series MY

600 Volt
Cu 16 up to 10 AWG
Double insulation
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature ratings: 90°C (Operating) – 160°C (Short-Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: ASTM B174

  • Conductor: Annealed electrolytic copper; flexible stranding

  • Primary Insulation: Special PVC compound

  • Secondary Insulation: Polyamide (Nylon)

  • Sheath: Flame retardant PVC, sunlight and mineral oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code
2x167,379MY 0216
3x167,795MY 0316
4x168,4115MY 0416
5x169,1139MY 0516
7x169,8176MY 0716
10x1612,2227MY 1016
12x1612,6263MY 1216
14x1614,3326MY 1416
16x1615,0367MY 1616
19x1615,8424MY 1916
21x1616,5461MY 2116
24x1618,0523MY 2416
27x1618,4577MY 2716
30x1619,3634MY 3016
32x1620,0675MY 3216
37x1620,8768MY 3716
48x1624,51032MY 4816
2x148,1104MY 0214
3x148,6128MY 0314
4x149,3156MY 0414
5x1410,2191MY 0514
7x1411,0245MY 0714
10x1414,6344MY 1014
12x1415,0396MY 1214
14x1416,0452MY 1414
16x1416,9515MY 1614
19x1417,8596MY 1914
21x1418,6650MY 2114
24x1420,4740MY 2414
27x1421,8865MY 2714
30x1422,9953MY 3014
32x1423,71013MY 3214
37x1424,61150MY 3714
48x1425,51185MY 4814
2x128,9141MY 0212
3x129,4176MY 0312
4x1210,3219MY 0412
5x1211,2267MY 0512
7x1212,2350MY 0712
10x1216,1487MY 1012
12x1216,6568MY 1212
14x1217,8654MY 1412
16x1218,8745MY 1612
19x1219,8866MY 1912
21x1220,8952MY 2112
24x1223,81135MY 2412
27x1224,31256MY 2712
30x1225,51384MY 3012
32x1226,41472MY 3212
37x1227,41678MY 3712
48x1230,92141MY 4812
2x1010,7213MY 0210
3x1011,4271MY 0310
4x1012,5339MY 0410
5x1014,4439MY 0510
7x1015,7575MY 0710
10x1019,7756MY 1010
12x1020,3885MY 1210
14x1022,81070MY 1410
16x1024,11220MY 1610
19x1025,31413MY 1910
21x1026,61553MY 2110
24x1029,11764MY 2410
27x1029,81963MY 2710
30x1031,32166MY 3010
32x1032,52311MY 3210
37x1033,82643MY 3710
48x1038,23380MY 4810