series RM

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
Insulation (MICA+XLPE)

Control, signalling, measuring and protective equipment, electric controls of home installations. Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in conduits, trays, cable ladders, in direct open air or indoors, buried in a trench or in ducts.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short-Circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 62266 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: Mica tape + XLPE (Cross-Linked Polyethylene)

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), flame retardant, sunlight, and oil resistant

  • Fire requirements: As per IEC 60332-3-24

  • Fire resistance standards: As per IEC 60331-21 (70000 BTU-750°C applied for 90 minutes)

  • Standard for Halogen absense and corrosive gases: IEC 60754-1/2

  • Smoke transparency requirements: IEC 61034-1/2

  • Toxicity standard: NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable for AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Fire-resistant

Fire-resistant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
Multipolar alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version. Special design can be manufactured to comply with reinforced circuit integrity, complying with other standards such as IEC 60331-1/2, EN 50200 or BS 6387.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.524.86--------------
1.513.316.96232016.111.511.510.48.1
2.57.9810.18312821.715.515.514.010.9
44.956.31433630.121.521.519.4--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x cross-section (mm²) External diameter mm Weight kg/km Code
2 x 19.4110RM 0210
3 x 19.9123RM 0310
4 x 110.8146RM 0410
5 x 111.7173RM 0510
7 x 112.8188RM 0710
10 x 115.7255RM 1010
12 x 116.1286RM 1210
14 x 117.3327RM 1410
19 x 119.2418RM 1910
24 x 122.1516RM 2410
30 x 123.7617RM 3010
37 x 125.6741RM 3710
48 x 129.0936RM 4810
2 x 1.510.0128RM 0215
3 x 1.510.6146RM 0315
4 x 1.511.5172RM 0415
5 x 1.512.5206RM 0515
7 x 1.513.7226RM 0715
10 x 1.516.8306RM 1015
12 x 1.517.4352RM 1215
14 x 1.518.6398RM 1415
19 x 1.520.7514RM 1915
24 x 1.523.9638RM 2415
30 x 1.525.6764RM 3015
37 x 1.527.7923RM 3715
48 x 1.531.41168RM 4815
2 x 2.510.9161RM 0225
3 x 2.511.6188RM 0325
4 x 2.512.6223RM 0425
5 x 2.513.7268RM 0525
7 x 2.515.0299RM 0725
10 x 2.518.6413RM 1025
12 x 2.519.2476RM 1225
14 x 2.520.6543RM 1425
19 x 2.522.9705RM 1925
24 x 2.526.5879RM 2425
30 x 2.528.51067RM 3025
37 x 2.530.91297RM 3725
48 x 2.535.21661RM 4825
2 x 411.9205RM 0240
3 x 412.6243RM 0340
4 x 413.8295RM 0440
5 x 415.0356RM 0540
7 x 416.5409RM 0740
10 x 420.5566RM 1040
12 x 421.2658RM 1240
14 x 422.8755RM 1440
19 x 425.4992RM 1940
24 x 429.51243RM 2440
30 x 431.91529RM 3040
37 x 434.61865RM 3740