Marlew

Clad series RP-F

0.6/1kV
Flexible Cu 1 up to 630mm²
Insulation (MICA+XLPE)
No PE conductor

For fixed power distribution networks for alternating current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 62266 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: Mica tape + XLPE (Cross-Linked Polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Single Conductor cables with double helical aluminum tape.Multiconductor cables with double galvanized steel helical tape.The use of armoured single conductor cables in A.C. systems, requires the armour to be of a non magnetic material.

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Fire resistance standards: As per IEC 60331-21 (70000 BTU-750°C applied for 90 minutes)

  • Standard for Halogen absense and corrosive gases: IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: suitable for AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Fire-resistant

Fire-resistant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Special design can be manufactured to comply with reinforced circuit integrity, complying with other standards such as IEC 60331-1/2, EN 50200 or BS 6387.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
2.57.9810.18------0.1030.110
44.956.31------0.0970.105
63.34.21------0.0900.098
101.912.44------0.0840.091
161.211.540.1480.1910.1330.0820.089
250.780.990.1340.1780.1200.0790.087
350.5540.7070.1250.1690.1110.0770.084
500.3860.4930.1190.1620.1040.0760.083
700.2720.3480.1140.1570.0990.0740.082
950.2060.2640.1090.1530.0940.0720.079
1200.1610.2070.1070.1510.0930.0720.079
1500.1290.1670.1040.1480.0900.0710.079
1850.1060.1380.1030.1470.0890.0720.079
2400.08010.1060.1010.1440.0860.0710.078
3000.06410.08600.0990.1430.0850.0700.077
4000.04860.06750.0980.1410.083----
5000.03840.05570.0970.1400.082----
6300.02870.04510.0950.1390.081----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
2.5------3128----4437
4------4336----5748
6------5447----7261
10------7465----9783
1683----10086121129129107
25122158117128109157168166141
35152196146160137188201200168
50187238179195166220236238199
70241305232250213271290292243
95295371283304257326349351293
120346432332354299371396399333
150401499384409345415444448373
185461572441468394470503508425
240548675524554465547586592493
300637780608640537621665669559
400751938712----710759----
5008631083818----825882----
6309951257941----9411007----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) Diameter below armour mm External diameter mm Weight kg/km Code Mat Number Previous Code
1 x 1612.016.4421RP-F 1x16830063460RP 1160 D
1 x 2512.016.4477RP-F 1x25830063470RP 1250 D
1 x 3512.016.4542RP-F 1x35830063480RP 1350 D
1 x 5013.317.7686RP-F 1x50830063490RP 1500 D
1 x 7015.520.1913RP-F 1x70830063500RP 1700 D
1 x 9517.522.11136RP-F 1x95830063510RP 1950 D
1 x 12019.223.81,403RP-F 1x120830063520RP 11200 D
1 x 15021.526.31,702RP-F 1x150830063530RP 11500 D
1 x 18523.428.22,017RP-F 1x185830063540RP 11850 D
1 x 24026.631.62,588RP-F 1x240830063550RP 12400 D
1 x 30029.734.93,192RP-F 1x300830063560RP 13000 D
1 x 40034.039.44,143RP-F 1x400830063570RP 14000 D
1 x 50037.443.05,126RP-F 1x500830063580RP 15000 D
1 x 63042.748.76,747RP-F 1x630830063590RP 16300 D
2 x 412.015.8398RP-F 2x4830063600RP 0240 F
2 x 612.115.9424RP-F 2x6830063610RP 0260 F
2 x 1014.218.0569RP-F 2x10830063620RP 2100 F
2 x 1616.520.3756RP-F 2x16830063630RP 2160 F
2 x 2519.223.01021RP-F 2x25830063640RP 2250 F
2 x 3521.225.01,277RP-F 2x35830063650RP 2350 F
2 x 5024.628.41,688RP-F 2x50830063660RP 2500 F
2 x 7029.033.02,277RP-F 2x70830063670RP 2700 F
2 x 9533.437.62,926RP-F 2x95830063680RP 2950 F
2 x 12036.742.34,038RP-F 2x120830063690RP 21200 F
2 x 15041.447.44,935RP-F 2x150830063700RP 21500 F
2 x 18545.651.85,884RP-F 2x185830063710RP 21850 F
2 x 24051.958.37,481RP-F 2x240830063720RP 22400 F
2 x 30058.765.39,263RP-F 2x300830063730RP 23000 F
3 x 2.512.015.8389RP-F 3x2.5830063740RP 0325 F
3 x 412.015.8415RP-F 3x4830063750RP 0340 F
3 x 612.916.7488RP-F 3x6830063760RP 0360 F
3 x 1015.118.9669RP-F 3x10830063770RP 3100 F
3 x 1617.721.5906RP-F 3x16830063780RP 3160 F
3 x 2520.624.41,245RP-F 3x25830063790RP 3250 F
3 x 3522.826.61,585RP-F 3x35830063800RP 3350 F
3 x 5026.430.22,114RP-F 3x50830063810RP 3500 F
3 x 7031.535.52,903RP-F 3x70830063820RP 3700 F
3 x 9535.840.23,708RP-F 3x95830063830RP 3950 F
3 x 12039.545.35,073RP-F 3x120830063840RP 31200 F
3 x 15045.051.26,249RP-F 3x150830063850RP 31500 F
3 x 18549.055.47,407RP-F 3x185830063860RP 31850 F
3 x 24056.362.99,526RP-F 3x240830063870RP 32400 F
3 x 30063.170.111,758RP-F 3x300830063880RP 33000 F
4 x 2.512.015.8395RP-F 4x2.5830063990RP 0425 F
4 x 412.816.6464RP-F 4x4830064000RP 0440 F
4 x 614.318.1573RP-F 4x6830064010RP 0460 F
4 x 1016.720.5797RP-F 4x10830064020RP 4100 F
4 x 1619.623.41092RP-F 4x16830064030RP 4160 F
3 x 25 + 1 x 1622.025.81,411RP-F 3x25/16830064130RP 2516 F
3 x 35 + 1 x 1623.927.71,733RP-F 3x35/16830064140RP 3516 F
3 x 50 + 1 x 2527.731.52,340RP-F 3x50/25830064150RP 5025 F
3 x 70 + 1 x 3532.736.93,212RP-F 3x70/35830064160RP 7035 F
3 x 95 + 1 x 5037.342.94,545RP-F 3x95/50830064170RP 9550 F
3 x 120 + 1 x 7041.747.75,733RP-F 3x120/70830064180RP 12070 F
3 x 150 + 1 x 7046.452.66,811RP-F 3x150/70830064190RP 15070 F
3 x 185 + 1 x 9551.057.48,169RP-F 3x185/95830064200RP 18595 F
3 x 240 + 1 x 12058.265.010,502RP-F 3x240/120830064210RP 240120 F
3 x 300 + 1 x 15065.472.412,918RP-F 3x300/150830064220RP 300150 F