For fixed power distribution networks for alternating current (50/60Hz), for single-phase systems (220/110V), three-phase systems (380/190V) and systems with voltages up to 1kV. For Direct Current, used in systems with voltages up to 1.5kV Use in closed environments with a high concentration of people (airports, hospitals, trains, cinemas, shopping centers, tunnels) and in control rooms with electronic equipment sensitive to the exposure of corrosive gases. Installed in conduits, trays, cable ladders, in direct open air or indoors, buried in a trench or in ducts.
Standard | ||
---|---|---|
Sheath | Conductors | |
3 Conductors | ||
4 Conductors | ||
5 Conductors |
The information provided corresponds to the standard version. Special design can be manufactured to comply with reinforced circuit integrity, complying with other standards such as IEC 60331-1/2, EN 50200 or BS 6387.
Nominal cross-section (mm²) | Electrical resistance in D.C. at 20°C (Ohm/km) | Electrical resistance in C.C. at 90°C (Ohm/km) | Inductive reactance at 50Hz (Ohm/Km) | Current-carrying capacity of cables in free air at 40°C as per IEC 364-5-523. Formations in cable ladder or perforated cable trays (Ampere) | Current-carrying capacity of cables directly buried at 25°C soil temperature and soil thermal resistance of 1 km/W as per IEC 364-5-523 (Ampere) | |||
---|---|---|---|---|---|---|---|---|
Multiconductor (1) | 4 Conductors (2) | 2 Conductors (3) | Multiconductor (4) | 2 Conductors (3) | Multiconductor (4) | |||
1 | 19.5 | 24.86 | 0.119 | 0.126 | -- | -- | -- | -- |
1.5 | 13.3 | 16.96 | 0.111 | 0.118 | 23 | 20 | 32 | 28 |
2.5 | 7.98 | 10.18 | 0.103 | 0.110 | 31 | 28 | 44 | 37 |
4 | 4.95 | 6.31 | 0.097 | 0.105 | 43 | 36 | 57 | 48 |
6 | 3.3 | 4.21 | 0.090 | 0.098 | 54 | 47 | 72 | 61 |
10 | 1.91 | 2.44 | 0.084 | 0.091 | 74 | 65 | 97 | 83 |
16 | 1.21 | 1.54 | 0.082 | 0.089 | 100 | 86 | 129 | 107 |
25 | 0.78 | 0.99 | 0.079 | 0.087 | 128 | 109 | 166 | 141 |
35 | 0.554 | 0.707 | 0.077 | 0.084 | 160 | 137 | 200 | 168 |
50 | 0.386 | 0.493 | 0.076 | 0.083 | 195 | 166 | 238 | 199 |
70 | 0.272 | 0.348 | 0.074 | 0.082 | 250 | 213 | 292 | 243 |
95 | 0.206 | 0.264 | 0.072 | 0.079 | 304 | 257 | 351 | 293 |
120 | 0.161 | 0.207 | 0.072 | 0.079 | 354 | 299 | 399 | 333 |
150 | 0.129 | 0.167 | 0.071 | 0.079 | 409 | 345 | 448 | 373 |
185 | 0.106 | 0.138 | 0.072 | 0.079 | 468 | 394 | 508 | 425 |
240 | 0.0801 | 0.106 | 0.071 | 0.078 | 554 | 465 | 592 | 493 |
300 | 0.0641 | 0.0860 | 0.070 | 0.077 | 640 | 537 | 669 | 559 |
(1) Calculation of Inductive reactance valid for three-conductor and five-conductor cables. (2) Calculation of Inductive reactance valid for four-conductor cables. (3) The values of current-carrying capacity informed, correspond to three conductor cable (two-conductor + protection conductor). (4) The values of current-carrying capacity informed, correspond to four-conductor, five-conductor.
Cable Formation, N° Cond. x cross-section (mm²) | External diameter mm | Weight kg/km | Code |
---|---|---|---|
3 x 1 | 9.9 | 124.0 | RPC 0310 |
3 x 1.5 | 10.6 | 146 | RPC 0315 |
3 x 2.5 | 11.6 | 187 | RPC 0325 |
3 x 4 | 12.6 | 244 | RPC 0340 |
3 x 6 | 13.9 | 317 | RPC 0360 |
3 x 10 | 16.1 | 472 | RPC 3100 |
3 x 16 | 21.3 | 799.0 | RPC 3160 |
3 x 25 | 24.2 | 1122.0 | RPC 3250 |
3 x 35 | 26.4 | 1448.0 | RPC 3350 |
3 x 50 | 30 | 1957 | RPC 3500 |
3 x 70 | 35.3 | 2715 | RPC 3700 |
3 x 95 | 39.8 | 3475 | RPC 3950 |
3 x 120 | 43.7 | 4371.0 | RPC 31200 |
3 x 150 | 49.8 | 5469 | RPC 31500 |
3 x 185 | 53.9 | 6545 | RPC 31850 |
3 x 240 | 61.6 | 8571 | RPC 32400 |
3 x 300 | 68.7 | 10671.0 | RPC 33000 |
4 x 1 | 10.8 | 145 | RPC 0410 |
4 x 1.5 | 11.5 | 171 | RPC 0415 |
4 x 2.5 | 12.6 | 222 | RPC 0425 |
4 x 4 | 13.8 | 295 | RPC 0440 |
4 x 6 | 15.3 | 385 | RPC 0460 |
4 x 10 | 17.7 | 581.0 | RPC 4100 |
4 x 16 | 23.2 | 974.0 | RPC 4160 |
3 x 25 + 1 x 16 | 25.6 | 1279.0 | RPC 2516 |
3 x 35 + 1 x 16 | 27.5 | 1590 | RPC 3516 |
3 x 50 + 1 x 25 | 31.3 | 2174 | RPC 5025 |
3 x 70 + 1 x 35 | 36.5 | 2999 | RPC 7035 |
3 x 95 + 1 x 50 | 41.5 | 3901.0 | RPC 9550 |
3 x 120 + 1 x 70 | 46.1 | 4992 | RPC 12070 |
3 x 150 + 1 x 70 | 51.2 | 6004 | RPC 15070 |
3 x 185 + 1 x 95 | 56.0 | 7297 | RPC 18595 |
3 x 240 + 1 x 120 | 63.7 | 9512.0 | RPC 240120 |
3 x 300 + 1 x 150 | 71.2 | 11832 | RPC 300150 |
5 x 1 | 11.7 | 165 | RPC 0510 |
5 x 1.5 | 12.5 | 198 | RPC 0515 |
5 x 2.5 | 13.7 | 260 | RPC 0525 |
5 x 4 | 15 | 347 | RPC 0540 |
5 x 6 | 16.7 | 457.0 | RPC 0560 |
5 x 10 | 19.4 | 694.0 | RPC 5100 |
5 x 16 | 215.2 | 1156.0 | RPC 5160 |
5 x 25 | 28.9 | 1650 | RPC 5250 |
5 x 35 | 31.6 | 2159 | RPC 5350 |
5 x 50 | 36.9 | 3011 | RPC 5500 |
5 x 70 | 43 | 4131.0 | RPC 5700 |
5 x 95 | 49.2 | 5364 | RPC 5950 |
5 x 120 | 53.9 | 6767 | RPC 51200 |
5 x 150 | 61.0 | 8367 | RPC 51500 |
5 x 185 | 66.6 | 10129.0 | RPC 51850 |
5 x 240 | 75.7 | 13174 | RPC 52400 |
5 x 300 | 84.9 | 16481 | RPC 53000 |