Marlew

series BX

0.6/1kV
Flexible Cu 1 up to 300mm²
XLPE 90°C / PVC
IRAM 2178-1

Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: Extruded PVC bedding

  • Shield: Consisting of copper wires plus a copper tape with 100% coverage. The screen cross-section is indicated in the electrical characteristics table.

  • Sheath: PVC, fire-retardant

  • Flame propagation standard: As per IEC 60332-1

  • Fire spread prevention standard: As per IEC 60332-3-24

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Concentric conductor nominal cross-section (mm²) DC electrical resistance at 20 °C (Ohm/km) Concentric conductor DC electrical resistance at 20 °C (Ohm/km) DC electrical resistance at 90 °C (Ohm/km) Concentric conductor DC electrical resistance at 90 °C (Ohm/km) Inductive reactance at 50 Hz (Ohm/km) Current rating, cables in air. At 40 °C according to IEC 364-5-523. Laid on perforated or ladder-type trays. (A) Current rating, cables directly buried. At 25 °C ground temperature and soil thermal resistivity of 1 K·m/W, according to IEC 364-5-523. (A)
1619.53.324.864.210.107----
1.5613.33.316.964.210.1002028
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.2100.7071.540.073137168
50250.3860.7800.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.070257293
120700.1610.2720.2070.3480.070299333
150700.1290.2720.1670.3480.070345373
185950.1060.2060.1380.2640.070394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.08600.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Shield diameter (mm) External diameter mm Weight kg/km Code Mat Number
3 x 19.212.3222BX 3X1+B6830044010
3 x 1.59.512.6238BX 3X1.5+B6830044020
3 x 2.510.513.6285BX 3X2.5+B6830044030
3 x 411.614.7339BX 3X4+B6830044040
3 x 612.815.9416BX 3X6+B6830044050
3 x 1014.918609BX 3X10+B10830044060
3 x 1617.020.1860BX 3X16+B16830044070
3 x 2520.623.71184BX 3X25+B16830044080
3 x 3522.825.91484BX 3X35+B16830044090
3 x 5026.629.72105BX 3X50+B25830044100
3 x 7032.936.32987BX 3X70+B35830044110
3 x 9537.240.83860BX 3X95+B50830044120
3 x 12040.444.24949BX 3X120+B70830044130
3 x 15047.451.56243BX 3X150+B70830044140
3 x 18552.456.77618BX 3X185+B95830044150
3 x 24058.162.89750BX 3X240+B120830044160
3 x 30065.570.511952BX 3X300+B150830044170