Clad series FF-F

Steel tape armour

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / PVC
Includes PE conductor

Fixed power distribution networks in factories, warehouses, machine rooms, power distribution stations. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 70ºC (operating), 160°C (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Cross-linked polyethylene)

  • Bedding: PVC

  • Armour: Double galvanized steel helical tape

  • Sheath: PVC fire-retardant

  • Fire requirements: As per IEC 60332-1

  • Outdoors requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Tray cable

Tray cable

Identification

Standard
Sheath Conductors
3 Conductors
4 Conductors
5 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Electrical resistance in D.C. at 20°C (Ohm/km) Electrical resistance in C.C. at 90°C (Ohm/km) Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Formations in cable ladder or perforated cable trays (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
Multiconductor (1) 4 Conductors (2) 2 Conductors (3) Multiconductor (4) 2 Conductors (3) Multiconductor (4)
119.524.860.1070.114--------
1.513.316.960.10.10723203228
2.57.9810.180.0930.131284437
44.956.310.0880.09543365748
63.34.210.0830.0954477261
101.912.440.0780.08574659783
161.211.540.0750.08210086129107
250.780.990.0750.083128109166141
350.5540.7070.0730.081160137200168
500.3860.4930.0730.08195166238199
700.2720.3480.0710.079250213292243
950.2060.2640.070.077304257351293
1200.1610.2070.070.077354299399333
1500.1290.1670.070.077409345448373
1850.1060.1380.070.077468394508425
2400.08010.1060.0690.077554465592493
3000.06410.0860.0690.076640537669559

(1) Calculation of Inductive reactance valid for three-conductor and five-conductor cables. (2) Calculation of Inductive reactance valid for four-conductor cables. (3)  The values of current-carrying capacity informed, correspond to three conductor cable (two-conductor + protection conductor) (4) The values of current-carrying capacity informed, correspond to four-conductor, five-conductor.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x cross-section (mm²) Diameter under armour mm External diameter mm Weight kg/km Code
3x2.510.013.8310FF 0325 F
3x410.314.1346FF 0340 F
3x611.515.3428FF 0360 F
3x1013.417.2589FF 3100 F
3x1615.719.5807FF 3160 F
3x2519.223.01162FF 3250 F
3x3521.725.51506FF 3350 F
3x5025.229.02013FF 3500 F
3x7029.633.62751FF 3700 F
3x9532.737.13454FF 3950 F
3x12037.443.24901FF 31200 F
3x15043.349.56128FF 31500 F
3x18548.154.57415FF 31850 F
3x24054.260.89451FF 32400 F
3x30061.468.411655FF 33000 F
4x2.510.013.8318FF 0425 F
4x411.315.1402FF 0440 F
4x612.616.4503FF 0460 F
4x1014.818.6705FF 4100 F
4x1617.321.1977FF 4160 F
4x2521.325.11421FF 4250 F
4x3524.127.91856FF 4350 F
4x5028.032.02511FF 4500 F
4x7032.937.13439FF 4700 F
4x9536.442.24743FF 4950 F
4x12042.048.26172FF 41200 F
4x15048.254.67617FF 41500 F
4x18553.560.19235FF 41850 F
4x24060.367.311840FF 42400 F
3x25+1x1620.324.11309FF 2516 F
3x35+1x1622.426.21633FF 3516 F
3x50+1x2526.330.12225FF 5025 F
3x70+1x3530.835.03053FF 7035 F
3x95+1x5034.440.04263FF 9550 F
3x120+1x7039.445.45535FF 12070 F
3x150+1x7044.450.66662FF 15070 F
3x185+1x9549.355.78101FF 18595 F
3x240+1x12055.862.610410FF 240120 F
3x300+1x15063.570.512812FF 300150 F
3x25+2x1621.825.61474FF 25216 F
3x35+2x1623.627.41788FF 35216 F
3x50+2x2528.032.02483FF 50225 F
3x70+2x3532.736.93385FF 70235 F
3x95+2x5036.842.64778FF 95250 F
3x120+2x7042.648.86296FF 120270 F
3x150+2x7046.853.27335FF 150270 F
3x185+2x9551.958.58953FF 185295 F
3x240+2x12058.965.911540FF 2402120 F
3x300+2x15067.174.514244FF 3002150 F
4x25+1x1622.726.51581FF 42516 F
4x35+1x1625.128.92002FF 43516 F
4x50+1x2529.934.12796FF 45025 F
4x70+1x3534.540.14166FF 47035 F
4x95+1x5038.544.55245FF 49550 F
4x120+1x7044.650.86844FF 412070 F
4x150+1x7050.156.58230FF 415070 F
4x185+1x9556.062.810110FF 418595 F
4x240+1x12062.970.112920FF 4240120 F