Clad series MM-H

Steel wire armour

600 Volt
Cu 16 up to 10 AWG
PVC 75°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 75ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Insulation: PVC

  • Bedding: PVC

  • Armour: Galvanized steel wire armour

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 75°C in AC. a 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.0114.411.5107.27.26.5
148.7710.6620161410109
125.526.72252017.512.512.511.3
103.484.23352824.517.517.515.8

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code
2x168.212.3282MM 0216 H
3x168.712.8310MM 0316 H
4x169.414.3372MM 0416 H
5x1610.316.1515MM 0516 H
7x1611.217.0580MM 0716 H
10x1613.919.7745MM 1016 H
12x1614.920.7818MM 1216 H
14x1615.922.41006MM 1416 H
19x1618.024.51195MM 1916 H
24x1619.826.31363MM 2416 H
30x1622.929.41671MM 3016 H
2x1410.516.3520MM 0214 H
3x1411.217.0573MM 0314 H
4x1412.218.0639MM 0414 H
5x1414.220.0761MM 0514 H
7x1415.421.9981MM 0714 H
10x1418.124.61173MM 1014 H
12x1419.626.11309MM 1214 H
14x1421.928.41515MM 1414 H
19x1424.831.31810MM 1914 H
24x1427.435.02369MM 2414 H
30x1430.237.82726MM 3014 H
2x1211.517.3586MM 0212 H
3x1212.218.0651MM 0312 H
4x1214.119.9779MM 0412 H
5x1215.421.9993MM 0512 H
7x1216.823.31147MM 0712 H
10x1219.826.31374MM 1012 H
12x1222.428.91628MM 1212 H
14x1223.930.41776MM 1412 H
19x1227.234.82443MM 1912 H
24x1230.037.62823MM 2412 H
30x1233.140.73329MM 3012 H
2x1012.718.5685MM 0210 H
3x1014.320.1808MM 0310 H
4x1015.622.11050MM 0410 H
5x1017.123.61181MM 0510 H
7x1018.625.11377MM 0710 H
10x1023.129.61768MM 1010 H
12x1024.931.41980MM 1210 H
14x1026.534.12465MM 1410 H
19x1030.237.82987MM 1910 H
24x1033.541.13542MM 2410 H
30x1037.046.34603MM 3010 H