series AI+

300 Volt
Cu 20 up to 12 AWG
LSZH 90°C / LSZH
UL 1424 FPLR

Fire detection systems and alarm notification, flow and control of automatic water sprinkler systems, Control of building security functions, sensors in elevators, door opening, fan output and control of smoke and smoke protection systems. firewall, intercom systems and public address system. Trays, stairs, conduits and buried. Vertical lines in shafts or tunnels that exceed more than 1 floor (Elevators, Forklifts). In closed places with a high concentrations of people. Indoor and Outdoor use.

Features

  • Temperature rating: 90°C

  • Voltage rating: 300 Volt

  • Construction requirements: As per UL 1424 type FPLR

  • Conductor requirements: As per ASTM B8 Class B

  • Conductor: Annealed electrolytic copper, 7-wire stranding

  • Insulation: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant)

  • Lay length: 50mm (20 twists/m)

  • Unshielded pair: Polyester tape helical wrap

  • Shield: Aluminium-polyester tape wrap plus tinned-copper braid

  • Sheath: LSZH-HFFR (Low Smoke Zero Halogen - Halogen Free Flame Retardant) flame retardant, sunlight, and oil resistant

  • Fire requirements: As per UL 1666 - UL 1685 – IEC 60332-3-24

  • Standard for halogen absence and corrosive gases: As per IEC 60754-1/2

  • Smoke transparency requirements: As per IEC 61034-1/2

  • Toxicity standard: As per NES 713 – CEI 20.37

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Water behaviour requirements: Suitable AD7 (Occasional water submersion)

  • NEC code (NFPA 70): Art. 760 FPLR

Fire-retardant

Fire-retardant

Halogen free

Halogen free

Low smoke

Low smoke

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Special marking

Special marking

Identification

Standard
Sheath Conductors
Pair
Triad
Quad

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Conductor’s gauge Cable structure Shield type Electrical resistance in D.C. at 20°C Mutual capacitance between conductors Characteristic impedance Mutual inductance
AWG ohm/km pf/m ohm microH/km
20Pair / triad / quadUnshielded35.789876588
Shielded18041
18Pair / triad / quadUnshielded22.788588641
Shielded16550
16Pair / triad / quadUnshielded14.2511266544
Shielded21035
14Pair / triad / quadUnshielded8.9410968553
Shielded20337
12Pair / triad / quadUnshielded5.6312162522
Shielded22833

pF/m = Mutual Capacitance between conductors, expressed in picofarad per meter / uH/km = Mutual inductance between conductors, expressed in microhenry per kilometer

DIMENSIONS & WEIGHT

Pair

AWG Shield Drain wire External diameter mm Weight kg/km Code
20----4.931AI+ 0500
Yes225.035AI+ 5000
18----5.641AI+ 0510
Yes225.747AI+ 5100
16----6.254AI+ 0520
Yes226.363AI+ 5200
14----7.784AI+ 0530
Yes227.893AI+ 5300
12----8.7115AI+ 0580
Yes228.8124AI+ 5800

Triad - Individual shielding

AWG Drain wire External diameter mm Weight kg/km Code
20225.343AI+ 6000
18226.059AI+ 6100
16226.781AI+ 6200
14228.3122AI+ 6300
12229.3165AI+ 6800

Quad - Individual shielding

AWG Drain wire External diameter mm Weight kg/km Code
20225.752AI+ 9000
18226.572AI+ 9100
16227.5104AI+ 9200
14229.0151AI+ 9300
122210.7221AI+ 9800