Marlew

series BX

0.6/1kV
Flexible Cu 1 up to 300mm²
XLPE 90°C / PVC
IRAM 2178-1

Variable frequency drive motor feed. (VFD) For Alternating Current (50/60Hz), for three-phase systems (380/190V) and systems with voltages up to 1kV. Installed in aerial trays, gutters or conduits, under roof or ladder under roof, buried in ducts or directly buried.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 2178-1 – IEC 60502-1

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: XLPE (Crosslinked polyethylene)

  • Bedding: Double helical wrapping

  • Shield: Composed of a concentric conductor made of copper wires plus an anti-unwinding copper tape. The shield cross-section is indicated in the electrical characteristics table.

  • Sheath: PVC, fire-retardant

  • Flame propagation standard: As per IEC 60332-1

  • Fire spread prevention standard: As per IEC 60332-3-24

  • Outdoors requirements: As per UL 2556 (UV rays)

Electromagnetic interference protection

Electromagnetic interference protection

Flame retardant

Flame retardant

Flexible stranded conductors

Flexible stranded conductors

UV resistant

UV resistant

Sequentially marked

Sequentially marked

Industrial applications

Industrial applications

Identification

Standard
Sheath Conductors
3 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section sq (mm²) Nominal cross-section Concentric conductorsq mm² Electrical resistance at 20°C in C.C.  Ohm/km Electrical resistance at 20°C in C.C. Concentric conductor Ohm/km Electrical resistance at 90°C in C.C. Ohm/km Electrical resistance at 90°C in C.C. Concentric conductor Ohm/km Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Cables displayed in Cable Ladder or perforated tray. (Ampere) Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523. (Ampere)
1619.53.324.864.210.107----
1.5613.33.316.964.210.1002028
2.567.983.310.184.210.0932837
464.953.36.314.210.0883648
663.33.34.214.210.0834761
10101.911.912.442.440.0786583
16161.211.211.541.540.07586107
25160.781.210.991.540.075109141
35160.5541.2100.7071.540.073137168
50250.3860.7800.4930.990.073166199
70350.2720.5540.3480.7070.071213243
95500.2060.3860.2640.4930.070257293
120700.1610.2720.2070.3480.070299333
150700.1290.2720.1670.3480.070345373
185950.1060.2060.1380.2640.070394425
2401200.08010.1610.1060.2070.069465493
3001500.06410.1290.08600.1670.069537559

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) Shield diameter (mm) External diameter mm Weight kg/km Code Mat Number
3 x 17.610.7208BX 3X1+B6830044010
3 x 1.58.111.2224BX 3X1.5+B6830044020
3 x 2.59.012.1257BX 3X2.5+B6830044030
3 x 410.213.3306BX 3X4+B6830044040
3 x 611.314.4365BX 3X6+B6830044050
3 x 1013.416.5533BX 3X10+B10830044060
3 x 1615.618.7745BX 3X16+B16830044070
3 x 2519.222.31017BX 3X25+B16830044080
3 x 3521.724.81296BX 3X35+B16830044090
3 x 5026.329.51850BX 3X50+B25830044100
3 x 7030.333.72519BX 3X70+B35830044110
3 x 9533.4373245BX 3X95+B50830044120
3 x 12037.541.34233BX 3X120+B70830044130
3 x 15046.850.95287BX 3X150+B70830044140
3 x 18550.855.36608BX 3X185+B95830044150
3 x 24058.1638436BX 3X240+B120830044160
3 x 30061.766.710303BX 3X300+B150830044170

The tolerance for the reported diameters shall be between -5% and +8%.