Control

RM FUEGAR ®
Multiconductor - 0.6/1KV - 90°C - IEC 60502-1 - IRAM 62266
Fire-resistant
Download PDF datasheet

Attributes

  • Low Smoke
  • Indoor Public Places
  • Industrial Applications
  • Halogen free
  • Fire-retardant
  • Fire-resistant

Certifications

Applications

Control, signalling, measuring and protective equipment; electric controls of industrial installations.
Suitable for overhead trays, direct earth burial or duct-buried installations.
Suitable for preserving electrical integrity in fire conditions in places like distilleries, petrochemical plants, shipyards, etcetera.

features

Temperature rating: 90ºC (service), 130°C (overload), 250°C (short circuit).
Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC
Construction requirements: As per IEC 60502-1 / IRAM 62266.
Fire requirements: As per IEC 60332-3-24 / IRAM NM IEC 60332-3-24 - Fire retardacy.
Fire-resistance requirements: As per IEC 60331-21 (at 750ºC for 90 minutes).Optional: IEC 60331-1/2 (830ºC) / BS6387 CWZ (950ºC). See alternatives: Extended circuit integrity.
Halogen content requirements: As per IEC 60754-1/2 - Non-halogen.
Smoke opacity requirements: As per IEC 61034 - Smoke density.
Toxicity requirements: As NES 713 / CEI 20-37 - Non-toxic.
Conductor requirements: As per IEC 60228 / IRAM NM 280.

description

Conductor: Annealed electrolytic copper, class 5 stranding.
Insulation: Mica tape + XLPE (crosslinked polyethylene).
Identification: White and alpha-numerically printed in black.
Sheath: LSZH-HFFR (Low Smoke, Zero Halogen - Halogen- Free, Flame-Retardant), orange.

optionals

Armour: Zinc-plated steel wire serve or double zinc-plated steel tape spiral wrap.

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) or 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.
Identification: One of the conductors of each cable isolated on green / yellow. Use other colors to identify such as black, gray, blue, etc.
Extended circuit integrity: This is a special design engineered to comply with highly demanding fire tests. Special construction is compliant with the following standards and tests:
BS 6387 standard:
Category C: Direct exposure to fire for 3 hours at 950ºC.
Category W: Direct exposure to fire for 15 minutes at 650ºC + Exposure to water spray for a further 15 minutes.
Category Z: Direct exposure to fire for 15 minutes at 950ºC + Mechanical shock simulated by striking the cable specimen against the backing panel every 30 seconds.
IEC 60331-1/2 standard: Direct exposure to fire for 2 hours at 830ºC +Mechanical shock simulated by striking the cable specimen against the backing panel every 5 minutes.

Tables

Dimensions & Weight



Conductors per cross-section
N° x sq mm
Code Outside diameter
mm
Weight kg/km Conductors per cross-section
N° x sq mm
Code Outside diameter
mm
Weight kg/km
2x1 RM 0210 9.9 113 2x2.5 RM 0225 11.4 163
3x1 RM 0310 10.4 126 3x2.5 RM 0325 12.0 186
4x1 RM 0410 11.3 147 4x2.5 RM 0425 13.1 222
5x1 RM 0510 12.3 177 5x2.5 RM 0525 14.3 269
7x1 RM 0710 13.3 213 7x2.5 RM 0725 15.5 332
10x1 RM 1010 17.1 279 10x2.5 RM 1025 20.0 435
12x1 RM 1210 17.6 314 12x2.5 RM 1225 20.7 501
14x1 RM 1410 18.9 358 14x2.5 RM 1425 22.2 571
16x1 RM 1610 19.9 404 16x2.5 RM 1625 23.4 647
19x1 RM 1910 20.9 453 19x2.5 RM 1925 24.6 734
21x1 RM 2110 21.9 491 21x2.5 RM 2125 25.9 805
24x1 RM 2410 24.0 557 24x2.5 RM 2425 28.4 912
27x1 RM 2710 24.5 607 27x2.5 RM 2725 29.0 1002
30x1 RM 3010 25.7 662 30x2.5 RM 3025 30.5 1101
32x1 RM 3210 26.7 708 32x2.5 RM 3225 31.8 1184
37x1 RM 3710 27.7 789 37x2.5 RM 3725 33.0 1331
48x1 RM 4810 31.3 991 48x2.5 RM 4825 37.6 1705
2x1.5 RM 0215 10.5 132 2x4 RM 0240 12.3 205
3x1.5 RM 0315 11.1 151 3x4 RM 0340 13.0 242
4x1.5 RM 0415 12.0 175 4x4 RM 0440 14.2 291
5x1.5 RM 0515 13.1 213 5x4 RM 0540 15.5 355
7x1.5 RM 0715 14.2 260 7x4 RM 0740 16.9 448
10x1.5 RM 1015 18.3 341 10x4 RM 1040 21.8 589
12x1.5 RM 1215 18.9 388 12x4 RM 1240 22.5 680
14x1.5 RM 1415 20.2 439 14x4 RM 1440 24.2 780
16x1.5 RM 1615 21.3 498 16x4 RM 1640 25.5 886
19x1.5 RM 1915 22.4 562 19x4 RM 1940 26.9 1018
21x1.5 RM 2115 23.5 612 21x4 RM 2140 28.3 1116
24x1.5 RM 2415 25.8 696 24x4 RM 2440 31.1 1268
27x1.5 RM 2715 26.3 759 27x4 RM 2740 31.8 1403
30x1.5 RM 3015 27.7 835 30x4 RM 3040 33.6 1555
32x1.5 RM 3215 28.7 888 32x4 RM 3240 35.0 1668
37x1.5 RM 3715 29.9 1003 37x4 RM 3740 36.4 1891
48x1.5 RM 4815 33.8 1262 48x4 RM 4840 41.6 2437

General Properties



Nominal cross-section
sq mm
Electrical resistance at
90ºC in AC Ohm/km
Current-carrying capacity in free air (*)
2x  Ampere 4x  Ampere 7x  Ampere 10x Ampere 19x Ampere 30x Ampere 40x Ampere 48x Ampere
1 24.86 N/A N/A N/A N/A N/A N/A N/A N/A
1.5 16.96 22.8 20.0 16.0 10.0 10.0 9.0 8.0 7.0
2.5 10.18 31.4 27.6 22.0 13.8 13.8 12.4 11.0 9.6
4 6.31 42.8 36.1 28.9 18.1 18.1 16.2 14.4 12.6

(*) In free air at 40ºC, according to IEC 364-5-523 and NEC 2008, table 310.15.