Building Wire

VK INSTALAR single
Flexible-Single Conductor - PVC- 450V/750V - 70ºC
Download PDF datasheet

Attributes

  • Flexible Stranded Conductors
  • Dwelling Installation
  • Fire-retardant

Certifications

Applications

Suitable for fixed indoor installations in buildings, and cabling of electronical devices.

features

Temperature rating: 70ºC maximum.
Voltage rating: 450V / 750V.
Construction requirements: As per IEC 60227-3 and IRAM NM 247-3.
Fire requirements: As per IEC 60332-3-23 and IRAM NM IEC 60332-3-23 - Fire-retardancy.
Conductor requirements: As per IEC 60228 and IRAM NM 280.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: PVC.
Identification: The choice of colours includes red, brown, black, blue, grey or green/yellow, among others.

installation

Assembly: Minimum bend radius is 7xOD.
Maximum pulling tension: 5daN/sq mm on copper conductors.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.

Tables

Dimensions, Weight & Electrical Characteristics



Code Nominal cross-section
sq mm
Insulation thickness
mm
Outside diameter
mm
Weight kg/km Elecrical resistance Ohm/km Current-carrying capacity
Ampere (*)
VK 0105 0.5 0.60 2.1 8 39 4.8
VK 0107 0.75 0.60 2.3 10 26 7.2
VK 0110 1 0.70 2.7 14 19.5 9.6
VK 0115 1.5 0.70 3.0 19 13.3 13
VK 0125 2.5 0.80 3.6 29 7.98 18
VK 0140 4 0.80 4.1 43 4.95 24
VK 0160 6 0.80 4.7 61 3.3 31
VK 1100 10 1.00 6.2 105 1.91 43
VK 1160 16 1.00 7.1 155 1.21 59
VK 1250 25 1.20 8.7 241 0.78 77
VK 1350 35 1.20 9.7 328 0.554 96
VK 1500 50 1.40 11.5 464 0.386 116
VK 1700 70 1.40 13.5 657 0.272 148
VK 1950 95 1.60 15.9 870 0.206 180
VK 11200 120 1.60 17.3 1170 0.161 207
VK 11500 150 1.80 19.9 1363 0.129 228
VK 11850 185 2.00 21.7 1658 0.106 260
VK 12400 240 2.20 25.1 2196 0.0801 290
VK 13000 300 2.40 28.3 2738 0.0641 340

(*) Values refer to ambient temp of 40ºC and 70ºC on the conductor, for three cables intalled in ducts.

powered by