Mining

FFj_UNe
Multiconductor - 0.6/1kV - 90ºC - TPE/TPU
Gr/Ye earth conductor
Download PDF datasheet

Attributes

  • Tear and Impacts.
  • Harsh Environment
  • Drilling Ring Equipment
  • Flame-retardant
  • High Flexibility
  • Mineral oil resistant

Applications

This type of cable is required for heavy duty industrial use such as drilling equipment and mining in general. It counts with an augmented flexibility and plastic material which provide the right protection against chemical products, harsh environment, tear and impacts.

features

Temperature rating: 90ºC (dry environments), 75ºC (wet environments)
Voltage rating: 600/1000V AC; 1200V AC / 1500V DC maximum.
Construction requirements: As per IEC 60502-1
Fire requirements: As per IEC 60332-1 - Fire-retardancy.
Conductor requirements: As per IEC 60228 / IRAM NM 280.


These cables comply with the Flexing tests specified in Mercosur standards NM 247-2 for 300000 simple cycles or 150000 double cycles.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: TPE (thermoplastic rubber)
Identification:
 

- 3 Conductors:          
- 4 Conductors:          
- 5 Conductors:          

 

Sheath: Polyurethane; black.

installation

Assembly: Minimum bend radius is 7xOD.
Maximum pulling tension: 5daN/sq mm on copper conductors.
Assembly temperature: 5ºC or higher.

Tables

Electrical Characteristics



Nominal cross-section sq mm Electrical resistance at 90ºC in AC Ohm/km Inductive reactance at 50hz Current-carrying capacity in free air (1) Current-carrying capacity in earth (2)
Multiconductor Ohm/km 3x (3) Ampere 3x(3)Amper
1 24,86 0,112 N/A N/A
1,5 16,96 0,104 20,0 27,6
2,5 10,18 0,097 27,6 37,1
4 6,31 0,097 36,1 48,5
6 4,21 0,091 46,6 60,8
10 2,44 0,084 64,6 82,7
16 1,54 0,080 86,5 107,4
25 0,995 0,080 109,3 140,6
35 0,707 0,078 136,8 168,2
50 0,493 0,077 166,3 198,6
70 0,348 0,074 212,8 243,2
95 0,264 0,074 257,5 292,6
120 0,207 0,072 299,3 333,5
150 0,166 0,072 344,9 373,4
185 0,137 0,072 394,3 424,7
240 0,105 0,072 464,6 493,1
300 0,0853 0,071 536,8 558,6

(1) Cables installed in free air at 40ºC according to IEC 364-5-523.(2) Cables directly buried in earth at a ground temperature of 25ºC with ground specific thermal resistivity of 1K.m/W.(3) The values also apply to 4-conductor and 5-conductor cables.For further information about current-carrying capacity values and types of installations refer to IEC 364-5-523 and the regulations for electrical installations in buildings defined by Argentina's Electrotechnical Association (in Spanish, "Reglamentación para la ejecución de Instalaciones eléctricas en inmuebles", part 7 section 771).

Dimensions & Weight



Conductors per cross-section N° x sq mm Code Outside diameter mm Weight kg/km Conductors per cross-section N° x sq mm Code Outside diameter mm Weight kg/km
3x1 FFj 0310 UNe 9,2 97 3x35+1x16 FFj 3516 UNe 27,5 1579
3x1,5 FFj 0315 UNe 9,8 115 3x50+1x25 FFj 5025 UNe 31,9 2202
3x2,5 FFj 0325 UNe 10,8 153 3x70+1x35 FFj 7035 UNe 36,8 3032
3x4 FFj 0340 UNe 12,6 223 3x95+1x50 FFj 9550 UNe 42,6 4019
3x6 FFj 0360 UNe 14,0 295 3x120+1x70 FFj 12070 UNe 47,0 5108
3x10 FFj 3100 UNe 16,3 447 3x150+1x70 FFj 15070 UNe 51,9 6132
3x16 FFj 3160 UNe 20,9 764 3x185+1x95 FFj 18595 UNe 57,0 7469
3x25 FFj 3250 UNe 24,4 1112 3x240+1x120 FFj 240120 UNe 64,8 9736
3x35 FFj 3350 UNe 26,6 1441 5x1 FFj 0510 UNe 10,7 134
3x50 FFj 3500 UNe 30,4 1969 5x1,5 FFj 0515 UNe 11,5 163
3x70 FFj 3700 UNe 35,6 2741 5x2,5 FFj 0525 UNe 12,7 220
3x95 FFj 3950 UNe 40,9 3588 5x4 FFj 0540 UNe 15 328
3x120 FFj 31200 UNe 44,2 4435 5x6 FFj 0560 UNe 16,8 439
3x150 FFj 31500 UNe 50,4 5571 5x10 FFj 5100 UNe 19,6 675
3x185 FFj 31850 UNe 54,7 6684 5x16 FFj 5160 UNe 24,8 1120
3x240 FFj 32400 UNe 62,8 8786 5x25 FFj 5250 UNe 29,1 1650
3x300 FFj 33000 UNe 70,1 10940 5x35 FFj 5350 UNe 32 2173
4x1 FFj 0410 UNe 9,9 114 5x50 FFj 5500 UNe 37,5 3045
4x1,5 FFj 0415 UNe 10,6 138 5x70 FFj 5700 UNe 43,3 4183
4x2,5 FFj 0425 UNe 11,7 186 5x95 FFj 5950 UNe 50,5 5542
4x4 FFj 0440 UNe 13,8 276 5x120 FFj 51200 UNe 54,5 6871
4x6 FFj 0460 UNe 15,3 364 5x150 FFj 51500 UNe 62,3 8615
4x10 FFj 4100 UNe 17,9 560 5x185 FFj 51850 UNe 67,6 10348
4x16 FFj 4160 UNe 22,8 939 5x240 FFj 52400 UNe 77,2 13512
3x25+1x16 FFj 2516 UNe 25,7 1267        