Clad series MM-F

Steel tape armour

600 Volt
Cu 16 up to 10 AWG
PVC 75°C
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 75ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Insulation: PVC

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Direct burial

Direct burial

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 75°C in AC. a 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.0114.411.5107.27.26.5
148.7710.6620161410109
125.526.72252017.512.512.511.3
103.484.23352824.517.517.515.8

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code
7x1611.215.3377MM 0716 F
10x1613.918.0492MM 1016 F
12x1614.919.0551MM 1216 F
14x1615.920.0608MM 1416 F
19x1618.022.1746MM 1916 F
24x1619.823.9878MM 2416 F
30x1622.927.01109MM 3016 F
4x1412.216.3413MM 0414 F
5x1414.218.3509MM 0514 F
7x1415.419.5597MM 0714 F
10x1418.122.2726MM 1014 F
12x1419.623.7822MM 1214 F
14x1421.926.0979MM 1414 F
19x1424.828.91213MM 1914 F
24x1427.431.51439MM 2414 F
30x1430.234.31713MM 3014 F
3x1212.216.3425MM 0312 F
4x1214.118.2527MM 0412 F
5x1215.419.5609MM 0512 F
7x1216.820.9723MM 0712 F
10x1219.823.9890MM 1012 F
12x1222.426.51080MM 1212 F
14x1223.928.01205MM 1412 F
19x1227.231.31512MM 1912 F
24x1230.034.11808MM 2412 F
30x1233.138.42541MM 3012 F
2x1012.716.8452MM 0210 F
3x1014.318.4557MM 0310 F
4x1015.619.7650MM 0410 F
5x1017.121.2759MM 0510 F
7x1018.622.7916MM 0710 F
10x1023.127.21208MM 1010 F
12x1024.929.01383MM 1210 F
14x1026.530.61554MM 1410 F
19x1030.235.52316MM 1910 F
24x1033.538.82761MM 2410 F
30x1037.043.03363MM 3010 F