Marlew

Clad series XF-F

0.6/1kV
Flexible Cu 2.5 up to 630mm²
XLPE 90°C / PVC
No PE conductor

Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Bedding: PVC

  • Armour: Single Conductor Cables with double aluminum helical tape.Multiconductor Cables with double galvanized steel helical tapeThe use of armoured single conductor cables in A.C. systems, requires the armour to be of a non-magnetic material.

  • Sheath: Flame retardant PVC

  • Fire requirements: As per IEC 60332-1

  • Outdoors requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
4 Conductos

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and reactance

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
119.524.860.1670.210.1520.1070.114
1.513.316.960.1570.20.1420.10.107
2.57.9810.180.1450.1890.1310.0930.1
44.956.310.1370.180.1220.0880.095
63.34.210.1280.1720.1130.0830.09
101.912.440.1180.1620.1040.0780.085
161.211.540.1120.1550.0970.0750.082
250.780.990.1090.1520.0940.0750.083
350.5540.7070.1050.1480.090.0730.081
500.3860.4930.1020.1450.0870.0730.08
700.2720.3480.0980.1420.0840.0710.079
950.2060.2640.0960.1390.0810.070.077
1200.1610.2070.0950.1380.080.070.077
1500.1290.1670.0940.1370.0790.070.077
1850.1060.1380.0940.1370.0790.070.077
2400.08010.1060.0920.1360.0770.0690.077
3000.06410.0860.0910.1350.0760.0690.076
4000.04860.06750.090.1340.076----
5000.03840.05570.090.1330.075----
6300.02870.04510.0860.130.072----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
1------------------
1.519----232032353228
2.526----312843464437
434----433655595748
645----544769747261
1062----7465931009783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code Mat Number Previous Code
1x1610.014.4347XF-F 1x16830004010XF 1160 DNe
1x2510.014.4399XF-F 1x25830004020XF 1250 DNe
1x3511.115.5504XF-F 1x35830004030XF 1350 DNe
1x5012.717.1657XF-F 1x50830004040XF 1500 DNe
1x7014.619.2871XF-F 1x70830004050XF 1700 DNe
1x9516.020.61073XF-F 1x95830004060XF 1950 DNe
1x12018.222.81369XF-F 1x120830004070XF 11200 DNe
1x15020.725.51682XF-F 1x150830004080XF 11500 DNe
1x18523.027.82029XF-F 1x185830004090XF 11850 DNe
1x24025.630.62594XF-F 1x240830004100XF 12400 DNe
1x30029.034.23184XF-F 1x300830004110XF 13000 DNe
1x40032.738.14142XF-F 1x400830004120XF 14000 DNe
1x50037.242.85339XF-F 1x500830004130XF 15000 DNe
1x63040.746.76687XF-F 1x630830004140XF 16300 DNe
2x410.013.8317XF-F 2x4830004150XF 0240 FNe
2x610.814.6369XF-F 2x6830004160XF 0260 FNe
2x1012.616.4496XF-F 2x10830004170XF 2100 FNe
2x1614.718.5665XF-F 2x16830004180XF 2160 FNe
2x2518.021.8946XF-F 2x25830004190XF 2250 FNe
2x3520.324.11210XF-F 2x35830004200XF 2350 FNe
2x5023.527.31600XF-F 2x50830004210XF 2500 FNe
2x7027.231.22140XF-F 2x70830004220XF 2700 FNe
2x9530.534.72695XF-F 2x95830004230XF 2950 FNe
2x12034.840.43872XF-F 2x120830004240XF 21200 FNe
2x15039.945.94810XF-F 2x150830004250XF 21500 FNe
2x18544.750.95863XF-F 2x185830004260XF 21850 FNe
2x24050.056.47365XF-F 2x240830004270XF 22400 FNe
2x30057.163.79136XF-F 2x300830004280XF 23000 FNe
3x2.510.013.8310XF-F 3x2.5830004290XF 0325 FNe
3x410.314.1346XF-F 3x4830004300XF 0340 FNe
3x611.515.3428XF-F 3x6830004310XF 0360 FNe
3x1013.417.2589XF-F 3x10830004320XF 3100 FNe
3x1615.719.5807XF-F 3x16830004330XF 3160 FNe
3x2519.223.01162XF-F 3x25830004340XF 3250 FNe
3x3521.725.51506XF-F 3x35830004350XF 3350 FNe
3x5025.229.02013XF-F 3x50830004360XF 3500 FNe
3x7029.633.62751XF-F 3x70830004370XF 3700 FNe
3x9532.737.13454XF-F 3x95830004380XF 3950 FNe
3x12037.443.24901XF-F 3x120830004390XF 31200 FNe
3x15043.349.56128XF-F 3x150830004400XF 31500 FNe
3x18548.154.57415XF-F 3x185830004410XF 31850 FNe
3x24054.260.89451XF-F 3x240830004420XF 32400 FNe
3x30061.468.411655XF-F 3x300830004430XF 33000 FNe
4x2.510.013.8318XF-F 4x2.5830004540XF 0425 FNe
4x411.315.1402XF-F 4x4830004550XF 0440 FNe
4x612.616.4503XF-F 4x6830004560XF 0460 FNe
4x1014.818.6705XF-F 4x10830004570XF 4100 FNe
4x1617.321.1977XF-F 4x16830004580XF 4160 FNe
4x2521.325.11421XF-F 4x25830004590XF 4250 FNe
4x3524.127.91856XF-F 4x35830004600XF 4350 FNe
4x5028.032.02511XF-F 4x50830004610XF 4500 FNe
4x7032.937.13439XF-F 4x70830004620XF 4700 FNe
4x9536.442.24743XF-F 4x95830004630XF 4950 FNe
4x12042.048.26172XF-F 4x120830004640XF 41200 FNe
4x15048.254.67617XF-F 4x150830004650XF 41500 FNe
4x18553.560.19235XF-F 4x185830004660XF 41850 FNe
4x24060.367.311840XF-F 4x240830004670XF 42400 FNe
3x25+1x1620.324.11309XF-F 3x25/16830004680XF 2516 FNe
3x35+1x1622.426.21633XF-F 3x35/16830004690XF 3516 FNe
3x50+1x2526.330.12225XF-F 3x50/25830004700XF 5025 FNe
3x70+1x3530.835.03053XF-F 3x70/35830004710XF 7035 FNe
3x95+1x5034.440.04263XF-F 3x95/50830004720XF 9550 FNe
3x120+1x7039.445.45535XF-F 3x120/70830004730XF 12070 FNe
3x150+1x7044.450.66662XF-F 3x150/70830004740XF 15070 FNe
3x185+1x9549.355.78101XF-F 3x185/95830004750XF 18595 FNe
3x240+1x12055.862.610410XF-F 3x240/120830004760XF 240120 FNe
3x300+1x15063.570.512812XF-F 3x300/150830004770XF 300150 FNe