Clad series YP-F

Steel tape armour

0.6/1kV
Flexible Cu 1 up to 630mm²
XLPE 90°C
Hydrocarbons and UV resistant PVC

Fixed power distribution lines for the oil and gas insdustry (Midstream and Downstream) For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Minimum Temperature: Suitable for use in installations up to -30ºC

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IEC 60502-1 – IRAM 2178-1

  • Conductor requirements: IEC 60228 - IRAM NM 280

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Bedding: Flame retardant PVC

  • Armour: Single Conductor cables with Double aluminum helical tape.Multiconductor Cables con Double galvanized steel helical tapeThe use of armoured single conductor cables in A.C. systems, requires the armour to be of a non magnetic material.

  • Sheath: Flame retardant PVC, enhanced hydrocarbons resistance, UV resistant and suitable for low temperature ratings, with low hydrochloric acid emissions (HCl)

  • Fire requirements: As per IEC 60332-3-24

  • Hydrocarbons resistance standard: UIC 895 OR (Oil and gas fuel)

  • Outdoors requirements: As per UL 2556 (UV Resistance)

  • Halogen emissions Standard: IEC 60754-1 (HCl emission < 15%)

Fire-retardant

Fire-retardant

HCL < 15%

HCL < 15%

Flexible stranded conductors

Flexible stranded conductors

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Suitable for low temperatures

