Block series YP-W

Copper tape shield

0.6/1kV
Flexible Cu 1 up to 630mm²
XLPE 90°C
Hydrocarbons and UV resistant PVC

Fixed power distribution lines for the oil and gas insdustry (Midstream and Downstream) For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Minimum temperature: Suitable for use in installations up to -30ºC

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IEC 60502-1 – IRAM 2178-1

  • Conductor requirements: IEC 60228 - IRAM NM 280

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Shield: Helical copper tape with 100% coverage and adequate overlap

  • Sheath: Flame retardant PVC, enhanced hydrocarbons resistance, UV resistant and suitable for low temperature ratings, with low hydrochloric acid emissions (HCl)

  • Fire requirements: As per IEC 60332-3-24

  • Hydrocarbons resistance standard: UIC 895 OR (Oil and gas fuel)

  • Outdoors requirements: As per UL 2556 (UV Resistance)

  • Halogen emissions standard: IEC 60754-1 (HCl emission < 15%)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Suitable for low temperatures

Suitable for low temperatures

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
3 Conductors including PE
4 Conductors
4 Conductors including PE
5 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
119.524.86---------0.1070.114
1.513.316.96---------0.1000.107
2.57.9810.18---------0.0930.100
44.956.31---------0.0880.095
63.34.210.1630.2060.1480.0830.090
101.912.440.1450.1880.1300.0780.085
161.211.540.1320.1750.1170.0750.082
250.780.990.1190.1620.1040.0750.083
350.5540.7070.1140.1580.1000.0730.081
500.3860.4930.1100.1540.0960.0730.080
700.2720.3480.1060.1500.0920.0710.079
950.2060.2640.1020.1460.0880.0700.077
1200.1610.2070.1000.1440.0860.0700.077
1500.1290.1670.0990.1420.0840.0700.077
1850.1060.1380.0990.1420.0840.0700.077
2400.08010.1060.0960.1400.0820.0690.077
3000.06410.08600.0950.1380.0800.0690.076
4000.04860.06750.0940.1380.080----
5000.03840.05570.0930.1370.079----
6300.02870.04510.0920.1360.078----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4)  Calculation of Inductive reactance valid for two-conductor, three-conductor, and five-conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Amper) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Amper)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
1------------------
1.5------2320----3228
2.5------3128----4437
4------4336----5748
645----544769747261
1062----7465931009783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor, and five-conductor cables.

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Diameter below shield mm External diameter mm Weight kg/km Code
1x169.011.8281YP 1160 W
1x2510.012.7357YP 1250 W
1x3511.113.9459YP 1350 W
1x5012.715.5606YP 1500 W
1x7014.617.5815YP 1700 W
1x9516.019.01011YP 1950 W
1x12018.221.11300YP 11200 W
1x15020.723.71609YP 11500 W
1x18523.026.21962YP 11850 W
1x24025.629.02519YP 12400 W
1x30029.032.63101YP 13000 W
1x40032.736.54050YP 14000 W
1x50037.241.25236YP 15000 W
1x63040.744.96556YP 16300 W
2x49.713.0261YP 0240 W
2x610.814.1322YP 0260 W
2x1012.615.9441YP 2100 W
2x1614.718.0602YP 2160 W
2x2518.021.3869YP 2250 W
2x3520.323.71137YP 2350 W
2x5023.526.91517YP 2500 W
2x7027.230.82044YP 2700 W
2x9530.534.32588YP 2950 W
2x12034.838.83358YP 21200 W
2x15039.944.14203YP 21500 W
2x18544.749.15184YP 21850 W
2x24050.054.86634YP 22400 W
2x30057.162.18304YP 23000 W
3x2.59.112.5244YP 0325 W
3x410.313.6301YP 0340 W
3x611.514.8378YP 0360 W
3x1013.416.8531YP 3100 W
3x1615.719.0739YP 3160 W
3x2519.222.61093YP 3250 W
3x3521.725.11428YP 3350 W
3x5025.228.61924YP 3500 W
3x7029.633.22646YP 3700 W
3x9532.736.53323YP 3950 W
3x12037.441.64350YP 31200 W
3x15043.347.75471YP 31500 W
3x18548.152.76687YP 31850 W
3x24054.259.08634YP 32400 W
3x30061.466.610731YP 33000 W
4x2.510.013.3274YP 0425 W
4x411.314.6353YP 0440 W
4x612.615.9448YP 0460 W
4x1014.818.1640YP 4100 W
4x1617.320.6902YP 4160 W
3x25+1x1620.323.71236YP 2516 W
3x35+1x1622.425.81554YP 3516 W
3x50+1x2526.329.72132YP 5025 W
3x70+1x3530.834.62945YP 7035 W
3x95+1x5034.438.43755YP 9550 W
3x120+1x7039.443.64935YP 12070 W
3x150+1x7044.448.85988YP 15070 W
3x185+1x9549.354.17379YP 18595 W
3x240+1x12055.860.89569YP 240120 W
3x300+1x15063.568.911890YP 300150 W