series BSPr U

0.6/1kV
Flexible CU 1.5 up to 150mm²
EPR 90°C / PUR
Includes PE conductor

Power supply of submersible pumps in aggressive environmental conditions such as sewage, contaminated water, various chemicals, oils and salts. Suitable for work in hydrocarbon exploration areas. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 63007

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: EPR

  • Construction: The conductos are arranged parallel line

  • Sheath: Polyurethane, fire-retardant and chemical agents resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Hydrocarbons requirements: As per UIC 895 OR

  • Outdoors requirements: As per UL 2556 (UV rays)

Flame retardant

Flame retardant

Grounded conductor

Grounded conductor

High flexibility

High flexibility

Hydrocarbon resistant

Hydrocarbon resistant

UV resistant

UV resistant

Submersible Pump

Submersible Pump

Identification

Standard
Sheath Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C en C.C. (Ohm/km) Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. (1) (Amper)
1.513.316.960.12619
2.57.9810.180.11826
44.956.310.11234
63.34.210.10545
101.912.440.10362
161.211.540.09883
250.780.990.097122
350.5540.7070.095152
500.3860.4930.094187
700.2720.3480.091241
950.2060.2640.09295
120 (2)0.1610.2070.088346
150 (2)0.1290.1670.088381

(1)  Cables installed in free air at 40ºC according to IEC 364-5-523. These values can be taken as a reference for submerged cable or in contact with water in wells of up to 100 meters deep. For wells deeper than 100 meters, each case must be analyzed in terms of how the cable will be affected by the environment due to temperature ratings, liquids and other conditions which may lower the cable conductivity. For further information on values of current-carrying capacity and types of installation, we suggest consulting IEC 364-5-523 standard. (2)  These cross-sections are out of the scope of IRAM 63007 standard.

DIMENSIONS & WEIGHT

Cable Formation, N° Cond. x cross-section (mm²) External height mm External width mm Weight kg/km Bend ratio mm Code
4 x 1.56.013.110342BSPr 0415 U
4 x 2.56.614.614046BSPr 0425 U
4 x 47.116.018750BSPr 0440 U
4 x 67.717.925054BSPr 0460 U
4 x 109.422.540966BSPr 4100 U
4 x 1610.525.558274BSPr 4160 U
4 x 2512.330.587486BSPr 4250 U
4 x 3513.333.51,16093BSPr 4350 U
4 x 5015.539.31,625109BSPr 4500 U
4 x 7017.745.52,242124BSPr 4700 U
4 x 9520.352.92,938142BSPr 4950 U
4 x 12021.957.33,689153BSPr 41200 U
4 x 15024.765.34,577173BSPr 41500 U