Clad series RP-F

Steel tape armour

0.6/1kV
Flexible Cu 1 up to 630mm²
Insulation (MICA+XLPE)
No PE conductor

For fixed power distribution networks for alternating current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 62266 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: Mica tape + XLPE (Cross-Linked Polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Single Conductor cables with double helical aluminum tape.Multiconductor cables with double galvanized steel helical tape.The use of armoured single conductor cables in A.C. systems, requires the armour to be of a non magnetic material.

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Fire resistance standards: As per IEC 60331-21 (70000 BTU-750°C applied for 90 minutes)

  • Standard for Halogen absense and corrosive gases: IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: suitable for AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Fire-resistant

Fire-resistant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Special design can be manufactured to comply with reinforced circuit integrity, complying with other standards such as IEC 60331-1/2, EN 50200 or BS 6387.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
2.57.9810.18------0.1030.110
44.956.31------0.0970.105
63.34.21------0.0900.098
101.912.44------0.0840.091
161.211.540.1480.1910.1330.0820.089
250.780.990.1340.1780.1200.0790.087
350.5540.7070.1250.1690.1110.0770.084
500.3860.4930.1190.1620.1040.0760.083
700.2720.3480.1140.1570.0990.0740.082
950.2060.2640.1090.1530.0940.0720.079
1200.1610.2070.1070.1510.0930.0720.079
1500.1290.1670.1040.1480.0900.0710.079
1850.1060.1380.1030.1470.0890.0720.079
2400.08010.1060.1010.1440.0860.0710.078
3000.06410.08600.0990.1430.0850.0700.077
4000.04860.06750.0980.1410.083----
5000.03840.05570.0970.1400.082----
6300.02870.04510.0950.1390.081----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
2.5------3128----4437
4------4336----5748
6------5447----7261
10------7465----9783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter below armour mm External diameter mm Weight kg/km Code
1 x 1612.016.4421RP 1160 D
1 x 2512.016.4477RP 1250 D
1 x 3512.016.4542RP 1350 D
1 x 5013.317.7686RP 1500 D
1 x 7015.520.1913RP 1700 D
1 x 9517.522.11136RP 1950 D
1 x 12019.223.81,403RP 11200 D
1 x 15021.526.31,702RP 11500 D
1 x 18523.428.22,017RP 11850 D
1 x 24026.631.62,588RP 12400 D
1 x 30029.734.93,192RP 13000 D
1 x 40034.039.44,143RP 14000 D
1 x 50037.443.05,126RP 15000 D
1 x 63042.748.76,747RP 16300 D
2 x 412.015.8398RP 0240 F
2 x 612.115.9424RP 0260 F
2 x 1014.218.0569RP 2100 F
2 x 1616.520.3756RP 2160 F
2 x 2519.223.01021RP 2250 F
2 x 3521.225.01,277RP 2350 F
2 x 5024.628.41,688RP 2500 F
2 x 7029.033.02,277RP 2700 F
2 x 9533.437.62,926RP 2950 F
2 x 12036.742.34,038RP 21200 F
2 x 15041.447.44,935RP 21500 F
2 x 18545.651.85,884RP 21850 F
2 x 24051.958.37,481RP 22400 F
2 x 30058.765.39,263RP 23000 F
3 x 2.512.015.8389RP 0325 F
3 x 412.015.8415RP 0340 F
3 x 612.916.7488RP 0360 F
3 x 1015.118.9669RP 3100 F
3 x 1617.721.5906RP 3160 F
3 x 2520.624.41,245RP 3250 F
3 x 3522.826.61,585RP 3350 F
3 x 5026.430.22,114RP 3500 F
3 x 7031.535.52,903RP 3700 F
3 x 9535.840.23,708RP 3950 F
3 x 12039.545.35,073RP 31200 F
3 x 15045.051.26,249RP 31500 F
3 x 18549.055.47,407RP 31850 F
3 x 24056.362.99,526RP 32400 F
3 x 30063.170.111,758RP 33000 F
4 x 2.512.015.8395RP 0425 F
4 x 412.816.6464RP 0440 F
4 x 614.318.1573RP 0460 F
4 x 1016.720.5797RP 4100 F
4 x 1619.623.41092RP 4160 F
3 x 25 + 1 x 1622.025.81,411RP 2516 F
3 x 35 + 1 x 1623.927.71,733RP 3516 F
3 x 50 + 1 x 2527.731.52,340RP 5025 F
3 x 70 + 1 x 3532.736.93,212RP 7035 F
3 x 95 + 1 x 5037.342.94,545RP 9550 F
3 x 120 + 1 x 7041.747.75,733RP 12070 F
3 x 150 + 1 x 7046.452.66,811RP 15070 F
3 x 185 + 1 x 9551.057.48,169RP 18595 F
3 x 240 + 1 x 12058.265.010,502RP 240120 F
3 x 300 + 1 x 15065.472.412,918RP 300150 F