Suitable for low temperatures

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
3 Conductors including PE
4 Conductors
4 Conductors including PE
5 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
2.57.9810.18------0.0930.100
44.956.31------0.0880.095
63.34.21------0.0830.090
101.912.44------0.0780.085
161.211.540.1390.1830.1250.0750.082
250.780.990.1270.1700.1120.0750.083
350.5540.7070.1210.1650.1070.0730.081
500.3860.4930.1170.1600.1020.0730.080
700.2720.3480.1120.1550.0970.0710.079
950.2060.2640.1070.1510.0930.0700.077
1200.1610.2070.1050.1490.0910.0700.077
1500.1290.1670.1030.1470.0890.0700.077
1850.1060.1380.1020.1460.0880.0700.077
2400.08010.1060.1000.1430.0850.0690.077
3000.06410.08600.0980.1410.0830.0690.076
4000.04860.06750.0970.1400.082----
5000.03840.05570.0960.1390.081----
6300.02870.04510.0940.1380.080----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor, three-conductor, and five-conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Amper) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Amper)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
2.5------3128----4437
4------4336----5748
6------5447----7261
10------7465----9783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor, and five-conductor cables.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
1x168.713.1304YP 1C16 F
1x2510.414.8413YP 1C25 F
1x3511.516.1527YP 1C35 F
1x5013.117.7682YP 1C50 F
1x7015.019.6890YP 1C70 F
1x9516.421.01093YP 1C95 F
1x12018.623.41402YP 1C120 F
1x15021.125.91707YP 1C150 F
1x18523.428.42070YP 1C185 F
1x24026.031.22638YP 1C240 F
1x30029.434.83234YP 1C300 F
1x40032.738.34162YP 1C400 F
1x50037.243.05361YP 1C500 F
1x63040.946.96713YP 1C630 F
2x410.113.9317YP 2C4 F
2x611.215.0382YP 2C6 F
2x1013.016.8509YP 2C10 F
2x1615.118.9678YP 2C16 F
2x2518.422.2957YP 2C25 F
2x3520.724.51219YP 2C35 F
2x5023.927.71606YP 2C50 F
2x7027.631.62143YP 2C70 F
2x9530.534.72658YP 2C95 F
2x12034.840.63844YP 2C120 F
2x15040.146.14772YP 2C150 F
2x18544.550.95781YP 2C185 F
2x24050.056.47264YP 2C240 F
2x30056.963.79000YP 2C300 F
3x2.59.513.3291YP 3C2.5 F
3x410.714.5360YP 3C4 F
3x611.915.7442YP 3C6 F
3x1013.817.6604YP 3C10 F
3x1616.119.9822YP 3C16 F
3x2519.623.41177YP 3C25 F
3x3522.125.91520YP 3C35 F
3x5025.629.62040YP 3C50 F
3x7029.633.82743YP 3C70 F
3x9532.738.53815YP 3C95 F
3x12037.443.44885YP 3C120 F
3x15043.149.36053YP 3C150 F
3x18548.154.57353YP 3C185 F
3x24054.060.89368YP 3C240 F
3x30061.468.411550YP 3C300 F
4x2.510.414.2332YP 4C2.5 F
4x411.715.5417YP 4C4 F
4x613.016.8519YP 4C6 F
4x1015.219.0721YP 4C10 F
4x1617.721.5994YP 4C16 F
4x2521.725.51438YP 4C25 F
4x3524.528.31872YP 4C35 F
4x5028.432.62542YP 4C50 F
4x7032.938.53806YP 4C70 F
4x9536.442.44737YP 4C95 F
4x12041.848.06112YP 4C120 F
4x15048.254.67570YP 4C150 F
4x18553.760.39206YP 4C185 F
4x24060.367.511795YP 4C240 F
3x25/1620.724.51326YP 3C25/16 F
3x35/1622.826.61650YP 3C35/16 F
3x50/2526.730.72255YP 3C50/25 F
3x70/3530.835.03033YP 3C70/35 F
3x95/5034.440.24259YP 3C95/50 F
3x120/7039.645.65528YP 3C120/70 F
3x150/7044.250.66620YP 3C150/70 F
3x185/9549.355.78051YP 3C185/95 F
3x240/12055.662.410314YP 3C240/120 F
3x300/15063.570.712759YP 3C300/150 F
4x1.5+PE1.510.113.9308YP 4C1.5G1.5 F
4x2.5+PE2.511.315.1380YP 4C2.5G2.5 F
4x4+PE412.716.5483YP 4C4G4 F
4x6+PE614.218.0607YP 4C6G6 F
4x10+PE1016.720.5854YP 4C10G10 F
4x16+PE1619.523.31189YP 4C16G16 F
4x25+PE2523.927.71712YP 4C25G25 F
4x35+PE3527.131.12256YP 4C35G35 F
4x50+PE5031.435.83072YP 4C50G50 F
4x70+PE7036.442.24572YP 4C70G70 F
4x95+PE9540.546.75728YP 4C95G95 F
4x120+PE12046.653.07401YP 4C120G120 F
4x150+PE15053.660.29165YP 4C150G150 F
4x185+PE18559.866.811186YP 4C185G185 F
3x25/16+PE1622.226.01492YP 3C25/16G16 F
3x35/16+PE1624.027.81807YP 3C35/16G16 F
3x50/25+PE2528.432.62518YP 3C50/25G25 F
3x70/35+PE3532.738.33754YP 3C70/35G35 F
3x95/50+PE5036.842.84777YP 3C95/50G50 F
3x120/70+PE7042.448.66242YP 3C120/70G70 F
3x150/70+PE7046.853.27299YP 3C150/70G70 F
3x185/95+PE9552.158.78938YP 3C185/95G95 F
3x240/120+PE12058.965.911481YP 3C240/120G120 F
3x300/150+PE15067.374.714205YP 3C300/150G150 F
4x25+PE1623.126.91600YP 4C25G16 F
4x35+PE1625.529.52035YP 4C35G16 F
4x50+PE2529.934.12781YP 4C50G25 F
4x70+PE3534.540.34166YP 4C70G35 F
4x95+PE5038.744.75245YP 4C95G50 F
4x120+PE7044.651.06834YP 4C120G70 F
4x150+PE7050.156.58188YP 4C150G70 F
4x185+PE9555.862.610025YP 4C185G95 F
4x240+PE12063.170.312888YP 4C240G120 F
2x2.5+PE2.59.513.3291YP 2C2.5G2.5 F
2x4+PE410.714.5360YP 2C4G4 F
2x6+PE611.915.7442YP 2C6G6 F
2x10+PE1013.817.6604YP 2C10G10 F
2x16+PE1616.119.9822YP 2C16G16 F
2x25+PE2519.623.41177YP 2C25G25 F
2x35+PE3522.125.91520YP 2C35G35 F
2x50+PE5025.629.62040YP 2C50G50 F
2x70+PE7029.633.82743YP 2C70G70 F
2x95+PE9532.738.53815YP 2C95G95 F
2x120+PE12037.443.44885YP 2C120G120 F
2x150+PE15043.149.36053YP 2C150G150 F
2x185+PE18548.154.57353YP 2C185G185 F
2x240+PE24054.060.89368YP 2C240G240 F
2x300+PE30061.468.411550YP 2C300G300 F
2x25+PE1619.423.21092YP 2C25G16 F
2x35+PE1620.924.71325YP 2C35G16 F
2x50+PE2524.728.51793YP 2C50G25 F
2x70+PE3528.332.32393YP 2C70G35 F
2x95+PE5031.936.13036YP 2C95G50 F
2x120+PE7036.642.44402YP 2C120G70 F
2x150+PE7040.046.05189YP 2C150G70 F
2x185+PE9544.650.86331YP 2C185G95 F
2x240+PE12050.556.98060YP 2C240G120 F
2x300+PE15057.764.59990YP 2C300G150 F
3x2.5+PE2.510.414.2332YP 3C2.5G2.5 F
3x4+PE411.715.5417YP 3C4G4 F
3x6+PE613.016.8519YP 3C6G6 F
3x10+PE1015.219.0721YP 3C10G10 F
3x16+PE1617.721.5994YP 3C16G16 F
3x25+PE2521.725.51438YP 3C25G25 F
3x35+PE3524.528.31872YP 3C35G35 F
3x50+PE5028.432.62542YP 3C50G50 F
3x70+PE7032.938.53806YP 3C70G70 F
3x95+PE9536.442.44737YP 3C95G95 F
3x120+PE12041.848.06112YP 3C120G120 F
3x150+PE15048.254.67570YP 3C150G150 F
3x185+PE18553.760.39206YP 3C185G185 F
3x240+PE24060.367.511795YP 3C240G240 F
3x25/1620.724.51326YP 3C25/16 F
3x35/1622.826.61650YP 3C35/16 F
3x50/2526.730.72255YP 3C50/25 F
3x70/3530.835.03033YP 3C70/35 F
3x95/5034.440.24259YP 3C95/50 F
3x120/7039.645.65528YP 3C120/70 F
3x150/7044.250.66620YP 3C150/70 F
3x185/9549.355.78051YP 3C185/95 F
3x240/12055.662.410314YP 3C240/120 F
3x300/15063.570.712759YP 3C300/150 F