Power supply of submersible pumps used in potable-water wells under 40ºC, in flooded areas, to evacuate swimming pools, to filter or clean the water in tanks or similar sites. For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV
Standard | ||
---|---|---|
Sheath | Conductors | |
4 Conductors |
The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.
Nominal cross-section (mm²) | Electrical resistance at 20°C in C.C. (Ohm/km) | Electrical resistance at 90°C en C.C. (Ohm/km) | Inductive reactance at 50Hz (Ohm/Km) | Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. (1) (Amper) |
---|---|---|---|---|
1.5 | 13.3 | 16.96 | 0.126 | 19 |
2.5 | 7.98 | 10.18 | 0.118 | 26 |
4 | 4.95 | 6.31 | 0.112 | 34 |
6 | 3.3 | 4.21 | 0.105 | 45 |
10 | 1.91 | 2.44 | 0.103 | 62 |
16 | 1.21 | 1.54 | 0.098 | 83 |
25 | 0.78 | 0.99 | 0.097 | 122 |
35 | 0.554 | 0.707 | 0.095 | 152 |
50 | 0.386 | 0.493 | 0.094 | 187 |
70 | 0.272 | 0.348 | 0.091 | 241 |
95 | 0.206 | 0.264 | 0.09 | 295 |
120 (2) | 0.161 | 0.207 | 0.088 | 346 |
150 (2) | 0.129 | 0.167 | 0.088 | 381 |
(1) Cables installed in free air at 40ºC according to IEC 364-5-523. These values can be taken as a reference for submerged cable or in contact with water in wells of up to 100 meters deep. For wells deeper than 100 meters, each case must be analyzed in terms of how the cable will be affected by the environment due to temperature ratings, liquids and other conditions which may lower the cable conductivity. For further information on values of current-carrying capacity and types of installation, we suggest consulting IEC 364-5-523 standard. (2) These cross-sections are out of the scope of IRAM 63007 standard.
Cable Formation N° Cond. x cross-section (mm²) | External height mm | External width mm | Weight kg/km | Bend ratio mm | Code |
---|---|---|---|---|---|
4 x 1.5 | 6.0 | 13.1 | 114 | 42 | BSP 0415 |
4 x 2.5 | 6.6 | 14.6 | 154 | 46 | BSP 0425 |
4 x 4 | 7.1 | 16.0 | 203 | 50 | BSP 0440 |
4 x 6 | 7.7 | 17.9 | 268 | 54 | BSP 0460 |
4 x 10 | 9.4 | 22.5 | 435 | 66 | BSP 4100 |
4 x 16 | 10.5 | 25.5 | 615 | 74 | BSP 4160 |
4 x 25 | 12.3 | 30.5 | 917 | 86 | BSP 4250 |
4 x 35 | 13.3 | 33.5 | 1,208 | 93 | BSP 4350 |
4 x 50 | 15.5 | 39.3 | 1,690 | 109 | BSP 4500 |
4 x 70 | 17.7 | 45.5 | 2,323 | 124 | BSP 4700 |
4 x 95 | 20.3 | 52.9 | 3,042 | 142 | BSP 4950 |
4 x 120 | 21.9 | 57.3 | 3,809 | 153 | BSP 41200 |
4 x 150 | 24.7 | 65.3 | 4,725 | 173 | BSP 41500 |