series CY

600 Volt
Cu 14 up to 10 AWG
Double insulation
UL 1277

Control, signalling, measuring and protective equipment; electric controls of industrial installations. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. Manufactured in compliance with the National Electrical Code ANSI/NFPA 70 of the US and the National Electrical Code NOM-001 SEDE, Mexico.

Features

  • Temperature rating: 90ºC (operating), 160ºC (short circuit)

  • Voltage rating: 600V AC

  • Construction requirements: As per UL 1277

  • Conductor requirements: As per ASTM B8

  • Conductor: Annealed electrolytic copper; class B

  • Primary insulation: Special PVC compound

  • Secondary insulation: THHN (Nylon)

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per UL 1685

  • Outdoors requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art 336 - Art 501 classified areas Cl 1 Div 2 and Cl 2 Div 2

Fire-retardant

Fire-retardant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Industrial applications

Industrial applications

Tray cable

Tray cable

Wet locations

Wet locations

Identification

Standard
Sheath Conductors
Multiconductor alphanumeric identification

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

ELECTRICAL CHARACTERISTICS

Resistances and intensity of admissible currents

Gauge AWG Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C in C.A. at 60Hz (Ohm/km) Current-carrying capacity (1)
2x 4x 7x 10x 19x 30x 48x
148.7911.21252017.512.512.511.38.8
125.547.06302421151513.510.5
103.484.4440322820201814

(1) Current-carrying capacity of cables with up to three conductors, installed in ducts or directly buried, up to an ambient temperature of 30ºC, according to chart 310.15 (B)(16) of the NFPA 70. As from four-conductors, we’ve additionally applied the correction factor for more than three conductors from the chart 310.15 (B)(3)(a) of the NFPA70.

DIMENSIONS & WEIGHT

Cable Formation N° Cond. x gauge AWG External diameter mm Weight kg/km Code
2 x 147.9101CY 0214
3 x 148.4124CY 0314
4 x 149.1152CY 0414
5 x 149.9180CY 0514
7 x 1410.8235CY 0714
10 x 1414.2332CY 1014
12 x 1414.6383CY 1214
14 x 1415.7439CY 1414
19 x 1417.3575CY 1914
24 x 1419.9714CY 2414
30 x 1422.3921CY 3014
37 x 1424.01112CY 3714
48 x 1427.01410CY 4814
2 x 128.9138CY 0212
3 x 129.4172CY 0312
4 x 1210.3213CY 0412
5 x 1211.2254CY 0512
7 x 1212.2335CY 0712
10 x 1216.1470CY 1012
12 x 1216.6547CY 1212
14 x 1217.8629CY 1412
19 x 1219.7829CY 1912
24 x 1223.71089CY 2412
30 x 1225.41326CY 3012
37 x 1227.41610CY 3712
48 x 1230.82051CY 4812
2 x 1010.6205CY 0210
3 x 1011.3259CY 0310
4 x 1012.4322CY 0410
5 x 1014.3411CY 0510
7 x 1015.6540CY 0710
10 x 1019.5412CY 1010
12 x 1020.1833CY 1210
14 x 1022.61012CY 1410
19 x 1025.11333CY 1910
24 x 1028.91664CY 2410
30 x 1031.02037CY 3010
37 x 1033.52482CY 3710
48 x 1037.83174CY 4810