Clad series OF-F

Steel tape armour

0.6/1kV
Flexible Cu 1 up to 4mm²
Up to 48 Conductors
PVC 70°C / PVC

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 75ºC (operating), 160°C (short circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: PVC

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: Flame retardant PVC

  • Fire requirements: As per IEC 60332-3-24

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Nominal cross-section sq mm² Electrical resistance at 20ºC in C.C Ohm/km Electrical resistance at 90ºC in C.A. Ohm/km Current-carrying capacity in free air. At 40°C as per IEC 364-5-523. Formations in perforated trays or ladder type. (Ampere)
2x 4x 7x 10x 19x 30x 48x
119.523.3--------------
1.513.315.918.115.312.79.19.18.16.3
2.57.989.55252117.512.512.511.38.8
44.955.92332923.116.516.514.9--

As from seven-conductors, we’ve additionally applied the correction factor for more than three conductors the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
10x112.316.1398OF 1010 F
12x113.317.1447OF 1210 F
14x114.218.0496OF 1410 F
19x116.220.0610OF 1910 F
24x117.921.7721OF 2410 F
30x119.823.6861OF 3010 F
37x121.825.61007OF 3710 F
48x124.528.31228OF 4810 F
5x1.510.314.1326OF 0515 F
7x1.511.215.0381OF 0715 F
10x1.513.317.1464OF 1015 F
12x1.514.318.1525OF 1215 F
14x1.515.319.1584OF 1415 F
19x1.517.521.3726OF 1915 F
24x1.519.423.2863OF 2415 F
30x1.521.525.31036OF 3015 F
37x1.523.627.41219OF 3715 F
48x1.527.031.01543OF 4815 F
3x2.510.013.8319OF 0325 F
4x2.510.514.3349OF 0425 F
5x2.511.515.3402OF 0525 F
7x2.512.516.3478OF 0725 F
10x2.514.818.6589OF 1025 F
12x2.516.119.9671OF 1225 F
14x2.517.221.0752OF 1425 F
19x2.519.723.5949OF 1925 F
24x2.521.825.61138OF 2425 F
30x2.524.228.01374OF 3025 F
37x2.526.730.71643OF 3725 F
48x2.530.534.72087OF 4825 F
2x410.914.7358OF 0240 F
3x411.615.4409OF 0340 F
4x412.716.5478OF 0440 F
5x414.017.8558OF 0540 F
7x415.319.1673OF 0740 F
10x418.222.0836OF 1040 F
12x419.823.6962OF 1240 F
14x421.225.01085OF 1440 F
19x424.328.11385OF 1940 F
24x427.531.71739OF 2440 F
30x430.534.72101OF 3040 F
37x433.639.42919OF 3740 F