series VF 3+3

600 Volt
Cu 14 AWG up to 400 MCM
XLPE 90°C
3 PE Conductors

Variable frequency drive motor feed. (VFD) For Alternating Current (60Hz), for single-phase systems (110V), three-phase systems (190/210V) and systems with voltages up to 600V. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 95-658

  • Conductor requirements: Serie ASTM B172 up to B174

  • Conductor: Annealed electrolytic copper - Flexible stranding

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Conductors’ assembly: 3 phases + 3 protection conductors (PE) gathered in between the gaps of the phases, conforming a symmetrical cable

  • Bedding: PVC

  • Shield: Conformed by a concentric conductor made of copper wires plus an additional copper tape with adequate overlap and 100% coverage. The shield cross-section is indicated in the electrical characteristics table.

  • Sheath: Flame retardant PVC, sunlight, and mineral oil resistant

  • Fire requirements: As per FT1 (UL 1581)

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (rayos UV)

Electromagnetic interference protection

Electromagnetic interference protection

Flame retardant

Flame retardant

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Conductor’s gauge (AWG) Earthing conductor PE cable formation (PE) (3xAWG) Concentric conductor gauge (AWG) Electrical resistance at 20°C in C.C. Ohm/km Electrical resistance at 20°C en C.C. Concentric conductor Ohm/km Electrical resistance at 90°C en C.C. Ohm/km Electrical resistance at 90°C en C.C. Concentric conductor Ohm/km Inductive reactance at 60Hz (Ohm/Km) Intensidad admisible (Ampere)
143x18108.778.7711.1911.190.09825
123x14105.525.527.047.040.09230
103x14103.483.484.434.430.08640
83x14102.193.482.794.430.09055
63x1281.402.191.782.790.08475
43x1280.8802.191.122.790.08095
23x1060.5561.400.7091.780.077130
13x1060.4391.400.5601.780.078145
1/03x1060.3511.400.4481.780.076170
2/03x1060.2791.400.3581.780.074195
3/03x840.2210.8800.2841.120.072225
4/03x840.1750.8800.2261.120.071260
2503x840.1500.8800.1941.120.072290
3003x730.1250.6990.1630.8930.071320
3503x730.1070.6990.1400.8930.070350
4003x730.09370.6990.1240.8930.070380

Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG Diameter below shield mm External diameter mm Weight kg/km Code
3 x 14 + 3 x 1810.314.6299VF 0314 0318
3 x 12 + 3 x 1412.416.7405VF 0312 0314
3 x 10 + 3 x 1413.718493VF 0310 0314
3 x 8 + 3 x 141620.3641VF 0308 0314
3 x 6 + 3 x 1218.523.8945VF 0306 0312
3 x 4 + 3 x 1220.425.71222VF 0304 0312
3 x 2 + 3 x 1023.228.51717VF 0302 0310
3 x 1 + 3 x 1026.531.82066VF 0301 0310
3 x 1/0 + 3 x 1029.134.42416VF 31/0 0310
3 x 2/0 + 3 x 1031.937.22896VF 32/0 0310
3 x 3/0 + 3 x 835.440.73659VF 33/0 0308
3 x 4/0 + 3 x 838.645.44504VF 34/0 0308
3 x 250 + 3 x 843.650.45338VF 3250 0308
3 x 300 + 3 x 747.554.36258VF 3300 0307
3 x 350 + 3 x 749.656.56995VF 3350 0307
3 x 400 + 3 x 752.259.17762VF 3400 0307