Marlew

Block series CY-A

600 Volt
Cu 14 up to 10 AWG
Double insulation
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It provides additional electromagnetic protection. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 160ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper; class B

  • Primary insulation: Special PVC compound

  • Secondary insulation: THHN (Nylon)

  • Shield: Helically applied Aluminium – Polyester tape plus tinned copper drain wire

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per UL 1685

  • Test requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art 336 - Art 501 classified areas Cl 1 Div 2 and Cl 2 Div 2

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Wet locations

Wet locations

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG Diameter under shield mm External diameter mm Weight kg/km Code Mat Number Previous Code
2 x 145.78.296CY-A 2x14-CY 0214 A
3 x 146.18.6122CY-A 3x14-CY 0314 A
4 x 146.99.4151CY-A 4x14-CY 0414 A
5 x 147.610.2180CY-A 5x14-CY 0514 A
7 x 148.511.0234CY-A 7x14-CY 0714 A
10 x 1411.014.3345CY-A 10x14-CY 1014 A
12 x 1411.514.7397CY-A 12x14-CY 1214 A
14 x 1412.515.8453CY-A 14x14-CY 1414 A
19 x 1414.117.4589CY-A 19x14-CY 1914 A
24 x 1416.720.0730CY-A 24x14-CY 2414 A
30 x 1418.122.4938CY-A 30x14-CY 3014 A
37 x 1419.824.11129CY-A 37x14-CY 3714 A
48 x 1422.827.11428CY-A 48x14-CY 4814 A
2 x 126.69.1126CY-A 2x12-CY 0212 A
3 x 127.19.7166CY-A 3x12-CY 0312 A
4 x 128.010.5207CY-A 4x12-CY 0412 A
5 x 128.911.5249CY-A 5x12-CY 0512 A
7 x 129.912.5329CY-A 7x12-CY 0712 A
10 x 1212.916.2484CY-A 10x12-CY 1012 A
12 x 1213.416.7561CY-A 12x12-CY 1212 A
14 x 1214.617.9643CY-A 14x12-CY 1412 A
19 x 1216.519.8845CY-A 19x12-CY 1912 A
24 x 1219.523.81106CY-A 24x12-CY 2412 A
30 x 1221.225.51344CY-A 30x12-CY 3012 A
37 x 1223.227.51629CY-A 37x12-CY 3712 A
48 x 1226.630.92071CY-A 48x12-CY 4812 A
2 x 108.410.9180CY-A 2x10-CY 0210 A
3 x 109.011.5242CY-A 3x10-CY 0310 A
4 x 1010.112.6306CY-A 4x10-CY 0410 A
5 x 1011.314.6396CY-A 5x10-CY 0510 A
7 x 1012.515.8523CY-A 7x10-CY 0710 A
10 x 1016.319.6727CY-A 10x10-CY 1010 A
12 x 1016.920.2849CY-A 12x10-CY 1210 A
14 x 1018.422.71029CY-A 14x10-CY 1410 A
19 x 1020.925.21351CY-A 19x10-CY 1910 A
24 x 1024.729.01683CY-A 24x10-CY 2410 A
30 x 1026.831.12057CY-A 30x10-CY 3010 A
37 x 1029.233.62504CY-A 37x10-CY 3710 A
48 x 1033.637.93197CY-A 48x10-CY 4810 A