series U83

600 Volt
Cu 14 AWG up to 500 MCM
THW-2
UL 83

Suitable for fixed indoor installations in buildings. Cable suitable for grounding, identified with the corresponding color according to the standards used. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90°C

  • Voltage rating: 600 Volt

  • Construction requirements: UL 83

  • Conductor requirements: ASTM B8

  • Conductor: Annealed electrolytic copper conductor, class B stranding o C

  • Insulation: THW-2 (Special PVC Compound)

  • Fire requirements: As per FT1

  • OilS Resistance: OIL RES I

  • NEC Code (NFPA 70): Art. 310

Flame retardant

Flame retardant

Mineral oil resistant

Mineral oil resistant

Industrial applications

Industrial applications

Dwelling installation

Dwelling installation

NEC cod

NEC cod

Wet locations

Wet locations

Identification

Standard
Conductors
Single conductor color of choice

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS, DIMENSIONS & WEIGHT

Gauge AWG/MCM Class Electrical resistance at 20ºC in C.C. Ohm/km Current-carrying capacity (1) (Ampere) Insulation thickness mm External diameter mm Weight kg/km Code
14B8.62350.763.428U83 0114
12B5.43400.763.940U83 0112
10B3.41550.764.560U83 0110
8B2.14801.14699U83 0108
6B1.351051.527.7160U83 0106
4B0.8481401.528.9240U83 0104
2B0.5431901.5210.4362U83 0102
1B0.4232202.0312.4466U83 0101
1/0B0.3352602.0313.5579U83 11/0
2/0B0.2663002.0314.6714U83 12/0
3/0B0.2113502.0315884U83 13/0
4/0C0.1674052.0317.41090U83 14/0
250B0.1424552.4119.31304U83 1250
300B0.1185002.4120.71541U83 1300
350B0.1015702.4122.11813U83 1350
400C0.08856152.4123.22020U83 1400
500C0.07097002.4125.32472U83 1500

(1) Values refered to a conductor temperature of 90ºC and an ambient temperature of 30ºC, for three cables in free air according to chart 310.15 (B)(17) of the NFPA70.