Clad series SB-RS 485

Steel wire armour (SWA)

300 Volt
Cu 24 AWG
UL 13
RS 485 System

Suitable for Fieldbus distribution circuits in RS 485 systems. Through this system a multiple-node net can be interconnected by means of a paired cable, which allows bi-directional communication, significant length of the interconnection cable and high speed data transmission. Installed in conduits, trays, cable ladders, in direct open air or indoors, buried in a trench or in ducts. It has additional mechanical protection.

Features

  • Temperature rating: 75°C

  • Voltage rating:: 300 Volt

  • Construction requirements: As per UL13

  • Conductor requirements: As per ASTM B8 Clase B

  • Conductor: Tinned annealed electrolytic copper, 7-wire stranding

  • Insulation: Thermoplastic compound

  • Lay length: 50mm (20 twists/m)

  • Shield: Aluminium-polyester tape wrap (100% coverage) plus tinned-copper braid (90% coverage)

  • Armour: Galvanized steel wire armour

  • Sheath: Flame retardant PVC; sunlight and hydrocarbon-resistant

  • Fire requirements: As per UL 1685

  • Hydrocarbons standard: As per NFC 32-200 – ASTM D 1239

  • Oils requirements: As per ICEA S 73-532

  • Outdoors requirements: As per UL 2556 (UV rays)

  • NEC code (NFPA 70): Art. 725 PLTC – Art. 727 ITC – Art. 800 CM – Art. 501 classified areas CL1 Div.2 y Cl2 Div.2

  • Connection: The maximum length for the RS 485 cable is 1200 meters , without the use of amplifiers. For longer distances, a signal re-generation and amplification device must be used. The RS485 is a bus series cable, therefore, the installation of equipment in star or ring is not allowed . It is recommended to avoid the passage of these cables near cables and power equipment, which produce electromagnetic induction which may cause the system malfunction.

Electromagnetic interference protection

Electromagnetic interference protection

Double shielding

Double shielding

Fire-retardant

Fire-retardant

Hydrocarbon resistant

Hydrocarbon resistant

Mineral oil resistant

Mineral oil resistant

UV resistant

UV resistant

Identification

Standard
Sheath Conductors
1 Pair
2 Pairs
3 Pairs
4 Pairs

Instalation

falta label en campo?
falta label en campo?
falta label en campo?

Constructive variants

The information provided corresponds to the standard version, and different alternatives of insulation and / or covering can be used upon request.

ELECTRICAL CHARACTERISTICS, DIMENSIONS & WEIGHT

Number of pairs Gauge Electrical resistance in D.C. at 20°C Velocity of propagation Impedancia característica Mutual capacitance Diameter under armour External diameter Weight Code
AWG ohm/km VP (%) Ohm pF/m pF/ft mm mm kg/km
12492.7661204413.46.610.7231SB 9701 H
28.712.9304SB 9702 H
39.413.5335SB 9703 H
410.714.8389SB 9704 H

pF/m: Mutual Capacitance between conductors of the same pair, expressed in picofarad per meter. pF/ft: Mutual Capacitance between conductors of the same pair, expressed in picofarad per feet.