Industrial Automation

SB SBAR ®
Shielded cables for Industrial Automation
Download PDF datasheet

Attributes

  • Direct burial
  • Sequentially Marked
  • Fire-retardant
  • Electromagnetic interference protection
  • Computer Systems

Certifications

Applications

Process control distribution circuits; suitable for underground and aerial raceways, industrial automation PLC and DCS.

features

Temperature rating: According to cable model.
Voltage rating: 30V / 300V / 600V according to cable model.
Construction requirements: As per UL 13 and UL 1277.
Fire requirements: As per UL 1685.
Conductor requirements: As per ASTM B8 and ASTM B 33.
NEC Code: Compliant with Art. 725 PLTC and Art. 800 Communications.

description

Conductor: Annealed tinned electrolytic copper, 7-wire stranding, class B.
Insulation: Thermoplastic compound.
The full configuration of each cable is described in the relevant associated table.

optionals

Armour: Zinc-plated steel served-wire helical armour or aluminium interlock armour plus grey PVC sheath;  fire-retardant, sunlight and hydrocarbon-resistant. These cables are UL certified for direct earth burial.

See Technical Note # 8, "Wire armour properties"

Tables

Dimensions, Weight and General Properties



SB 2074 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL1277 600 75 1 18 Blue PVC 10.2 115
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
23.6 Tape + Braid 64.5 55 16.76 100 White /Blue Industrial Twinax

2



SB 2083(*) Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 / 30 80 2 15 / 18 Gray PVC 12.5 188
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
11.5 / 23.6 Individually taped pairs + Braid 75 (data pair) 45 13.72 120 Black / Red (15AWG) Blue / White (18AWG) DeviceNet

(*) SB 2084: Alternative cable sheathed with yellow CPE instead of PVC.

3



SB 2085(*) Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 / 30 80 2 22 / 24 Gray PVC 7.5 67
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
57.4 / 90.9 Individually taped pairs + Braid 76 (data pair) 39 11.89 120 Black / Red (22AWG) Blue / White (24AWG) DeviceNet

(*) SB 2086: Alternative cable sheathed with yellow CPE instead of PVC.

4



SB 2087 Manufacturing standard Voltage rating Temperature Nº of pairs   Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 80 2 16 / 20 Gray PVC 9.6 98
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
14.9 / 37.1 Individually taped pairs 76 (data pair) 39 11.89 120 Blue / Brown (16AWG) Black / White (20AWG) DeviceBus

5



SB 2088 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 80 2 22 Gray PVC 7.6 60
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
57.4 Individually taped pairs 75 (data pair) 39 11.89 120 Blue / Brown Black / White DeviceBus

6



SB 7761 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG Sheath material mm kg/km
UL13 300 / 30 60 1 18 Gray PVC 5.8 41
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
23.6 Tape 66 60 18.29 N/A White / Black N/A

7



SB 8208 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 75 1(*) 20 Black PVC 7.9 71
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
35.8 / 37.2 Tape + Braid 66 52 15.85 100 White / Black Industrial Twinax

(*) The pair consists of an annealed copper conductor and an annealed tinned copper conductor.

8



SB 8273 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 60 1 20 Blue PVC 6.2 50
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
37.2 Braid 66 65 19.81 78 White / Blue Industrial Twinax

9



SB 8464 Manufacturing standard Voltage rating Temperature Nº of pairs Gauge Sheath material Outside diameter Weight
Volt °C AWG mm kg/km
UL13 300 80 1 20 Blue PVC 6.2 50
Electrical resistance Shielding Velocity of propagation Mutual capacitance Characteristic impedance Identification of conductors System
Ohm/km VP(%) pF/m pF/ft Ohm
37.2 Tape + Braid 66 65 19.81 78 White / Blue Industrial Twinax

Shielding characterization
Tape: Aluminium-polyester (AI/Pt) tape helical wrap with 100% coverage. Cables that are shielded only with tape  include a tinned-copper drain wire in conctact with the aluminium layer. 
Braid: Tinned-copper wire braid applied on the AI/Pt tape.

Installation

Assembly:
Minimum bend radius is 7xOD (unarmoured versions) and 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

 