Industrial Automation

SB 2100-9700-9800
Shielded multipair for RS 485 systems
Download PDF datasheet

Attributes

  • Double Shielding
  • Fire-retardant
  • Electromagnetic interference protection
  • Hydrocarbon-resistant
  • Sunlight resistant
  • Computer Systems

Certifications

Applications

Through this system a multiple-node net can be interconnected by means of a paired cable, which allows bi-directional communication, significant length of the interconnection cable and high speed data transmission.
Fieldbus distribution circuits; suitable for underground and aerial raceways in RS 485 systems.

features

Temperature rating: 75ºC maximum.
Voltage rating: 300V.
Construction requirements: As per UL 13 Type PLTC.
Fire requirements: As per UL 1685.
Conductor requirements: As per ASTM B8 and ASTM B33.
NEC Code: Compliant with Art. 725 PLTC and Art. 800 Communications.

description

Conductor: Annealed tinned electrolytic copper, 7-wire stranding, class B.
Insulation: Thermoplastic compound.
Identification: Colours according to colour coding chart.
Lay length: 50mm (20 twists/m).
Shield: Aluminium-polyester tape plus tinned-copper braid.
Sheath: Grey PVC, fire-retardant, sunlight and hydrocarbon-resistant. Black for SB 2100 series. Grey for SB 9700 and SB 9800 series.
Stripping: Polyamide ripcord under the sheath.

optionals

Armour: Zinc-plated steel served-wire helical armour or aluminium interlock armour plus grey PVC sheath; fire-retardant, sunlight and hydrocarbon-resistant.

See Technical Note # 8, "Wire armour properties"

installation

Connection: Without amplifiers, RS 485 bus  maximum length is 1200 m. Longer extensions require suitable equipment to re-generate and amplify the signal. RS 485 is a serial bus, and, consequently, allows no star or ring installations. Bus cables should not run close to power cables and equipment, as these generate electromagnetic induction, which may lead to system malfunctioning.
Assembly: Minimum bend radius is 7xOD (unarmoured versions) and 12xOD (armoured versions).
Maximum pulling tension: 5 daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Construction: The sheath material is LSZH-HFFR (Low Smoke, Zero Halogen; Halogen-Free, Flame-Retardant). Compliant with IEC 60502-1, IEC 60754-1-2, IEC 61034, NES 713 and CEI 20-37 standards.

Tables

Dimensions, Weight & General Properties



Code N° of Pairs Gauge Electrical resistance Shield Velocity of propagation Characteristic impedance Mutual capacitance Outside diameter Weight
AWG Ohm/km VP(%) Ohm pF/m pF/ft mm kg/km
SB 2106 1 22 57.4 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 78 120 42 12.8 8.2 78
SB 2107 1.5 (*) 8.6 88
SB 2108 2 8.6 85
SB 2109 3 9.1 98
SB 2110 4 10.4 126
SB 9701 1 24 90.9 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 66 120 48 14.6 6.5 68
SB 9702 2 8.8 88
SB 9703 3 9.2 102
SB 9704 4 10.6 129
SB 9708 8 13.4 208
SB 9712 12 16.5 293
SB 9716 16 18.1 347
SB 9801 1 22 57.4 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 66 120 44 13.4 8.6 89
SB 9802 2 8.4 91
SB 9803 3 8.9 108
SB 9804 4 9.6 128
SB 9808 8 12.6 223
SB 9812 12 15.2 334
SB 9816 16 17.2 438

(*) It consists of three conductors: two conductors paired under the tape and one conductor cabled between the tape and the braid.
pF/m = Mutual capacitance between conductors in the same pair expressed in picoFarad per metre.
pF/ft = Mutual capacitance between conductors in the same pair expressed in picoFarad per foot. 

ARMORED



Code N° of Pairs Gauge Electrical resistance Shield Velocity of propagation Characteristic impedance Mutual capacitance Outside diameter Weight
AWG Ohm/km VP(%) Ohm pF/m pF/ft mm kg/km
SB 2106 H 1 22 57.4 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 78 120 42 12.8 12.4 279
SB 2107 H 1.5 (*) 12.8 298
SB 2108 H 2 12.8 301
SB 2109 H 3 13.3 318
SB 2110 H 4 14.6 362
SB 9701 H 1 24 90.9 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 66 120 48 14.6 11.3 249
SB 9702 H 2 13.0 302
SB 9703 H 3 13.5 326
SB 9704 H 4 14.8 380
SB 9708 H 8 18.1 539
SB 9712 H 12 21.5 761
SB 9716 H 16 23.7 885
SB 9801 H 1 22 57.4 Aluminium / Polyester  tape + tinned copper braid (65% coverage) 66 120 44 13.4 12.6 293
SB 9802 H 2 12.8 297
SB 9803 H 3 13.1 325
SB 9804 H 4 13.8 357
SB 9808 H 8 17.3 535
SB 9812 H 12 20.3 775
SB 9816 H 16 22.8 956

In all cases, the armour consists of a zinc-plated steel wire serve (SWA, Steel Wire Armour).
(*) It consists of three conductors: two conductors paired under the tape and one conductor cabled between the tape and the braid.
pF/m = Mutual capacitance between conductors in the same pair expressed in picoFarad per metre.
pF/ft = Mutual capacitance between conductors in the same pair expressed in picoFarad per foot.