Clad series NF-F

Steel tape armour

0.6/1kV
Flexible Cu 2.5 up to 630mm²
PVC 70°C / PVC
No PE conductor

Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 70ºC (operating), 160°C (short circuit)

  • Voltage rating: 600/1000 Volt A.C. – 1200 Volt A.C. (Max) – 1500 Volt D.C.

  • Construction requirements: IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: PVC

  • Bedding: PVC

  • Armour: Single Conductor cables with double aluminum tape.Multi conductor cables with double galvanized steel helical tape.The use of armoured single conductor cables in A.C. systems, requires the armour to be of a non magnetic material.

  • Sheath: Flame retardant PVC Fire

  • Fire requirements: As per IEC 60332-3-24

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
1 Conductor
2 Conductors
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances and reactances

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 70°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) Multiconductor (4) 4 Conductors (5)
119.523.330.1690.2120.1540.1110.119
1.513.315.910.1590.2020.1440.1040.112
2.57.989.550.1470.1910.330.0970.104
44.955.920.1420.1860.1280.0970.104
63.33.950.1330.1760.1180.0910.098
101.912.290.1220.1660.1080.0840.092
161.211.450.1160.1590.1010.080.088
250.780.930.1120.1560.0970.080.087
350.5540.6630.1080.1520.0930.0780.085
500.3860.4620.1050.1490.0910.0770.085
700.2720.3260.1010.1440.0860.0740.082
950.2060.2480.0990.1430.0850.0740.081
1200.1610.1940.0970.1410.0830.0720.08
1500.1290.1560.0960.140.0820.0720.08
1850.1060.1290.0960.140.0820.0720.08
2400.08010.09930.0950.1380.080.0720.079
3000.06410.0810.0940.1370.0790.0710.079
4000.04860.06370.0930.1360.078----
5000.03840.05270.0920.1350.077----
6300.02870.04290.090.1340.076----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) Calculation of Inductive reactance valid for two-conductor and three conductor cables. (5) Calculation of Inductive reactance valid for four-conductor cables.

Intensity of admissible currents

Nominal cross-section (mm²) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523.Single-conductors cable up to 16mm² in contact with each other, displayed in unperforated trays, remaining cross-sections, single-conductors displays and formations in cable ladder or perforated cable trays (Amper) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Amper)
1 Conductor (1) 1 Conductor (2) 1 Conductor (3) 2 Conductors Multiconductor (4) 1 Conductor (1) 1 Conductor (2) 2 Conductors Multiconductor (4)
1------------------
1.514.4----18.115.328292824
2.520----252137403732
427----332948514842
634----423560646252
1048----584980858470
1663----786710311010690
2594121919884133142137117
35118149113123105160171164140
50143181138149126186199197164
70186232179192162230246241200
95227282219233197276295291241
120265328255271228314335333276
150308377295314263352376373309
185352430338358301398426423351
240419508401425355464496493407
300485586464490410525562558460
400569704542----600642----
500652811619----695744----
630748941707----796852----

(1) Three single conductor cables displayed in flat, in contact with each other. (2) Three single conductor cables displayed in flat, separated by 1 diameter between each other. (3) Three single-conductor cables displayed in a trefoil in contact with each other. (4) The values of current-carrying capacity informed, correspond to three-conductor, four-conductor.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
1x1610.014.4354NF 1160 D
1x2510.615.0432NF 1250 D
1x3511.716.1540NF 1350 D
1x5013.518.1716NF 1500 D
1x7015.219.8923NF 1700 D
1x9517.021.61149NF 1950 D
1x12019.023.61451NF 11200 D
1x15021.526.31782NF 11500 D
1x18523.828.82158NF 11850 D
1x24026.631.82758NF 12400 D
1x30030.235.43375NF 13000 D
1x40033.939.54383NF 14000 D
1x50038.444.25625NF 15000 D
1x63041.547.56947NF 16300 D
2x410.914.7358NF 0240 F
2x612.015.8427NF 0260 F
2x1013.817.6563NF 2100 F
2x1615.919.7740NF 2160 F
2x2519.223.01039NF 2250 F
2x3521.525.31313NF 2350 F
2x5025.128.91750NF 2500 F
2x7028.432.42283NF 2700 F
2x9532.536.92942NF 2950 F
2x12036.442.24143NF 21200 F
2x15041.547.55109NF 21500 F
2x18546.352.56205NF 21850 F
2x24052.058.47816NF 22400 F
2x30059.566.39752NF 23000 F
3x2.510.013.8319NF 0325 F
3x411.615.4409NF 0340 F
3x612.716.5496NF 0360 F
3x1014.718.5668NF 3100 F
3x1617.020.8896NF 3160 F
3x2520.524.31275NF 3250 F
3x3523.026.81632NF 3350 F
3x5026.930.92209NF 3500 F
3x7030.935.12945NF 3700 F
3x9534.940.74148NF 3950 F
3x12039.145.15235NF 31200 F
3x15045.051.26506NF 31500 F
3x18549.856.27849NF 31850 F
3x24056.363.110050NF 32400 F
3x30064.071.012388NF 33000 F
4x2.510.514.3349NF 0425 F
4x412.716.5478NF 0440 F
4x614.017.8586NF 0460 F
4x1016.320.1800NF 4100 F
4x1618.822.61085NF 4160 F
4x2522.826.61559NF 4250 F
4x3525.629.42011NF 4350 F
4x5030.334.52785NF 4500 F
4x7034.339.94068NF 4700 F
4x9538.844.85136NF 4950 F
4x12044.050.26564NF 41200 F
4x15050.156.58087NF 41500 F
4x18555.862.49843NF 41850 F
4x24062.769.912584NF 42400 F
3x25+1x1621.825.61440NF 2516 F
3x35+1x1623.927.71777NF 3516 F
3x50+1x2528.132.12441NF 5025 F
3x70+1x3532.236.43260NF 7035 F
3x95+1x5036.742.54622NF 9550 F
3x120+1x7041.647.65938NF 12070 F
3x150+1x7046.352.77097NF 15070 F
3x185+1x9551.457.88603NF 18595 F
3x240+1x12058.164.911042NF 240120 F
3x300+1x15066.173.313646NF 300150 F
3x25+2x1623.427.21624NF 25216 F
3x35+2x1625.329.11951NF 35216 F
3x50+2x2530.434.62760NF 50225 F
3x70+2x3534.339.94027NF 70235 F
3x95+2x5039.245.25182NF 95250 F
3x120+2x7044.650.86693NF 120270 F
3x150+2x7048.755.17790NF 150270 F
3x185+2x9554.761.39592NF 185295 F
3x240+2x12061.468.412244NF 2402120 F