Block series CY-BW10

Shield of wires + helical spiral copper wrap

600 Volt
Cu 14 up to 10 AWG
Double insulation
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 160ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper; class B

  • Primary insulation: Special PVC compound

  • Secondary insulation: THHN (Nylon)

  • Shield: Helically applied annealed electrolytic copper wires + annealed copper tape helical wrap, with 100% coverage. With this double shielding, a minimum section of 10mm² is guaranteed

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per UL 1685

  • Test requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art 336 - Art 501 classified areas Cl 1 Div 2 and Cl 2 Div 2

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Wet locations

Wet locations

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, for other specific requirements at the request of the user, higher shielding section values can be guaranteed by varying the number of copper wires that make up the screen.

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter below shield mm External diameter mm Weight kg/km Code
2 x 147.310.6233CY 0214 BW10
3 x 147.711.1259CY 0314 BW10
4 x 148.411.8291CY 0414 BW10
5 x 149.212.6325CY 0514 BW10
7 x 1410.114.2401CY 0714 BW10
10 x 1412.816.9496CY 1014 BW10
12 x 1413.217.3544CY 1214 BW10
14 x 1414.218.3606CY 1414 BW10
19 x 1415.920752CY 1914 BW10
24 x 1418.423.6954CY 2414 BW10
30 x 1420.625.71156CY 3014 BW10
37 x 1422.227.41362CY 3714 BW10
48 x 1425.230.41678CY 4814 BW10
2 x 128.211.6276CY 0212 BW10
3 x 128.712.1313CY 0312 BW10
4 x 129.613360CY 0412 BW10
5 x 1210.514.7425CY 0512 BW10
7 x 1211.515.7513CY 0712 BW10
10 x 1214.718.8636CY 1012 BW10
12 x 1215.219.3716CY 1212 BW10
14 x 1216.320.5805CY 1412 BW10
19 x 1218.323.51067CY 1912 BW10
24 x 122227.11332CY 2412 BW10
30 x 1223.628.81584CY 3012 BW10
37 x 1225.630.81874CY 3712 BW10
48 x 1229.134.22338CY 4812 BW10
2 x 101014.1370CY 0210 BW10
3 x 1010.614.8430CY 0310 BW10
4 x 1011.715.8502CY 0410 BW10
5 x 1012.917576CY 0510 BW10
7 x 1014.118.3706CY 0710 BW10
10 x 101823.2945CY 1010 BW10
12 x 1018.723.81075CY 1210 BW10
14 x 1020.9261250CY 1410 BW10
19 x 1023.328.51586CY 1910 BW10
24 x 1027.132.21941CY 2410 BW10
30 x 1029.234.42326CY 3010 BW10
37 x 1031.736.82792CY 3710 BW10
48 x 1036.141.23522CY 4810 BW10