Clad series ME-F

Steel tape armour

600 Volt
Cu 16 up to 10 AWG
XLPE 90°C / LSZH
ICEA S 73-532

Control, signalling, measuring and protective equipment, electric controls of home installations. Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in conduits, trays, cable ladders, in direct open air or indoors, buried in a trench or in ducts. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating),130ºC (overload) and 250ºC (short circuit)

  • Voltage rating: 600 AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Armour: Double galvanized steel helical tape

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant), fire-retardant sunlight and oils resistant

  • Fire requirements: As per ICEA T 30-520

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Water immersion

Water immersion

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 75°C in AC. a 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG Diameter under armour mm External diameter mm Weight kg/km Code
10x1811.315.4355ME 1018 F
12x1812.116.2394ME 1218 F
14x1812.917.0432ME 1418 F
19x1815.419.5561ME 1918 F
30x1818.622.7765ME 3018 F
7x1610.414.5344ME 0716 F
10x1612.216.3415ME 1016 F
12x1613.918.0499ME 1216 F
14x1614.818.9549ME 1416 F
19x1616.720.8667ME 1916 F
30x1620.224.3924ME 3016 F
4x1410.414.5341ME 0414 F
5x1411.315.4388ME 0514 F
7x1412.316.4454ME 0714 F
10x1415.419.5591ME 1014 F
12x1416.520.6665ME 1214 F
14x1417.621.7736ME 1414 F
19x1420.024.1910ME 1914 F
30x1425.429.51358ME 3014 F
3x1210.514.6361ME 0312 F
4x1211.515.6416ME 0412 F
5x1212.616.7480ME 0512 F
7x1214.518.6607ME 0712 F
10x1217.121.2745ME 1012 F
12x1218.422.5846ME 1212 F
14x1219.623.7945ME 1412 F
19x1223.327.41253ME 1912 F
24x1225.729.81492ME 2412 F
30x1228.332.41781ME 3012 F
2x1011.215.3394ME 0210 F
3x1011.916.0453ME 0310 F
4x1013.017.1530ME 0410 F
5x1015.019.1654ME 0510 F
7x1016.420.5787ME 0710 F
10x1019.323.4981ME 1010 F
14x1023.327.41333ME 1410 F
19x1026.430.51684ME 1910 F
24x1029.233.32024ME 2410 F
30x1032.237.52800ME 3010 F