Block series MM-W

Copper tape shield

600 Volt
Cu 16 up to 10 AWG
PVC 75°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection.

Features

  • Temperature rating: 75ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Insulation: PVC

  • Shield: Annealed copper tape helical wrap with 100% coverage and overlap

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 75°C in AC. a 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.0114.411.5107.27.26.5
148.7710.6620161410109
125.526.72252017.512.512.511.3
103.484.23352824.517.517.515.8

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter below shield mm External diameter mm Weight kg/km Code
3x168.010.7176MM 0316 W
4x168.811.4204MM 0416 W
5x169.612.2229MM 0516 W
7x1610.513.8297MM 0716 W
10x1612.916.3392MM 1016 W
12x1613.917.3444MM 1216 W
14x1614.918.2495MM 1416 W
19x1617.020.3619MM 1916 W
24x1618.823.2790MM 2416 W
30x1621.325.8983MM 3016 W
2x149.812.4226MM 0214 W
3x1410.513.9281MM 0314 W
4x1411.614.9327MM 0414 W
5x1413.116.5399MM 0514 W
7x1414.417.7478MM 0714 W
10x1417.120.5597MM 1014 W
12x1418.522.9734MM 1214 W
14x1420.424.9870MM 1414 W
19x1423.327.81090MM 1914 W
24x1425.930.31303MM 2414 W
30x1428.633.11551MM 3014 W
2x1210.814.1296MM 0212 W
3x1211.514.9341MM 0312 W
4x1213.116.5417MM 0412 W
5x1214.417.7490MM 0512 W
7x1215.819.1595MM 0712 W
10x1218.823.2801MM 1012 W
12x1221.025.4968MM 1212 W
19x1225.730.11378MM 1912 W
24x1228.533.01660MM 2412 W
30x1231.636.01991MM 3012 W
2x1012.015.4367MM 0210 W
3x1013.216.6447MM 0310 W
4x1014.617.9531MM 0410 W
5x1016.019.4630MM 0510 W
7x1017.622.0826MM 0710 W
10x1021.626.11093MM 1010 W
19x1028.733.21825MM 1910 W
24x1032.036.42217MM 2410 W
30x1035.539.92679MM 3010 W