Electronic Instrumentation

AE MILIAR ® single
Pair, triad and quad - 300V - 90ºC - PLTC - UL13
Halogen Free (LSZH-HFFR)
Download PDF datasheet

Attributes

  • Direct burial
  • Low Smoke
  • Indoor Public Places
  • Halogen free
  • Fire-retardant
  • Sunlight resistant

Certifications

Applications

Electronic instrumentation, analog and digital signal circuits (4-20mA).
Intrinsically safe circuits.
Gas and/or fluid leak detection systems.
Pressure, temperature and volume measuring and monitoring equipment.
Alarm signal monitoring.
Recommended for use in highly populated enclosed public areas (control rooms, airports, hospitals, trains, underground trains, shopping malls, department stores, theatres, cinemas, tunnels, etc).

features

Temperature rating: 90ºC maximum.
Voltage rating: 300V.
Construction requirements: As per UL 13 Type PLTC.
Fire requirements: As per IEC 60332-3-24 and UL 1685.
Halogen content requirements: As per IEC 60754-1/2.
Smoke opacity requirements: As per IEC 61034.
Toxicity requirements: As per NES 713 and CEI 20-37.
Conductor requirements: As per ASTM B8, class B.
NEC Code: Compliant with Art. 725 PLTC, Art. 727 ITC, Art. 800 Communications, Art. 501 classified locations Class 1 Div.2 and Class 2 Div.2.
 

description

Conductor: Annealed electrolytic copper, 7-wire stranding, class B.
Insulation: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant).
Identification:
 

  Standard Intrinsically Safe
- Pair:                
- Triad:                
- Quad:                

Lay length: 50 mm (20 twists/m).
Unshielded pair: Polyester tape wrap.
Shield: Aluminium-polyester tape helical wrap plus tinned-copper drain-wire conductor, 7-wire stranding, class B.
Sheath: Black LSZH- HFFR (blue for intrinsically safe systems), fire-retardant; sunlight, and hydrocarbon-resistant. 
Stripping: Polyamide ripcord under the sheath.

optionals

Armour: Zinc-plated steel served-wire helical armour or aluminium interlock armour plus black LSZH sheath (blue for intrinsically safe systems); fire-retardant; sunlight and hydrocarbon-resistant. These cables are UL certified for direct earth burial.

See Technical Note # 8, "Wire armour properties"

installation

Assembly: Minimum bend radius is 7xOD (unarmoured versions) and 12xOD (armoured versions).
Maximum pulling tension: 5daN/mm2 on copper conductors. Wire-armoured cables can withstand 10daN/mm2 over the the armour wires.
Assembly temperature: 5ºC or higher.

alternatives

Construction requirements: As per ICEA S 73-532 (300V and 600V), British Standard 5308, EN 50288-7 and NBR 10300.
Materials:  Sheath LSZH–HFFR, thermoset; fire-retardant; sunlight  and hydrocarbon-resistant.

Tables

Electrical Characteristics



Description Unit 20 AWG /
0.52 sq mm
18 AWG /
0.82 sq mm
16 AWG /
1.31 sq mm
14 AWG /
2.08 sq mm
12 AWG /
3.31 sq mm
Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded
Electrical resistance at 20ºC in DC Ohm/km 35.78 35.78 22.78 22.78 14.25 14.25 8.94 8.94 5.63 5.63
Mutual capacitance between conductors pF/m 98 180 85 165 112 210 109 203 121 228
Characteristic impedance Ohm 76 41 88 50 66 35 68 37 62 33
Mutual inductance between conductors uH/km 588 588 641 641 544 544 553 553 522 522

pF/m = Mutual capacitance between conductors expressed in picoFarad/ per metre.
uH/km = Mutual inductance between conductors expressed in microHenry per kilometre.

Dimensions & Weight



Type Gauge AWG Standard Armoured
Conductor Drain wire Code Outside diameter
mm
Weight kg/km Code Under armour
diameter mm
Outside diameter
mm
Weight kg/km
Unshielded pair 20 -- AE 0500 4.9 31 AE 0500 H 4.9 8.5 153
Unshielded pair 18 -- AE 0510 5.6 41 AE 0510 H 5.6 9.2 178
Unshielded pair 16 -- AE 0520 6.2 54 AE 0520 H 6.2 10.3 214
Unshielded pair 14 -- AE 0530 7.7 83 AE 0530 H 7.7 11.9 276
Unshielded pair 12 -- AE 0580 8.7 113 AE 0580 H 8.7 12.9 328
Shielded pair 20 22 AE 5000 5.0 35 AE 5000 H 5.0 8.6 157
Shielded pair 18 20 AE 5100 5.7 47 AE 5100 H 5.7 9.3 185
Shielded pair 16 18 AE 5200 6.3 63 AE 5200 H 6.3 10.4 223
Shielded pair 14 18 AE 5300 7.8 92 AE 5300 H 7.8 12.0 286
Shielded pair 12 18 AE 5800 8.8 123 AE 5800 H 8.8 13.0 338
Shielded triad 20 22 AE 6000 5.3 43 AE 6000 H 5.3 8.9 171
Shielded triad 18 20 AE 6100 6.0 59 AE 6100 H 6.0 9.6 202
Shielded triad 16 18 AE 6200 6.7 80 AE 6200 H 6.7 10.8 251
Shielded triad 14 18 AE 6300 8.3 120 AE 6300 H 8.3 12.5 324
Shielded triad 12 18 AE 6800 9.3 163 AE 6800 H 9.3 13.5 389
Shielded quad 20 22 AE 9000 5.7 51 AE 9000 H 5.7 9.3 189
Shielded quad 18 20 AE 9100 6.5 71 AE 9100 H 6.5 10.6 237
Shielded quad 16 18 AE 9200 7.5 103 AE 9200 H 7.5 11.7 291
Shielded quad 14 18 AE 9300 9.0 149 AE 9300 H 9.0 13.2 369
Shielded quad 12 18 AE 9800 10.7 218 AE 9800 H 10.7 14.9 476

Cables are letter coded to the type of protection they include.
H = zinc-plated steel wire serve.