Marlew

Clad series MM-F

600 Volt
Cu 16 up to 10 AWG
PVC 75°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 75ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Insulation: PVC

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 75°C in AC. a 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.0114.411.5107.27.26.5
148.7710.6620161410109
125.526.72252017.512.512.511.3
103.484.23352824.517.517.515.8

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code Mat Number
10x1812,216,3394MM-F 10x18820039010
12x1813,918,0473MM-F 12x18820039020
14x1814,818,9520MM-F 14x18820039030
19x1816,720,8631MM-F 19x18820039040
24x1818,422,5737MM 2418 FMM-F 24x18
30x1820,224,3871MM-F 30x18820039060
7x1611.215.3377MM-F 7x16820039070
10x1613.918.0492MM-F 10x16820039080
12x1614.919.0551MM-F 12x16820039090
14x1615.920.0608MM-F 14x16820039100
19x1618.022.1746MM-F 19x16820039110
24x1619.823.9878MM-F 24x16820039120
30x1622.927.01109MM-F 30x16820039130
4x1412.216.3413MM-F 4x14820039140
5x1414.218.3509MM-F 5x14820039150
7x1415.419.5597MM-F 7x14820039160
10x1418.122.2726MM-F 10x14820039170
12x1419.623.7822MM-F 12x14820039180
14x1421.926.0979MM-F 14x14820039190
19x1424.828.91213MM-F 19x14820039200
24x1427.431.51439MM-F 24x14820039210
30x1430.234.31713MM-F 30x14820039220
3x1212.216.3425MM-F 3x12820039230
4x1214.118.2527MM-F 4x12820039240
5x1215.419.5609MM-F 5x12820039250
7x1216.820.9723MM-F 7x12820039260
10x1219.823.9890MM-F 10x12820039270
12x1222.426.51080MM-F 12x12820039280
14x1223.928.01205MM-F 14x12820039290
19x1227.231.31512MM-F 19x12820039300
24x1230.034.11808MM-F 24x12820039310
30x1233.138.42541MM-F 30x12820039320
2x1012.716.8452MM-F 2x10820039330
3x1014.318.4557MM-F 3x10820039340
4x1015.619.7650MM-F 4x10820039350
5x1017.121.2759MM-F 5x10820039360
7x1018.622.7916MM-F 7x10820039370
10x1023.127.21208MM-F 10x10820039380
12x1024.929.01383MM-F 12x10820039390
14x1026.530.61554MM-F 14x10820039400
19x1030.235.52316MM-F 19x10820039410
24x1033.538.82761MM-F 24x10820039420
30x1037.043.03363MM-F 30x10820039430