Block series MX-W

Copper tape shield

600 Volt
Cu 16 up to 10 AWG
XLPE 90°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: ASTM B174

  • Conductor: Annealed electrolytic copper - Flexible stranding

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Shield: Helical copper tape with 100% coverage and adequate overlap

  • Sheath: Flame retardant PVC, sunlight, and mineral oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter below shield mm External diameter mm Weight kg/km Code
3x167.410.1156MX 0316 W
4x168.210.8180MX 0416 W
5x168.911.6207MX 0516 W
7x169.712.3238MX 0716 W
10x1611.614.9330MX 1016 W
12x1612.916.3389MX 1216 W
14x1613.817.2431MX 1416 W
19x1615.719.1535MX 1916 W
24x1617.420.8635MX 2416 W
30x1619.223.7818MX 3016 W
2x148.311.0183MX 0214 W
3x148.811.5208MX 0314 W
4x149.712.3235MX 0414 W
5x1410.714.0298MX 0514 W
7x1411.715.0357MX 0714 W
10x1414.317.7469MX 1014 W
12x1415.518.9534MX 1214 W
14x1416.619.9598MX 1414 W
19x1419.023.3805MX 1914 W
24x1421.626.01011MX 2414 W
30x1423.828.31197MX 3014 W
2x129.211.9226MX 0212 W
3x129.912.5255MX 0312 W
4x1210.914.2325MX 0412 W
5x1211.915.3381MX 0512 W
7x1213.516.8480MX 0712 W
10x1216.119.4610MX 1012 W
12x1217.420.7701MX 1212 W
19x1221.926.31116MX 1912 W
24x1224.228.71341MX 2412 W
30x1226.831.21602MX 3012 W
2x1010.513.8306MX 0210 W
3x1011.214.5360MX 0310 W
4x1012.315.7428MX 0410 W
5x1014.017.3524MX 0510 W
7x1015.318.7647MX 0710 W
10x1018.322.7879MX 1010 W
19x1024.929.41529MX 1910 W
24x1027.732.11853MX 2410 W
30x1030.735.12234MX 3010 W