Suitable for fixed indoor installations in buildings. Cable suitable for grounding, identified with the corresponding color according to the standards used. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.
Standard | |
---|---|
Conductors | |
Single | color of choice |
Gauge AWG/MCM | Class | Electrical resistance at 20ºC in C.C. Ohm/km | Current-carrying capacity (1) (Ampere) | Primary insulation thicknessmm | Secondary insulation thicknessmm | External diameter mm | Weight kg/km | Code |
---|---|---|---|---|---|---|---|---|
14 | B | 8.62 | 35 | 0.38 | 0.11 | 2.8 | 24 | UY83 0114 |
12 | B | 5.43 | 40 | 0.38 | 0.11 | 3.3 | 36 | UY83 0112 |
10 | B | 3.41 | 55 | 0.51 | 0.11 | 4.2 | 58 | UY83 0110 |
8 | B | 2.14 | 80 | 0.76 | 0.14 | 5.5 | 92 | UY83 0108 |
6 | B | 1.35 | 105 | 0.76 | 0.14 | 6.4 | 141 | UY83 0106 |
4 | B | 0.848 | 140 | 1.02 | 0.16 | 8.2 | 227 | UY83 0104 |
2 | B | 0.543 | 190 | 1.02 | 0.16 | 9.7 | 347 | UY83 0102 |
(1) Values refered to a conductor temperature of 90ºC and an ambient temperature of 30ºC, for three cables in free air according to chart 310.15 (B)(17) of the NFPA70.