Clad series MX-H

Steel wire amour

600 Volt
Cu 16 up to 10 AWG
XLPE 90°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: ASTM B174

  • Conductor: Annealed electrolytic copper - Flexible stranding

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Bedding: PVC

  • Armour: Galvanized steel wire armour

  • Sheath: Flame retardant PVC, sunlight, and mineral oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code
2x167.711.8258MX 0216 H
3x168.112.3283MX 0316 H
4x168.813.0314MX 0416 H
5x169.614.5376MX 0516 H
7x1610.416.2534MX 0716 H
10x1612.218.0631MX 1016 H
12x1613.919.7742MX 1216 H
14x1614.820.6805MX 1416 H
19x1616.723.21079MX 1916 H
24x1618.424.91228MX 2416 H
30x1620.226.71406MX 3016 H
2x149.013.1319MX 0214 H
3x149.514.4376MX 0314 H
4x1410.416.2531MX 0414 H
5x1411.317.1591MX 0514 H
7x1412.318.1669MX 0714 H
10x1415.421.9963MX 1014 H
12x1416.523.01061MX 1214 H
14x1417.624.11157MX 1414 H
19x1420.026.51378MX 1914 H
24x1423.129.61686MX 2414 H
30x1425.433.02202MX 3014 H
2x129.914.8397MX 0212 H
3x1210.516.3550MX 0312 H
4x1211.517.3617MX 0412 H
5x1212.618.4702MX 0512 H
7x1214.520.3853MX 0712 H
10x1217.123.61153MX 1012 H
12x1218.424.91294MX 1212 H
14x1219.626.11415MX 1412 H
19x1223.329.81791MX 1912 H
24x1225.733.32359MX 2412 H
30x1228.335.92704MX 3012 H
2x1011.217.0586MX 0210 H
3x1011.917.7661MX 0310 H
4x1013.018.8758MX 0410 H
5x1015.021.51028MX 0510 H
7x1016.422.91183MX 0710 H
10x1019.325.81437MX 1010 H
12x1021.828.31706MX 1210 H
14x1023.329.81871MX 1410 H
19x1026.434.02571MX 1910 H
24x1029.236.82966MX 2410 H
30x1032.239.83548MX 3010 H