Steel wire armour
Fixed power distribution lines for the oil and gas insdustry (Midstream and Downstream) For Alternating Current (60Hz), for single-phase systems (110V), three-phase systems (190/210V) and systems with voltages up to 600V. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.
Standard | ||
---|---|---|
Sheath | Conductors | |
2 Conductors | ||
3 Conductors | ||
4 Conductors |
Conductor’s gauge (AWG) | Flexible class conductors. Electrical resistance at 20°C en D.C. (Ohm/km) | Flexible class conductors. Electrical resistance in C.C. at 90°C (Ohm/km) | Reactancia inductiva a 60Hz (Ohm/Km) | Current-carrying capacity (3) | |
---|---|---|---|---|---|
Multiconductor (1) | 4 Conductors (2) | ||||
14 | 8.77 | 11.19 | 0.098 | 0.105 | 25 |
12 | 5.52 | 7.04 | 0.092 | 0.099 | 30 |
10 | 3.48 | 4.43 | 0.086 | 0.093 | 40 |
8 | 2.19 | 2.79 | 0.090 | 0.097 | 55 |
6 | 1.40 | 1.78 | 0.084 | 0.091 | 75 |
4 | 0.880 | 1.12 | 0.080 | 0.087 | 95 |
2 | 0.556 | 0.709 | 0.077 | 0.084 | 130 |
1 | 0.439 | 0.560 | 0.078 | 0.085 | 145 |
1/0 | 0.351 | 0.448 | 0.076 | 0.083 | 170 |
2/0 | 0.279 | 0.358 | 0.074 | 0.081 | 195 |
3/0 | 0.221 | 0.284 | 0.072 | 0.080 | 225 |
4/0 | 0.175 | 0.226 | 0.071 | 0.079 | 260 |
250 | 0.150 | 0.194 | 0.072 | 0.079 | 290 |
300 | 0.125 | 0.163 | 0.071 | 0.078 | 320 |
350 | 0.107 | 0.140 | 0.070 | 0.078 | 350 |
400 | 0.0937 | 0.124 | 0.070 | 0.077 | 380 |
450 | 0.0833 | 0.111 | 0.069 | 0.076 | 405 |
500 | 0.0750 | 0.1011 | 0.068 | 0.076 | 430 |
(1) Calculation of Inductive reactance valid for two-conductor, three-conductor, and five-conductor cables. (2) Calculation of Inductive reactance valid for four-conductor cables. (3) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.
Cable formation N° Cond. x gauge AWG | Diameter under armour mm | External diameter mm | Weight kg/km | Code |
---|---|---|---|---|
2 x 14 | 10.8 | 15.9 | 511 | ML 0214 HRV |
2 x 12 | 11.8 | 16.8 | 575 | ML 0212 HRV |
2 x 10 | 13.0 | 18.0 | 671 | ML 0210 HRV |
2 x 8 | 16.2 | 22.7 | 1054 | ML 0208 HRV |
2 x 6 | 18.2 | 24.7 | 1269 | ML 0206 HRV |
2 x 4 | 20.5 | 27.0 | 1549 | ML 0204 HRV |
2 x 2 | 24.2 | 30.7 | 2035 | ML 0202 HRV |
2 x 1 | 27.0 | 34.6 | 2651 | ML 0201 HRV |
2 x 1/0 | 28.8 | 36.4 | 2993 | ML 21/0 HRV |
2 x 2/0 | 32.1 | 39.7 | 3640 | ML 22/0 HRV |
2 x 3/0 | 34.5 | 42.9 | 4221 | ML 23/0 HRV |
2 x 4/0 | 38.9 | 48.3 | 5489 | ML 24/0 HRV |
2 x 250 | 41.0 | 50.4 | 6156 | ML 2250 HRV |
2 x 300 | 46.1 | 55.5 | 7012 | ML 2300 HRV |
2 x 350 | 47.8 | 57.2 | 7743 | ML 2350 HRV |
2 x 400 | 50.4 | 59.8 | 8464 | ML 2400 HRV |
2 x 450 | 52.2 | 62.3 | 9055 | ML 2450 HRV |
2 x 500 | 55.1 | 65.3 | 9908 | ML 2500 HRV |
3 x 14 | 11.4 | 16.4 | 542 | ML 0314 HRV |
3 x 12 | 12.4 | 17.4 | 616 | ML 0312 HRV |
3 x 10 | 13.7 | 18.8 | 729 | ML 0310 HRV |
3 x 8 | 17.2 | 23.7 | 1162 | ML 0308 HRV |
3 x 6 | 19.4 | 25.9 | 1421 | ML 0306 HRV |
3 x 4 | 21.8 | 28.3 | 1779 | ML 0304 HRV |
3 x 2 | 25.7 | 33.3 | 2631 | ML 0302 HRV |
3 x 1 | 28.7 | 36.3 | 3072 | ML 0301 HRV |
3 x 1/0 | 31.5 | 39.1 | 3584 | ML 31/0 HRV |
3 x 2/0 | 34.2 | 42.6 | 4318 | ML 32/0 HRV |
3 x 3/0 | 36.8 | 46.2 | 5380 | ML 33/0 HRV |
3 x 4/0 | 41.6 | 50.9 | 6502 | ML 34/0 HRV |
3 x 250 | 43.9 | 53.2 | 7361 | ML 3250 HRV |
3 x 300 | 49.4 | 58.7 | 8371 | ML 3300 HRV |
3 x 350 | 51.2 | 60.6 | 9353 | ML 3350 HRV |
3 x 400 | 54.0 | 64.1 | 10248 | ML 3400 HRV |
3 x 450 | 55.9 | 66.1 | 10825 | ML 3450 HRV |
3 x 500 | 59.1 | 69.2 | 11957 | ML 3500 HRV |
4 x 14 | 12.3 | 17.3 | 594 | ML 0414 HRV |
4 x 12 | 13.4 | 18.4 | 690 | ML 0412 HRV |
4 x 10 | 14.9 | 19.9 | 823 | ML 0410 HRV |
4 x 8 | 18.7 | 25.2 | 1296 | ML 0408 HRV |
4 x 6 | 21.2 | 27.7 | 1640 | ML 0406 HRV |
4 x 4 | 24.7 | 31.2 | 2136 | ML 0404 HRV |
4 x 2 | 28.2 | 35.8 | 3047 | ML 0402 HRV |
4 x 1 | 32.4 | 40.0 | 3751 | ML 0401 HRV |
4 x 1/0 | 34.6 | 43.0 | 4346 | ML 41/0 HRV |
4 x 2/0 | 37.6 | 47.0 | 5513 | ML 42/0 HRV |
4 x 3/0 | 40.6 | 50.0 | 6355 | ML 43/0 HRV |
4 x 4/0 | 45.9 | 55.3 | 7755 | ML 44/0 HRV |
4 x 250 | 48.5 | 57.8 | 8824 | ML 4250 HRV |
4 x 300 | 54.6 | 64.8 | 9990 | ML 4300 HRV |
4 x 350 | 56.7 | 66.8 | 11163 | ML 4350 HRV |
4 x 400 | 59.8 | 70.0 | 12158 | ML 4400 HRV |