Marlew

Clad series MX-F

600 Volt
Cu 16 up to 10 AWG
XLPE 90°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature ratings: 90°C (Operating) – 130°C (Overload) – 250°C (Short Circuit)

  • Voltage rating: 600 Volt A.C.

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: ASTM B174

  • Conductor: Annealed electrolytic copper - Flexible stranding

  • Insulation: XLPE (Cross-Linked Polyethylene)

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: Flame retardant PVC, sunlight, and mineral oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code Mat Number
10x1811,293215,3932346,413MX-F 10x18820033010
12x1812,143116,2431385,2MX-F 12x18820033020
14x1812,917,0423MX-F 14x18820033030
19x1815,422919,5229548,444MX-F 19x18820033040
24x1816,943821,0438635,874MX-F 24x18820033050
30x1818,618222,7182750,111MX-F 30x18820033060
7x1610.414.5336MX-F 7x16820033070
10x1612.216.3406MX-F 10x16820033080
12x1613.918.0488MX-F 12x16820033090
14x1614.818.9537MX-F 14x16820033100
19x1616.720.8654MX-F 19x16820033110
24x1618.422.5766MX-F 24x16820033120
30x1620.224.3907MX-F 30x16820033130
4x1410.414.5332MX-F 4x14820033140
5x1411.315.4379MX-F 5x14820033150
7x1412.316.4444MX-F 7x14820033160
10x1415.419.5578MX-F 10x14820033170
12x1416.520.6651MX-F 12x14820033180
14x1417.621.7722MX-F 14x14820033190
19x1420.024.1894MX-F 19x14820033200
24x1423.127.21125MX-F 24x14820033210
30x1425.429.51335MX-F 30x14820033220
3x1210.514.6352MX-F 3x12820033230
4x1211.515.6406MX-F 4x12820033240
5x1212.616.7469MX-F 5x12820033250
7x1214.518.6593MX-F 7x12820033260
10x1217.121.2731MX-F 10x12820033270
12x1218.422.5831MX-F 12x12820033280
14x1219.623.7929MX-F 14x12820033290
19x1223.327.41232MX-F 19x12820033300
24x1225.729.81468MX-F 24x12820033310
30x1228.332.41755MX-F 30x12820033320
2x1011.215.3383MX-F 2x10820033330
3x1011.916.0442MX-F 3x10820033340
4x1013.017.1518MX-F 4x10820033350
5x1015.019.1640MX-F 5x10820033360
7x1016.420.5772MX-F 7x10820033370
10x1019.323.4965MX-F 10x10820033380
12x1021.825.91169MX-F 12x10820033390
14x1023.327.41312MX-F 14x10820033400
19x1026.430.51660MX-F 19x10820033410
24x1029.233.31997MX-F 24x10820033420
30x1032.237.52770MX-F 30x10820033430