Power

VF COPERINT®
Three-conductor shielded - XLPE/PVC 600V - 90ºC - ICEA S-95-658
Concentric copper conductor
Download PDF datasheet

Attributes

  • Flexible Stranded Conductors
  • Double Shielding
  • Industrial Applications
  • Fire-retardant
  • Electromagnetic interference protection
  • Mineral oil resistant

Applications

Variable frequency drive motor feed. (VFD)

features

Temperature rating: 90ºC (operating), 130°C (overload), 250°C (short circuit).
Voltage rating: 600V AC.
Construction requirements: As per ICEA S-95-658.
Fire requirements: As per ICEA T 30-520.
Conductor requirements: As per ASTM B 172, ASTM B 173, ASTM B 174.

description

Conductor: Annealed electrolytic copper; flexible stranding.
Insulation: XLPE (crosslinked polyethylene).
Identification:

- 3 Conductors:      

Shield: Copper wire concenctric conductor plus copper tape with adequate overlap and 100% coverage. See the table for the cross-section value relevant to each cable version.
Sheath: Black PVC, fire-retardant.

As from July 1st 2018 this cable family will be commercialized with standard BLACK sheath.
 

optionals

Armour: Helical wire wrap or double zinc-plated steel tape spiral wrap.

installation

Assembly: Minimum bend radius is 12xOD.
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: ASTM B 8 compliant class B, C or D semi-rigid stranded cable can be supplied upon request.

Tables

Dimensions & Weight



Conductors x gauge
N° x AWG/MCM
Code Under screen diameter mm Outside diameter
mm
Weight kg/km
3x14 VF 0314 9.5 13 255
3x12 VF 0312 10.4 14.6 342
3x10 VF 0310 11.8 16 447
3x8 VF 0308 15.7 19.9 657
3x6 VF 0306 17.5 23.0 928
3x4 VF 0304 19.9 25.4 1225
3x2 VF 0302 22.7 28.5 1714
3x1 VF 0301 26 31.8 2098
3x1/0 VF 31/0 29 34.8 2548
3x2/0 VF 32/0 31.8 37.6 3051
3x3/0 VF 33/0 35.9 42.1 3783
3x4/0 VF 34/0 38.9 46.6 4729
3x250 VF 3250 42.3 50 5501
3x300 VF 3300 46.2 53.9 6446
3x350 VF 3350 48.8 56.5 7345
3x400 VF 3400 51.4 59.1 8210

Electrical Characteristics



Conductors Gauge AWG/MCM Shield Gauge AWG Electrical resistance at 90ºC in AC Inductive reactance at 60hz Current-carrying  capacity in free air (1) Ampere Current-carrying  capacity in earth (2) Ampere
Ohm/km Ohm/km
14 14 11.22 0.115 32 25
12 12 7.08 0.109 36 30
10 10 4.44 0.102 50 40
8 10 2.78 0.105 73 55
6 8 1.75 0.100 96 75
4 8 1.10 0.096 127 95
2 6 0.692 0.092 173 130
1 6 0.551 0.093 200 150
1/0 6 0.436 0.091 237 170
2/0 6 0.347 0.089 273 195
3/0 4 0.276 0.087 319 225
4/0 4 0.220 0.085 369 260
250 4 0.186 0.087 414 290
300 4 0.157 0.085 460 320
350 3 0.135 0.084 519 350
400 3 0.119 0.084 560 380
500 3 0.098 0.082 637 430
600 3 0.083 0.084 710 475

(1) Cables installed in free air at 40ºC according to NEC table 310-17.
(2) Cables directly buried in earth at 30ºC ambient temperature according to NEC table 310-16.