Clad series BX-H

Steel wire armour

0.6/1kV
Flexible Cu 1.5 up to 300mm²
XLPE 90°C / PVC
PE conductor

Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried. It has additional mechanical protection.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: PVC

  • Shield: Copper tape (if necessary) with adequate overlap and 100% coverage. See the table for shield cross-section values

  • Inner sheath: PVC, fire-retardant

  • Armour: Galvanized steel wire armour

  • Sheath: PVC, fire-retardant

  • Fire requirements: As per IEC 60332-1

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Fire-retardant

Fire-retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq (mm²) Nominal cross-section Concentric conductorsq mm Electrical resistance at 20°C in C.C.  Ohm/km Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km Electrical resistance at 90°C en C.C. Ohm/km Electrical resistance at 90°C en C.C. Concentric conductor Ohm/km Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1619.53.324.864.210.107----
1.5613.33.316.964.210.1002028
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.2100.7071.540.073137168
50250.3860.7800.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.070257293
120700.1610.2720.2070.3480.070299333
150700.1290.2720.1670.3480.070345373
185950.1060.2060.1380.2640.070394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.08600.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Diameter under shield mm Diameter below armour mm External diameter mm Weight kg/km Code
3 x 1912.717.3546BX 0310 H
3 x 1.5912.717.3552BX 0315 H
3 x 2.59.313.118.6722BX 0325 H
3 x 410.314.119.6809BX 0340 H
3 x 611.715.521928BX 0360 H
3 x 101417.723.21197BX 3100 H
3 x 161619.8261664BX 3160 H
3 x 2519.523.329.52,128BX 3250 H
3 x 3521.725.531.92,541BX 3350 H
3 x 5025.128.936.83,596BX 3500 H
3 x 7030.334.142.24,707BX 3700 H
3 x 9534.639.447.75,861BX 3950 H
3 x 1203843.152.87,595BX 31200 H
3 x 15044.149.3599,063BX 31500 H
3 x 18547.953.463.910,872BX 31850 H
3 x 24055.360.971.813,617BX 32400 H