series CD

Bare conductor
Class 2 and Class 5
1 up to 630 mm²
IRAM NM 280

Suitable for earthing networks, as neutral or return conductor in certain electrical systems.

Features

  • Temperature rating: 90ºC

  • Voltage rating: Not apply

  • Construction requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper class 2 or class 5

Grounded conductor

Grounded conductor

Flexible stranded conductors

Flexible stranded conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

These ropes can be provided with tinned wires as anticorrosive protection in installations where there is a high aggressiveness of the environment or terrain.

CLASS 2

Nominal cross-section (mm²) Stranding (*) Minimum amount of wires External diameter mm Weight kg/km Electrical resistance ohm/km Bend radius mm Pulling tension daN/mm² Code
0.5-0.95---CD 0105
0.7-1.17---CD 0107
171.3918,1195CD 0110
1.571.51312,1247,5CD 0115
2.572.0227,413012,5CD 0125
472.5354,613820CD 0140
673.1533,084730CD 0160
1074.0881,836050CD 1100
1675.01391,157580CD 1160
2576.32200,72794125CD 1250
3577.43050,524111175CD 1350
50198.84160,387130250CD 1500
701910.56000,268157350CD 1700
951912.88390,193192475CD 1950
1203714.610530,153220600CD 11200
1503715.912910,124239750CD 11500
1853717.516150,0991262925CD 11850
2406119.821210,07543001200CD 12400
3006122.226620,06013331500CD 13000
4006126.233780,0473932000CD 14000
5006128.443330,03664262500CD 15000
6309133.556190,02834913150CD 16300

(*) For class 2, there is a standardized minimum amount of wires to form the strand.

CLASS 5

Nominal cross-section (mm²) Maximum wire diameter External diameter mm Weight kg/km Electrical resistance ohm/km Bend radius mm Pulling tension daN/mm² Code
0.5-0.94---CDff 0105
0.75-1.16---CDff 0107
10,211.2819,5195CDff 0110
1.50,261.51113,3237,5CDff 0115
2.50,261.9197,983012,5CDff 0125
40,312.4314,953320CDff 0140
60,313.0473,34630CDff 0160
100,413.9801,916250CDff 1100
160,414.91291,217680CDff 1160
250,416.22020,7894125CDff 1250
350,417.32850,554109175CDff 1350
500,418.74050,386130250CDff 1500
700,5110.45720,272160350CDff 1700
950,5111.87430,206190475CDff 1950
1200,5113.89840,161211600CDff 11200
1500,5115.912230,129244750CDff 11500
1850,5117.815110,106265925CDff 11850
2400,5120.219930,08013101200CDff 12400
3000,5123.424810,06413521500CDff 13000
4000,5126.332920,04864062000CDff 14000
5000,6130.443300,03844512500CDff 15000
6300,6133.555240,02875203150CDff 16300

(*) For class 5, there is a standardized minimum amount of wires to form the strand.