Marlew

series BSPU

0.6/1kV
Flexible CU 1.5 up to 150mm²
EPR 90°C / PUR
Includes PE conductor

For Alternating Current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Power supply of submersible pumps in aggressive environmental conditions such as sewage, contaminated water, various chemicals, oils and salts. Suitable for work in hydrocarbon exploration areas.

Features

  • Temperature rating: 90ºC (operating), 130ºC (overload), 250ºC (short circuit)

  • Voltage rating: 600/1000V AC, maximum 1200V AC / 1500V DC

  • Construction requirements: As per IRAM 63007

  • Conductor requirements: As per IRAM NM 280 – IEC 60228

  • Conductor: Annealed electrolytic copper - Flexible stranding class 5

  • Insulation: EPR

  • Construction: The conductos are arranged parallel line

  • Sheath: Polyurethane, fire-retardant and chemical agents resistant

  • Fire requirements: As per IEC 60332-1

  • Oils requirements: As per ICEA S 73-532

  • Hydrocarbons requirements: As per UIC 895 OR

  • Outdoors requirements: As per UL 2556 (UV rays)

  • Permanent immersion test in water: AD8

Flame retardant

Flame retardant

High flexibility

High flexibility

UV resistant

UV resistant

Hydrocarbon resistant

Hydrocarbon resistant

Submersible Pump

Submersible Pump

Diving up to 800 meters

Diving up to 800 meters

Identification

Estandar
Cubierta Conductores
3 Conductors
4 Conductors

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering materials can be used upon request.

ELECTRICAL CHARACTERISTICS

Resistances, reactance and intensity of admissible currents

Nominal cross-section (mm²) Electrical resistance at 20°C in C.C.  (Ohm/km) Electrical resistance at 90°C en C.C. (Ohm/km) Inductive reactance at 50Hz (Ohm/Km) Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. (1) (Amper)
1.513.316.960.12619
2.57.9810.180.11826
44.956.310.11234
63.34.210.10545
101.912.440.10362
161.211.540.09883
250.780.990.097122
350.5540.7070.095152
500.3860.4930.094187
700.2720.3480.091241
950.2060.2640.09295
120 (2)0.1610.2070.088346
150 (2)0.1290.1670.088381

(1) Cables installed in air at 40ºC according to IEC 364-5-523. These values can be taken as a reference for cables submerged or in contact with water in wells up to 100 meters deep. When it comes to depths greater than 100 meters, each particular case must be studied as to how the cable will be affected by the environment due to temperatures, liquids and other conditions that may impair the conduction of the cable.For more information on allowable intensity values and types of installation, we suggest consulting the IEC 364-5-523 standard.(2) These sections are outside the scope of IRAM 63007.

DIMENSIONS & WEIGHT

Final height Final width Weight Radius of curvature Code
mm mm kg/km mm
6.013.111442BSPU 3x1.5
6.614.615446BSPU 3x2.5
7.0516.020349BSPU 3x4
7.717.926854BSPU 3x6
9.422.543565BSPU 3x10
10.525.561574BSPU 3x16
12.330.591786BSPU 3x25
13.333.51,20893BSPU 3x35
15.539.31,690109BSPU 3x50
17.745.52,323124BSPU 3x70
20.352.93,042142BSPU 3x95
21.957.33,809153BSPU 3x120
24.765.34,725173BSPU 3x150
6.013.110342BSPU 3x1.5+PE1.5
6.614.614046BSPU 3x2.5+PE2.5
7.116.018750BSPU 3x4+PE4
7.717.925054BSPU 3x6+PE6
9.422.540966BSPU 3x10+PE10
10.525.558274BSPU 3x16+PE16
12.330.587486BSPU 3x25+PE25
13.333.51,16093BSPU 3x35+PE35
15.539.31,625109BSPU 3x50+PE50
17.745.52,242124BSPU 3x70+PE70
20.352.92,938142BSPU 3x95+PE95
21.957.33,689153BSPU 3x120+PE120