Marlew

series VF 3+3

600 Volt
Cu 14 AWG up to 400 MCM
XLPE 90°C
3 PE Conductors

Variable frequency drive motor feed. (VFD) For Alternating Current (60Hz), for single-phase systems (110V), three-phase systems (190/210V) and systems with voltages up to 600V. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 95-658

  • Conductor requirements: Serie ASTM B172 up to B174

  • Conductor: Annealed electrolytic copper - Flexible stranding

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Conductors’ assembly: 3 phases + 3 protection conductors (PE) gathered in between the gaps of the phases, conforming a symmetrical cable

  • Bedding: Double helical wrapping

  • Shield: Composed of a concentric conductor made of copper wires plus an anti-unwinding copper tape. The electrical resistance of the shield is indicated in the electrical characteristics table.

  • Sheath: Flame retardant PVC, sunlight, and mineral oil resistant

  • Flame propagation standard: As per FT1 (UL 1581)

  • Fire spread prevention standard: As per ICEA T 30-520

  • Outdoors requirements: As per UL 2556 (rayos UV)

Electromagnetic interference protection

Electromagnetic interference protection

Flame retardant

Flame retardant

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Conductor’s gauge (AWG) Earthing conductor PE cable formation (PE) (3xAWG) Concentric conductor gauge (AWG) Electrical resistance at 20°C in C.C. Ohm/km Electrical resistance at 20°C en C.C. Concentric conductor Ohm/km Electrical resistance at 90°C en C.C. Ohm/km Electrical resistance at 90°C en C.C. Concentric conductor Ohm/km Inductive reactance at 60Hz (Ohm/Km) Intensidad admisible (Ampere)
143x18108.778.7711.1911.190.09825
123x14105.525.527.047.040.09230
103x14103.483.484.434.430.08640
83x14102.193.482.794.430.09055
63x1281.402.191.782.790.08475
43x1280.8802.191.122.790.08095
23x1060.5561.400.7091.780.077130
13x1060.4391.400.5601.780.078145
1/03x1060.3511.400.4481.780.076170
2/03x1060.2791.400.3581.780.074195
3/03x840.2210.8800.2841.120.072225
4/03x840.1750.8800.2261.120.071260
2503x840.1500.8800.1941.120.072290
3003x730.1250.6990.1630.8930.071320
3503x730.1070.6990.1400.8930.070350
4003x730.09370.6990.1240.8930.070380

Allowable ampacity for three-conductor cables installed in conduits or direct-buried, at an ambient temperature of 30°C, in accordance with Table 310.15(B)(16) of NFPA 70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG Shield diameter (mm) External diameter mm Weight kg/km Code Mat Number
3 x 10 + 3 x 1413.718493VF 3x10+3G14+Sh10%830123210
3 x 8 + 3 x 141620.3641VF 3x8+3G14+Sh10%830123220
3 x 6 + 3 x 1218.523.8945VF 3x6+3G12+Sh10%830123230
3 x 4 + 3 x 1220.425.71222VF 3x4+3G12+Sh10%830123240
3 x 2 + 3 x 1023.228.51717VF 3x2+3G10+Sh10%830123250
3 x 1 + 3 x 1026.531.82066VF 3x1+3G10+Sh10%830123260
3 x 1/0 + 3 x 1029.134.42416VF 3x1/0+3G10+Sh10%830123270
3 x 2/0 + 3 x 1031.937.22896VF 3x2/0+3G10+Sh10%830123280
3 x 3/0 + 3 x 835.440.73659VF 3x3/0+3G8+Sh10%830123290
3 x 4/0 + 3 x 838.645.44504VF 3x4/0+3G8+Sh10%830123300
3 x 250 + 3 x 843.650.45338VF 3x250+3G8+Sh10%830123310
3 x 300 + 3 x 747.554.36258VF 3x300+3G7+Sh10%830123320
3 x 350 + 3 x 749.656.56995VF 3x350+3G7+Sh10%830123330
3 x 400 + 3 x 752.259.17762VF 3x400+3G7+Sh10%830123340

The tolerance for the reported diameters shall be between -5% and +8%.