series MA

Aluminium/polyester tape helical wrap

600 Volt
Cu 16 up to 10 AWG
Double insulation
ICEA S 73-532

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection.

Features

  • Temperature rating: 90ºC (operating), 160°C (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per ICEA S 73-532

  • Conductor requirements: As per ASTM B174

  • Conductor: Annealed electrolytic copper; flexible

  • Primary insulation: Special PVC

  • Secondary insulation: Nylon

  • Shield: Aluminium/polyester tape helical wrap with 100% coverage and overlap. Drain wire in contact with the aluminium side of the tape. Drain consists of a 7-wire tinned copper thread

  • Sheath: PVC fire-retardant; sunlight and mineral-oil resistant.

  • Fire requirements: As per ICEA T 30-520

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
MulticonductorMethod 3 Table E-2

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C. (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x
1613.9917.841814.412.6998.1
148.7711.18252017.512.512.511.3
125.527.04302421151513.5
103.484.44403228202018

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code
2x167,473MA 0216
3x167,892MA 0316
4x168,6115MA 0416
5x169,3139MA 0516
7x1610173MA 0716
10x1612,3238MA 1016
12x1612,7274MA 1216
14x1614,4338MA 1416
16x1615,1379MA 1616
19x1615,8432MA 1916
21x1616,6474MA 2116
24x1618,1535MA 2416
27x1618,5590MA 2716
30x1619,4648MA 3016
32x1620,1689MA 3216
37x1621,9829MA 3716
48x1624,51041MA 4816
2x148,396MA 0214
3x148,8124MA 0314
4x149,6154MA 0414
5x1410,4188MA 0514
7x1411,2238MA 0714
10x1414,6353MA 1014
12x1415,1408MA 1214
14x1416,1464MA 1414
16x1417527MA 1614
19x1417,8605MA 1914
21x1418,7663MA 2114
24x1420,5754MA 2414
27x1421,9879MA 2714
30x1423968MA 3014
32x1423,81028MA 3214
37x1424,71165MA 3714
48x1427,71471MA 4814
2x129,1127MA 0212
3x129,7170MA 0312
4x1210,5212MA 0412
5x1211,4260MA 0512
7x1212,4338MA 0712
10x1216,2499MA 1012
12x1216,7580MA 1212
14x1217,9667MA 1412
16x1218,8753MA 1612
19x1219,8875MA 1912
21x1221,81008MA 2112
24x1223,81144MA 2412
27x1224,31265MA 2712
30x1225,51393MA 3012
32x1226,51488MA 3212
37x1227,51694MA 3712
48x12312158MA 4812
2x1010,9185MA 0210
3x1011,6252MA 0310
4x1012,7441MA 0410
5x1013,9549MA 0510
7x1015,2710MA 0710
10x10191045MA 1010
12x1019,61197MA 1210
14x1021,11392MA 1410
16x1022,31585MA 1610
19x1023,61837MA 1910
21x1024,92035MA 2110
24x1027,42371MA 2410
27x1028,12604MA 2710
30x1029,62891MA 3010
32x1030,83107MA 3210
37x1032,13518MA 3710
48x1036,54554MA 4810