Power

FF CONPREX ®
Multiconductor - XLPE/PVC - 0.6/1KV - 90ºC- IRAM 2178-1
Gr/Ye earth conductor
Download PDF datasheet

Attributes

  • Grounded Conductor
  • Flexible Stranded Conductors
  • Industrial Applications
  • Sequentially Marked
  • Fire-retardant

Certifications

Applications

Suitable for overhead trays, direct earth burial or duct-buried installations.
Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations, etc.

features

Temperature rating: 90°C (operating), 130°C (overload) and 250°C (short circuit).
Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC
Construction requirements: As per IEC 60502-1 / IRAM 2178-1.
Fire requirements: As per IEC 60332-3-24 / IRAM NM IEC 60332-3-24 - Fire-retardancy.
Conductor requirements: As per IEC 60228 / IRAM NM 280.

description

Conductor: Annealed electrolytic copper; class 5 stranding.
Insulation: XLPE (crosslinked polyethylene).
Identification:

- 3 Conductors:          
- 4 Conductors:          
- 5 Conductors:          

Sheath: black PVC; fire-retardant.

As from July 1st 2018 this cable family will be commercialized with standard BLACK sheath.

optionals

Armour: Helical wire wrap or double zinc-plated steel tape spiral wrap (in multiconductor cables).

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) or 12xOD (armoured versions).
Maximum pulling tension: 5daN/sq mm on copper conductors. Wire-armoured cables can withstand 10daN/sq mm on the armour wires.
Assembly temperature: C or higher.

alternatives

Conductor: Class 2 semi-rigid stranded cable can be supplied upon request.

Tables

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Armoured
Code Outside diameter mm Weight kg/km Code Under armour diameter mm Outside diameter mm Weight kg/km
3x1 FF 0310 Ne 8,7 97 FF 0310 HNe 7,7 12,9 290
3x1,5 FF 0315 Ne 9,4 120 FF 0315 HNe 8,4 13,6 326
3x2,5 FF 0325 Ne 10,3 154 FF 0325 HNe 9,3 14,5 379
3x4 FF 0340 Ne 11,3 206 FF 0340 HNe 10,3 15,5 452
3x6 FF 0360 Ne 12,7 277 FF 0360 HNe 11,7 16,9 552
3x10 FF 3100 Ne 15 427 FF 3100 FNe 14 18,8 700
3x16 FF 3160 Ne 19,6 722 FF 3160 FNe 16 20,8 915
3x25 FF 3250 Ne 23,1 1056 FF 3250 FNe 19,5 24,3 1287
3x35 FF 3350 Ne 25,3 1377 FF 3350 FNe 21,7 26,5 1632
3x50 FF 3500 Ne 28,7 1860 FF 3500 FNe 25,1 29,9 2154
3x70 FF 3700 Ne 34,1 2630 FF 3700 FNe 30,3 35,3 2981
3x95 FF 3950 Ne 38,6 3387 FF 3950 FNe 34,6 40 3805
3x120 FF 31200 Ne 42,2 4467 FF 31200 FNe 38 44,4 5223
3x150 FF 31500 Ne 48,7 5363 FF 31500 FNe 44,1 50,9 6235
3x185 FF 31850 Ne 52,7 6440 FF 31850 FNe 47,9 54,9 7387
3x240 FF 32400 Ne 60,5 8517 FF 32400 FNe 55,3 62,7 9604
3x300 FF 33000 Ne 67,3 10546 FF 33000 FNe 61,7 69,5 11758
4x1 FF 0410 Ne 9,4 114 FF 0410 HNe 8,4 13,6 320
4x1,5 FF 0415 Ne 10,1 140 FF 0415 HNe 9,1 14,3 361
4x2,5 FF 0425 Ne 11,2 184 FF 0425 HNe 10,2 15,4 428
4x4 FF 0440 Ne 12,3 251 FF 0440 HNe 11,3 16,5 516
4x6 FF 0460 Ne 13,9 341 FF 0460 HNe 12,9 18,1 639
4x10 FF 4100 Ne 16,4 527 FF 4100 FNe 15,4 20,2 826
4x16 FF 4160 Ne 21,3 884 FF 4160 FNe 17,7 22,5 1096

Cables are letter coded to the type of protection they include.Here,F = double zinc-plated steel tape spiral wrap.H = zinc-plated steel wire serve.

