Clad series RM-H

Steel wire armour

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
Insulation (MICA+XLPE)

Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations. Control, signalling, measuring and protective equipment, electric controls of home installations. Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 62266 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: Mica tape + XLPE (Cross-Linked Polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Galvanized Steel Wire Armour

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Fire resistance standards: As per IEC 60331-21 (70000 BTU-750°C applied for 90 minutes)

  • Standard for Halogen absense and corrosive gases: IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable for AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Fire-resistant

Fire-resistant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
Multipolar alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Special design can be manufactured to comply with reinforced circuit integrity, complying with other standards such as IEC 60331-1/2, EN 50200 or BS 6387.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter below armour mm External diameter mm Weight kg/km Code
2 x 18.413.0312RM 0210 H
3 x 18.913.5336RM 0310 H
4 x 19.814.4376RM 0410 H
5 x 110.715.3421RM 0510 H
7 x 111.816.4459RM 0710 H
10 x 114.720.2736RM 1010 H
12 x 115.120.6780RM 1210 H
14 x 116.321.8854RM 1410 H
19 x 118.223.71000RM 1910 H
24 x 121.127.31348RM 2410 H
30 x 122.728.91507RM 3010 H
37 x 124.630.81699RM 3710 H
48 x 128.034.42031RM 4810 H
2 x 1.59.013.6342RM 0215 H
3 x 1.59.614.2373RM 0315 H
4 x 1.510.515.1416RM 0415 H
5 x 1.511.516.1470RM 0515 H
7 x 1.512.717.3515RM 0715 H
10 x 1.515.821.3819RM 1015 H
12 x 1.516.421.9881RM 1215 H
14 x 1.517.623.1963RM 1415 H
19 x 1.519.725.21139RM 1915 H
24 x 1.522.929.11533RM 2415 H
30 x 1.524.630.81723RM 3015 H
37 x 1.526.732.91956RM 3715 H
48 x 1.530.436.82351RM 4815 H
2 x 2.59.914.5393RM 0225 H
3 x 2.510.615.2434RM 0325 H
4 x 2.511.616.2489RM 0425 H
5 x 2.512.717.3557RM 0525 H
7 x 2.514.019.5761RM 0725 H
10 x 2.517.623.1978RM 1025 H
12 x 2.518.223.71058RM 1225 H
14 x 2.519.625.11166RM 1425 H
19 x 2.521.928.11567RM 1925 H
24 x 2.525.531.71869RM 2425 H
30 x 2.527.533.92144RM 3025 H
37 x 2.529.936.32460RM 3725 H
48 x 2.534.442.33434RM 4825 H
2 x 410.915.5458RM 0240 H
3 x 411.616.2511RM 0340 H
4 x 412.817.4586RM 0440 H
5 x 414.019.5817RM 0540 H
7 x 415.521.0913RM 0740 H
10 x 419.525.71342RM 1040 H
12 x 420.226.41458RM 1240 H
14 x 421.828.01613RM 1440 H
19 x 424.430.61944RM 1940 H
24 x 428.534.92355RM 2440 H
30 x 430.737.32725RM 3040 H
37 x 433.841.73608RM 3740 H