Marlew

Clad series TKC

600 Volt
Cu 14 up to 10 AWG
XLPE 90°C / PVC
CSA 22.2 N°131

Control, signalling, measuring and protective equipment, electric controls of mining, industrial and petrochemical projects For dry and wet locations, fixed on trays, indoors or outdoors, buried in ducts or directly buried. Suitable for mobile installations at low temperatures Manufactured in compliance with the Canadian Electrical Code CEC

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Minimum operating temperature: -40°C

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: CSA 22.2 N°131

  • Conductor requirements: ASTM B8

  • Conductor: Annealed electrolytic copper conductor, class B stranding

  • Bonding: In all cable formations these cables have a bare copper bonding conductor (PE)

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Inner Sheath: Flame retardant PVC

  • Armour: Aluminum tape interlock armour

  • External Sheath: Flame retardant PVC and UV resistant

  • Fire requirements: As per FT1

  • Outdoors requirements: As per CSA 22.2 N° 2556 (UV rays)

  • Acid gas evolution: CSA 22.2 N° 2556 (Low HCl content)

Flame retardant

Flame retardant

HCL < 15%

HCL < 15%

High flexibility

High flexibility

Hydrocarbon resistant

Hydrocarbon resistant

UV resistant

UV resistant

Impact resistant

Impact resistant

Identification

Standard
Sheath Conductors
2 Conductors
3 Conductors
4 Conductors
5 Conductors (=>)alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Alternative interlock armour (made of galvanized steel tape) can be manufactured upon request

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 37x
148.7911.21252017.512.512.511.310
125.547.06302421151513.512
103.484.4440322820201816

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation Diameter below armour mm Diameter under armour mm External diameter mm Weight kg/ km Code Mat Number
Fase conductor Bonding conductor (1)
N° Cond. x gauge AWG/MCM Gauge AWG
2 x 14149.616.419.4360TKC 2x14820046270
3 x 141410.817.720.7411TKC 3x14820046280
4 x 141412.019.022.0463TKC 4x14820046290
5 x 141412.019.022.0490TKC 5x14820046300
6 x 141412.719.622.6531TKC 6x14820046310
7 x 143 x 1814.521.524.5619TKC 7x14820046320
9 x 141417.024.127.1713TKC 9x14820046330
12 x 141418.225.328.3821TKC 12x14820046340
15 x 141420.227.930.91027TKC 15x14820046350
19 x 143 x 1823.931.734.71273TKC 19x14820046360
25 x 141425.132.935.91466TKC 25x14820046370
30 x 141427.635.538.51663TKC 30x14820046380
37 x 143 x 1830.138.041.01921TKC 37x14820046390
2 x 121410.217.120.1399TKC 2x12820046140
3 x 121411.418.321.3463TKC 3x12820046150
4 x 121412.719.622.6528TKC 4x12820046160
5 x 121413.320.223.2580TKC 5x12820046170
6 x 121415.222.125.2679TKC 6x12820046180
7 x 123 x 1617.024.127.1765TKC 7x12820046190
9 x 121418.225.328.3859TKC 9x12820046200
12 x 121420.227.930.91109TKC 12x12820046210
15 x 121422.730.433.41328TKC 15x12820046220
19 x 123 x 1626.434.237.21603TKC 19x12820046230
25 x 121427.635.538.51859TKC 25x12820046240
30 x 121430.138.041.02122TKC 30x12820046250
37 x 123 x 1633.841.844.82513TKC 37x12820046260
2 x 101211.418.321.3476TKC 2x10820046010
3 x 101212.719.622.6558TKC 3x10820046020
4 x 101214.521.524.5677TKC 4x10820046030
5 x 101215.222.125.2753TKC 5x10820046040
6 x 101217.024.127.1842TKC 6x10820046050
7 x 103 x 1617.024.127.1906TKC 7x10820046060
9 x 101221.429.132.11211TKC 9x10820046070
12 x 101223.931.734.71500TKC 12x10820046080
15 x 101225.132.935.91712TKC 15x10820046090
19 x 103 x 1627.635.538.52014TKC 19x10820046100
25 x 101231.339.342.32475TKC 25x10820046110
30 x 101235.143.146.12867TKC 30x10820046120
37 x 103 x 1636.044.447.43416TKC 37x10820046130

(1) For 7, 19 and 37-conductor cables, the bonding is divided in three conductors. For the remaing formations, it is gathered in only one conductor together with the phases.