Electrical Characteristics



Nominal cross-section
sq mm
Electrical resistance at 90ºC in AC
Ohm/km
Inductive reactance at 50hz Current-carrying  capacity in free air (1) Current-carrying  capacity in earth (2)
Multiconductor Ohm/km 3x (3) Ampere 3x(3)Amper
1 24,86 0,107 N/A N/A
1.5 16,96 0,100 20,0 27,6
2.5 10,18 0,093 27,6 37,1
4 6,31 0,088 36,1 48,5
6 4,21 0,083 46,6 60,8
10 2,44 0,078 64,6 82,7
16 1,54 0,075 86,5 107,4
25 0,995 0,075 109,3 140,6
35 0,707 0,073 136,8 168,2
50 0,493 0,073 166,3 198,6
70 0,348 0,071 212,8 243,2
95 0,264 0,070 257,5 292,6
120 0,207 0,070 299,3 333,5
150 0,166 0,070 344,9 373,4
185 0,137 0,070 394,3 424,7
240 0,105 0,069 464,6 493,1
300 0,0853 0,069 536,8 558,6

(1) Cables installed in free air at 40ºC according to IEC 364-5-523.
(2) Cables directly buried in earth at a ground temperature of 25ºC with ground specific thermal resistivity of 1K.m/W.
(3) The values also apply to 4-conductor and 5-conductor cables.
For further information about current-carrying capacity values and types of installations refer to IEC 364-5-523 and the regulations for electrical installations in buildings defined by Argentina's Electrotechnical Association (in Spanish, "Reglamentación para la ejecución de Instalaciones eléctricas en inmuebles", part 7 section 771).

Dimensions & Weight



Conductors per cross-section N° x sq mm Standard Armoured
Code Outside diameter mm Weight kg/km Code Under armour diameter mm Outside diameter mm Weight kg/km
3x25+1x16 FF 2516 Ne 24,2 1198 FF 2516 FNe 20,6 25,4 1441
3x35+1x16 FF 3516 Ne 26 1501 FF 3516 FNe 22,4 27,2 1764
3x50+1x25 FF 5025 Ne 29,9 2069 FF 5025 FNe 26,3 31,3 2389
3x70+1x35 FF 7035 Ne 35,1 2898 FF 7035 FNe 31,3 36,5 3277
3x95+1x50 FF 9550 Ne 40,1 3791 FF 9550 FNe 35,9 42,1 4488
3x120+1x70 FF 12070 Ne 44,6 5079 FF 12070 FNe 40,2 46,8 5877
3x150+1x70 FF 15070 Ne 49,9 5878 FF 15070 FNe 45,3 52,1 6774
3x185+1x95 FF 18595 Ne 54,7 7177 FF 18595 FNe 49,7 56,9 8158
3x240+1x120 FF 240120 Ne 62,3 9495 FF 240120 FNe 56,9 64,5 10614
3x300+1x150 FF 300150 Ne 69,7 11691 FF 300150 FNe 63,9 71,7 12912
5x1 FF 0510 Ne 10,1 131 FF 0510 HNe 9,1 14,3 352
5x1,5 FF 0515 Ne 11 165 FF 0515 HNe 10 15,2 403
5x2,5 FF 0525 Ne 12,2 218 FF 0525 HNe 11,2 16,4 481
5x4 FF 0540 Ne 13,4 297 FF 0540 HNe 12,4 17,6 585
5x6 FF 0560 Ne 15,2 407 FF 0560 FNe 14,2 19 683
5x10 FF 5100 Ne 18 635 FF 5100 FNe 17 21,8 960
5x16 FF 5160 Ne 23,2 1056 FF 5160 FNe 19,6 24,4 1288
5x25 FF 5250 Ne 27,5 1562 FF 5250 FNe 23,9 28,7 1841
5x35 FF 5350 Ne 30,2 2058 FF 5350 FNe 26,6 31,6 2382
5x50 FF 5500 Ne 35,3 2873 FF 5500 FNe 31,3 36,5 3236
5x70 FF 5700 Ne 41,4 4004 FF 5700 FNe 37,2 43,6 4744
5x95 FF 5950 Ne 47,6 5235 FF 5950 FNe 43 49,6 6065
5x120 FF 51200 Ne 52,2 6967 FF 51200 FNe 47,4 54,4 7903
5x150 FF 51500 Ne 59,6 8210 FF 51500 FNe 54,4 61,8 9280
5x185 FF 51850 Ne 65,2 9982 FF 51850 FNe 59,6 67,4 11154
5x240 FF 52400 Ne 74,3 13102 FF 52400 FNe 68,3 76,5 14439
5x300 FF 53000 Ne 83,2 16323 FF 53000 FNe 76,8 85,4 17823

Cables are letter coded to the type of protection they include.Here,F = double zinc-plated steel tape spiral wrap.H = zinc-plated steel wire serve.

powered by