Electronic Instrumentation

AF MILIAR ® single
Pair, triad and quad - 300V - 90°C - PLTC - UL 13
Fire-resistant - Halogen Free
Download PDF datasheet

Attributes

  • Low Smoke
  • Indoor Public Places
  • Halogen free
  • Fire-retardant
  • Sunlight resistant
  • Fire-resistant

Certifications

Applications

Electronic instrumentation, analog and digital signal circuits (4-20mA).
Intrinsically safe circuits.
Gas and/or fluid leak detection systems.
Pressure, temperature and volume measuring and monitoring equipment.
Alarm signal monitoring.
Suitable for preserving electrical integrity in fire conditions in places like distilleries, petrochemical plants, shipyards, etcetera.

features

Temperature rating: 90ºC (maximun).
Voltage rating: 300V.
Construction requirements: As per UL 13 Type PLTC and UL 2250 Type ITC.
Fire requirements: As per IEC 60332-3-24 and UL 1685.
Fire-resistance requirements: As per IEC 60331-23 (70,000 BTU flame at 750°C for 90 minutes).
Halogen content requirements: As per IEC 60754-1/2
Smoke opacity requirements: As per IEC 61034
Toxicity requirements: As per NES 713 / CEI 20-37
Conductor requirements: As per ASTM B8, class B.
NEC Code: Compliant with Art. 725 PLTC, Art. 727 ITC, Art. 800 Communications, Art. 501 classified locations Class 1 Div.2 and Class 2 Div.2.
Hydrocarbon requirements: As per NFC 32-200 and ASTM D 1239.

description

Conductor: Annealed electrolytic copper, 7-wire stranding, class B.
Insulation: Mica tape helical wrap plus extruded LSZH layer.
Identification:

  Standard Intrinsically Safe
- Pair:                
- Triad:                
- Quad:                

Lay length: 50 mm (20 twists/m).
Unshielded pair : Polyester tape wrap.
Shield: Aluminium-polyester tape helical wrap plus tinned-copper drain-wire conductor, 7-wire stranding, class B.
Sheath: orange LSZH- HFFR (blue for intrinsically safe systems), fire-retardant; sunlight, and hydrocarbon-resistant. 
Stripping: Polyamide ripcord under the sheath.

optionals

Armour: Zinc-plated steel served-wire helical armour or aluminium interlock armour plus orange LSZH sheath (blue for intrinsically safe systems); fire-retardant; sunlight and hydrocarbon-resistant. These cables are UL certified for direct earth burial.

See Technical Note # 8, "Wire armour properties"

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) and 12xOD (armoured versions).
Maximum pulling tension: 5daN/mm2 on copper conductors. Wire-armoured cables can withstand 10daN/mm2 on the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Construction Standards: As per British Standard 5308, EN 50288-7 and NBR 10300.
Materials: Sheath LSZH–HFFR, thermoset; fire-retardant; sunlight  and hydrocarbon-resistant.

Tables

Electrical Characteristics



Description Unit 20 AWG /
0.52 sq mm
18 AWG /
0.82 sq mm
16 AWG /
1.31 sq mm
14 AWG /
2.08 sq mm
12 AWG /
3.31 sq mm
Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded
Electrical resistance at 20ºC in DC Ohm/km 35.78 35.78 22.78 22.78 14.25 14.25 8.94 8.94 5.63 5.63
Mutual capacitance between conductors pF/m 74 131 66 117 88 160 90 164 101 185
Characteristic impedance Ohm 102 57 114 64 85 47 83 46 75 41
Mutual inductance between conductors uH/km 703 703 755 755 628 628 620 620 580 580

pF/m = Mutual capacitance between conductors expressed in picoFarad/ per metre.
uH/km = Mutual inductance between conductors expressed in microHenry per kilometre.

Dimensions & Weight



Type Gauge AWG Standard Armoured
Conductor Drain wire Code Outside diameter
mm
Weight kg/km Code Under armour
diameter mm
Outside diameter
mm
Weight kg/km
Unshielded pair 20 -- AF 0500 6.0 39 AF 0500 H 6.0 9.6 180
Unshielded pair 18 -- AF 0510 6.7 50 AF 0510 H 6.7 10.8 218
Unshielded pair 16 -- AF 0520 7.5 67 AF 0520 H 7.5 11.7 253
Unshielded pair 14 -- AF 0530 8.8 94 AF 0530 H 8.8 13.0 306
Unshielded pair 12 -- AF 0580 10.2 135 AF 0580 H 10.2 14.4 379
Shielded pair 20 22 AF 5000 6.1 43 AF 5000 H 6.1 10.2 200
Shielded pair 18 20 AF 5100 6.8 56 AF 5100 H 6.8 10.9 225
Shielded pair 16 18 AF 5200 7.6 77 AF 5200 H 7.6 11.8 266
Shielded pair 14 18 AF 5300 8.9 103 AF 5300 H 8.9 13.1 320
Shielded pair 12 18 AF 5800 10.3 144 AF 5800 H 10.3 14.5 389
Shielded triad 20 22 AF 6000 6.4 53 AF 6000 H 6.4 10.5 216
Shielded triad 18 20 AF 6100 7.4 74 AF 6100 H 7.4 11.6 259
Shielded triad 16 18 AF 6200 8.0 96 AF 6200 H 8.0 12.2 292
Shielded triad 14 18 AF 6300 9.4 133 AF 6300 H 9.4 13.6 360
Shielded triad 12 18 AF 6800 10.9 188 AF 6800 H 10.9 15.1 448
Shielded cuad 20 22 AF 9000 7.1 67 AF 9000 H 7.1 11.3 246
Shielded cuad 18 20 AF 9100 8.0 90 AF 9100 H 8.0 12.2 286
Shielded cuad 16 18 AF 9200 8.7 117 AF 9200 H 8.7 12.9 329
Shielded quad 14 18 AF 9300 10.8 177 AF 9300 H 10.8 15.0 432
Shielded quad 12 18 AF 9800 12.0 235 AF 9800 H 12.0 16.7 535

Cables are letter coded to the type of protection they include.
H = zinc-plated steel wire serve.