Block series CY-M

Shield with annealed electrolytic copper wires braid

600 Volt
Cu 14 up to 10 AWG
Double insulation
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 160ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper; class B

  • Primary insulation: Special PVC compound

  • Secondary insulation: THHN (Nylon)

  • Shield: Annealed Electrolytic Copper wires braid with 80% overlap

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per UL 1685

  • Test requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art 336 - Art 501 classified areas Cl 1 Div 2 and Cl 2 Div 2

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Wet locations

Wet locations

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, the shield can also be made with tinned annealed copper wires to increase its protection in given installations with high corrosion and/or ambient humidity.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under shield mm External diameter mm Weight kg/km Code
2 x 145.98.8113CY 0214 M
3 x 146.39.2141CY 0314 M
4 x 147.19.9172CY 0414 M
5 x 147.910.7203CY 0514 M
7 x 148.711.6260CY 0714 M
10 x 1411.314.9381CY 1014 M
12 x 1411.715.3434CY 1214 M
14 x 1412.716.3494CY 1414 M
19 x 1414.418.2655CY 1914 M
24 x 1416.920.7808CY 2414 M
30 x 1418.423.21024CY 3014 M
37 x 1420.025.11250CY 3714 M
48 x 1423.028.01567CY 4814 M
2 x 126.89.7146CY 0212 M
3 x 127.410.2188CY 0312 M
4 x 128.211.1232CY 0412 M
5 x 129.212.0277CY 0512 M
7 x 1210.113.0360CY 0712 M
10 x 1213.116.8526CY 1012 M
12 x 1213.617.3605CY 1212 M
14 x 1214.818.6712CY 1412 M
19 x 1216.820.6922CY 1912 M
24 x 1219.724.81226CY 2412 M
30 x 1221.426.51473CY 3012 M
37 x 1223.428.41769CY 3712 M
48 x 1226.931.92232CY 4812 M
2 x 108.611.5206CY 0210 M
3 x 109.212.1270CY 0310 M
4 x 1010.314.0361CY 0410 M
5 x 1011.515.1432CY 0510 M
7 x 1012.816.4565CY 0710 M
10 x 1016.520.4803CY 1010 M
12 x 1017.122.0978CY 1210 M
14 x 1018.623.51116CY 1410 M
19 x 1021.126.21480CY 1910 M
24 x 1024.929.91832CY 2410 M
30 x 1027.032.12219CY 3010 M
37 x 1029.534.52679CY 3710 M