0325 HNe 9.3 14.5 379
4x2.5 FX 0425 Ne 11.2 184 FX 0425 WNe 11.0 14.9 323 FX 0425 HNe 10.2 15.4 428
5x2.5 FX 0525 Ne 12.2 224 FX 0525 WNe 11.2 15.1 340 FX 0525 HNe 11.2 16.4 481
7x2.5 FX 0725 Ne 13.2 280 FX 0725 WNe 12.3 16.2 382 FX 0725 HNe 12.3 17.5 540
10x2.5 FX 1025 Ne 17.0 376 FX 1025 WNe 15.4 19.3 508 FX 1025 FNe 15.7 20.5 653
12x2.5 FX 1225 Ne 17.5 430 FX 1225 WNe 15.9 19.8 566 FX 1225 FNe 16.3 21.1 720
14x2.5 FX 1425 Ne 18.7 490 FX 1425 WNe 17.1 21.0 634 FX 1425 FNe 17.1 21.9 788
16x2.5 FX 1625 Ne 19.7 555 FX 1625 WNe 18.1 22.0 704 FX 1625 FNe 18.1 22.9 863
19x2.5 FX 1925 Ne 20.7 634 FX 1925 WNe 19.1 23.0 793 FX 1925 FNe 19.1 23.9 965
21x2.5 FX 2125 Ne 21.8 697 FX 2125 WNe 20.2 24.1 865 FX 2125 FNe 20.3 25.1 1046
24x2.5 FX 2425 Ne 23.8 788 FX 2425 WNe 22.2 26.2 989 FX 2425 FNe 22.5 27.3 1173
27x2.5 FX 2725 Ne 24.3 867 FX 2725 WNe 22.7 26.7 1072 FX 2725 FNe 23.1 27.9 1267
30x2.5 FX 3025 Ne 25.5 952 FX 3025 WNe 23.9 27.9 1167 FX 3025 FNe 23.9 28.7 1359
32x2.5 FX 3225 Ne 26.5 1018 FX 3225 WNe 24.9 28.9 1238 FX 3225 FNe 24.9 29.7 1434
37x2.5 FX 3725 Ne 27.5 1150 FX 3725 WNe 25.9 29.9 1380 FX 3725 FNe 25.9 30.9 1603
48x2.5 FX 4825 Ne 31.3 1474 FX 4825 WNe 29.9 34.3 1785 FX 4825 FNe 30.3 35.5 2038
2x4 FX 0240 Ne 10.7 171 FX 0240 WNe 11.0 14.9 324 FX 0240 HNe 9.7 14.9 405
3x4 FX 0340 Ne 11.3 206 FX 0340 WNe 11.0 14.9 343 FX 0340 HNe 10.3 15.5 452
4x4 FX 0440 Ne 12.3 251 FX 0440 WNe 11.3 15.2 370 FX 0440 HNe 11.3 16.5 516
5x4 FX 0540 Ne 13.4 305 FX 0540 WNe 12.4 16.3 432 FX 0540 HNe 12.4 17.6 585
7x4 FX 0740 Ne 14.6 391 FX 0740 WNe 13.7 17.6 498 FX 0740 FNe 13.7 18.5 624
10x4 FX 1040 Ne 18.8 525 FX 1040 WNe 17.2 21.1 670 FX 1040 FNe 17.5 22.3 830
12x4 FX 1240 Ne 19.3 604 FX 1240 WNe 17.7 21.6 752 FX 1240 FNe 18.2 23.0 926
14x4 FX 1440 Ne 20.7 693 FX 1440 WNe 19.1 23.0 852 FX 1440 FNe 19.1 23.9 1024
16x4 FX 1640 Ne 21.8 786 FX 1640 WNe 20.2 24.1 950 FX 1640 FNe 20.2 25.0 1126
19x4 FX 1940 Ne 23.0 909 FX 1940 WNe 21.4 25.4 1102 FX 1940 FNe 21.4 26.2 1276
21x4 FX 2140 Ne 24.2 998 FX 2140 WNe 22.6 26.6 1201 FX 2140 FNe 22.7 27.5 1386
24x4 FX 2440 Ne 26.5 1133 FX 2440 WNe 24.9 28.9 1355 FX 2440 FNe 25.2 30.2 1573
27x4 FX 2740 Ne 27.0 1250 FX 2740 WNe 25.4 39.4 1475 FX 2740 FNe 25.8 30.8 1705
30x4 FX 3040 Ne 28.6 1391 FX 3040 WNe 26.8 31.0 1628 FX 3040 FNe 26.8 31.8 1845
32x4 FX 3240 Ne 29.7 1484 FX 3240 WNe 27.9 32.1 1728 FX 3240 FNe 28.3 33.5 1999
37x4 FX 3740 Ne 30.9 1690 FX 3740 WNe 29.5 33.9 1994 FX 3740 FNe 29.5 34.7 2233
48x4 FX 4840 Ne 35.3 2182 FX 4840 WNe 33.5 38.1 2508 FX 4840 FNe 33.9 40.3 3076

Meaning of the trailing letters in the codes of armored cables. Here, F:Helical double tape of tinned galvanized steel. H: Galvanized steel wires helically applied. W: annealed copper tape helical wrap.

General Properties



Nominal cross-section sq mm Electrical resistance at 90ºC in AC Ohm/km Current-carrying capacity in free air (*)
2x  Ampere 4x  Ampere 7x  Ampere 10x Ampere 19x Ampere 30x Ampere 40x Ampere 48x Ampere
1 24.86 N/A N/A N/A N/A N/A N/A N/A N/A
1.5 16.96 22.8 20.0 16.0 10.0 10.0 9.0 8.0 7.0
2.5 10.18 31.4 27.6 22.0 13.8 13.8 12.4 11.0 9.6
4 6.31 42.8 36.1 28.9 18.1 18.1 16.2 14.4 12.6

(*) In free air at 40ºC, according to IEC 364-5-523 and NEC 2008, table 310.15.

powered by